| 1 | Aerosol Based Fire ExtinguisherSupply & Installation 8 gm Portable Aerosol based Automatic Fire Shield (Coverage: 0.08 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Firepro/Stat-x/Equivalent |
| 2 | Supply & Installation of 20 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.2 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Firepro/Stat-x/Equivalent |
| 3 | Supply & Installation of 30 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.3 m3) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Firepro/Stat-x/Equivalent |
| 4 | Supply & Installation of 50 gm aerosol based Manual Fire Extinguisher (Duration:10-20 sec) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 5 years. Make-Pyrogen/Firepro/Stat-x/Equivalent |
| 5 | SITC of 2 kg capacity Eco friendly stored pressure type filled with HFC 236(Clean agent fire extinguisher having zero ozone depletion potential) clean agent fire extinguisher s with safety seal,pressure gauge, controlable discharge mechanism helium leak detection tested and confirming to IS:15683 complete with initial charge as required. Make : Fireshield/Kanex/ Safex/ ceasefire/Flameklog |
| 6 | Supply & Installation of 3.3 Kg Manual aerosol based Fire Extinguisher covering 150m3 for big fire (Throwable unit) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Firepro/Stat-x/Equivalent |
| 7 | Supply and Installation of linear heat detection cable compatible with aerosol based fire extinguisher as per direction of Engineer-in-charge.Make-Make-Pyrogen/ Firepro/Stat-x |
| 8 | Pressurization System for LiftsSupply, Installing, Testing and Commissioning of VANE AXIAL FANS as per specifications stated below. Fan shall be direct driven Vane axial fan , IP55, AMCA Certified (For Air and Sound Performance as well as FEG). The fan shall be equipped with mounting bracket, inlet guard (If required) & spring isolators for the installation of the fans. Motors shall be VFD Compatible suitable for 415+10% volts, 50 cycles, 3 phase AC supply. Fan static pressure shall be as indicated but actual fan static pressure to be checked by HVAC / MEP Vendor. Supply Fans shall be activated from fire signal from fire alarm system. Fan shall be with fire proof flexible connection at outlet. Motors shall be of minimum IE2 efficiency, class F insulation. Fan total efficiency should not be less than 72% and FEG should not be less than 85, noise level should not be more than 84 dB(A) @ 3m distance when measured in hemispherical reverberant room conditions. Sound attenutors of appropriate length shall be included in the cost to achieve the desired result.The differential pressure should be maintained as per NBC 2016. MAKE - SYSTEMAIR/ GREENHECK/ ELTA/Krugger/Nikotra18600 cfm ,30 mm Static pressure for Lift well/Lift lobby |
| 9 | Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BMS. All starters shall be provided with potential free Contact for Connections to Building Automation System.Over-load relay, suitable for motor duty and able to withstand fault level of suitable KA rating.single phase preventer (Electronics type) as per the ratings given below.Terminal block for power distribution.Power Contactor.Phase indicating lights and indicating light for ON/OFF/TRIP status phase sequence relay shall also be provided.Time delay relay for delayed automatic restart of motor (0-180 sec).Integration with fire alarm detection system and fire damper for starting / stopping the fan (in case of fire) / Power supply for damper control panel.For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation.All starters shall be provided with suitable potential free contract for connections to the Building Automation System.The number of control panels shall be as follows.Make (Switchgear) - ( MCCB : Make-Legrand-(DPX3)/Schneider-(CVS)/Siemens-(3VA) /ABB (Formula), MCB : Make-Legrand-(DX3)/Schneider-(Acti9)/Siemens-(betagard)/ ABB (SB200)Make of VFD-Siemens/Schneider/ABB16/25/32/63A 4P MPCB with 5/10/15 HP Three phase VFD with bypass star delta/DOL starter with overload relay and single phase preventer . Each of these compartment shall contain indicating lamp with ON/ OFF/ TRIP status for fan sections/axial fans.The price is inclusive fire control relay module. |
| 10 | Supply & Fixing of Air Distribution Duting fabricated with Class VI GI Sheet(180 GSM) Complete With Supports, dampers, guiding vanes, access doors, MS Angle, Fire inhibiting gaskets, Nuts, bolts and all oyher accessories in accordance with approved drawing and the Specification. (Make:- Jindal/ Sail/ Tata)22 G (0.8 mm) |
| 11 | 20 G (1 mm) |
| 12 | S/I/T&Commissioning of CPRI Approved LT Outdoor floor mounted cubical type electrical pressurization panel made out by 2mm CRCA steel sheet duly derusted & pented by simens gray powder cote paint is designed as G.A drawing as per direction of Engg.-in-Charge.20x10mm separate aluminium earth busbar is to be provided.ON/OFF/TRIP indication for all the feeders is to be provided.Mandatory provision of cable alley is to be given. In commer- 01 number of 200 Amps 4P TMR MCCB,25KA, Ics=100%Icu Busbar- 04 numbers of 250Amps Aluminium busbar duly sleeved by color coaded PVC sleeve and 01 no. busbar for Earthing & supported by suitable size DMC insulator Out going- (i) 63A,16KA 4P TMR MCCB, Ics=100%Icu, 6 nos (ii) 63A 4P MCB, C series, 10 kA- 3 nos Instrument- (i) phase indicating lamp with HRC fuse for the incomer.(ii) 01 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication(iii) 01 set of 40KA TYPE 2 3P+N SPD along with 63A 4P MCB C series, 10 kA.Make of MCCB-Legrand(DPX3)/ABB-Formula/Schneider-CVS/Siemens-3VAMake of MCB-Legrand(DX3)/ABB SB200/Schneider-Acti 9/Siemens-BetaguardMake of SPD-Legrand/Siemens/Schneider/ABB/OBO/DEHN |
| 13 | Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in confirmation to IS and as per specifications complete etc. as required as per the direction of Engineer-in-charge..(Make: Air Flow/ Systemair/ Dynacraft)a) Fire Dampers |
| 14 | b) Actuators (Make:- Belimo/ Siemens/ Danfoss) |
| 15 | Supply of 95 sq.mm 3 & 1/2 core XLPE Aluminium FRLS Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster) |
| 16 | Supply and laying of 6 sq.mm 4 core XLPE copper FRLS Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster) |
| 17 | Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm on surface as required. |
| 18 | S/IT/C of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 19 | Supplying and laying of 6SWG GI wire ISI marked on surface or in recess for connection etc as required. Please Enable Macros to View BoQ information |