| 1 | BUILDINGS & STRUCTURE (Sch 'A' PART-I) |
| 2 | Lump sum price worked out by the Contractor for “BUILDINGS & STRUCTURE” as listed in Schedule ‘A’ Part-I. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.6,37,70,000.00 inserted by the MES in Schedule ‘A’ Part-I. |
| 3 | EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT (Sch 'A' PART-II) |
| 4 | Lump sum price worked out by the Contractor for “EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT” as listed in Schedule ‘A’ Part-II. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.1,11,30,888.65 inserted by the MES in Schedule ‘A’ Part-II. |
| 5 | INTERNAL WATER SUPPLY (Sch 'A' PART-III) |
| 6 | Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-III. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.14,013.48 inserted by the MES in Schedule ‘A’ Part-III. |
| 7 | INTERNAL ELECTRIFICATION (Sch 'A' PART-IV) |
| 8 | Lump sum price worked out by the Contractor for “(INTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-IV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 5,73,137.95 inserted by the MES in Schedule ‘A’ Part-IV. |
| 9 | ROAD, PATH, CULVERT & HARDSTANDING (Sch 'A' PART-V) |
| 10 | Lump sum price worked out by the Contractor for “(ROAD, PATH, CULVERT & HARDSTANDING)” as listed in Schedule ‘A’ Part-V. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 79,45,300.36 inserted by the MES in Schedule ‘A’ Part-V. |
| 11 | AREA DRAINAGE (Sch 'A' Part-VI) |
| 12 | Lump sum price worked out by the Contractor for “(AREA DRAINAGE)” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 60,37,276.00 inserted by the MES in Schedule ‘A’ Part-VI. |
| 13 | SEWAGE DISPOSAL (Sch 'A' PART-VII) |
| 14 | Lump sum price worked out by the Contractor for “(SEWAGE DISPOSAL)” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 54,784.87 inserted by the MES in Schedule ‘A’ Part-VII. |
| 15 | EXTERNAL WATER SUPPLY (Sch 'A' Part-VIII) |
| 16 | Lump sum price worked out by the Contractor for “(EXTERNAL WATER SUPPLY)” as listed in Schedule ‘A’ Part-VIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 36,37,942.90 inserted by the MES in Schedule ‘A’ Part-VIII. |
| 17 | EXTERNAL ELECTRIFICATION (Sch 'A' PART-IX) |
| 18 | Lump sum price worked out by the Contractor for “(EXTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-IX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 47,63,314.52 inserted by the MES in Schedule ‘A’ Part-IX. |
| 19 | FIRE FIGHTING (Sch 'A' Part-X) |
| 20 | Lump sum price worked out by the Contractor for “(FIRE FIGHTING)” as listed in Schedule ‘A’ Part-X. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 46,58,605.41 inserted by the MES in Schedule ‘A’ Part-X. |
| 21 | (PROTECTIVE WORK, BOUNDARY WALL, RETAINING WALL, STEEL GATE AND FENCING) (Sch 'A' Part-XI) |
| 22 | Lump sum price worked out by the Contractor for “(PROTECTIVE WORK, BOUNDARY WALL, RETAINING WALL, STEEL GATE AND FENCING)” as listed in Schedule ‘A’ Part-XI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,17,59,837.29 inserted by the MES in Schedule ‘A’ Part-XI. |
| 23 | LIGHTNING PROTECTION (Sch 'A' Part-XII) |
| 24 | Lump sum price worked out by the Contractor for “(LIGHTNING PROTECTION) ” as listed in Schedule ‘A’ Part-XII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 5,47,751.00 inserted by the MES in Schedule ‘A’ Part-XII. |
| 25 | DG SET (Sch 'A' Part-XIII) |
| 26 | Lump sum price worked out by the Contractor for “(DG SET)” as listed in Schedule ‘A’ Part-XIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 45,437.40inserted by the MES in Schedule ‘A’ Part-XIII. |
| 27 | MISCELLANEOUS ITEMS REQUIRED FOR B/R & E/M SERVICES (Sch 'A' Part-XIV) |
| 28 | INTERNAL WATER SUPPLYS&F two way bib cock with wall flange chromium plated with crutch or butterfly handle screwed down for iron pipe 20 mm bore and fixed complete all as specified and as directed. |
| 29 | INTERNAL ELECTRIFICATIONS & F 3 star (EEL) LED lamp 5w capable to output 525im, 6500k suitable base B22 type complete all as specified and directed. |
| 30 | S&F Flame proof distribution board 8 way with connected accessories prewired complete all as specified & directed. |
| 31 | S&F Flame proof metallic junction box 4 way, threaded type complete all as specified & directed. |
| 32 | S&F Flame proof flexible metallic hose conduit 20mm dia, 500mm long complete all as specified & directed. |
| 33 | S & F Modular type RJ-11 telephone socket outlet in the modular MS/GI sheet box and cover plate including concealed 25 mm PVC conduit in wall/ceiling/fixed to roof , connections etc complete all as specified and directed. |
| 34 | SEWAGE DISPOSALOn site LLDPE septic tank for 10 users with (up flow filter including media) designed to carry sewage and sludge water including excavation in any type of soil, PCC (1:4:8) below foundation, vent shaft, connection etc complete all as specified and directed. |
| 35 | Construction of soakage well including excavation in ordinary soil foundation on PCC (1:3:6) walls of honey combed and solid M-25 concrete intercepting chambers, screen chambers, brick work in CM (1:4), RCC cover slab in M-25/RR masonry / filling with brick baths complete of size 1.8 m dia, 3.0 m deep complete all as specified and directed. |
| 36 | PROTECTIVE WORK, BOUNDARY WALL, STEEL GATE AND FENCINGConstruction of Steel Gate 5.5 m wide and 2.3 m height with RCC M-25 Columns with foundation with necessary earthwork, PCC below foundation, plastering, painting complete all as specified alongwith 1.2 m wide wicket gate complete all as specified and shown on drawing No. CESZ/TD/72 Sheet No. 1/2 & 2/2.. |
| 37 | EXTERNAL ELECTRIFICATIONS & F and commissioning of outdoor factory made weather and vermin proof, CPRI approved MS cubical LT panel, fabricated with 3.15 mm thick MS sheet for outer and 1.6 mm thick for inner shell & zinc metal powder coated paint over a coat of primer red oxide and reqd capacity of aluminium bus bar channel insulated with heat shrinkable sleaves and mounted on epoxy insulator of reqd size in conical type, double door be provided with proper hinged incl locking arrangements, provn of suitable cable ducts at bottom and control wire of 2.5 sqmm multi stranded copper conductor with adequate size of lugs be properly bunched. The cubical panel be fixed on PCC (1:2:4) type B1 foundation of reqd size. The compart-mentalized to accommodated to incomer and outgoing MCCBs, MCB's and measuring eqpt and separate door will cover to each MCCB incl suitable space for accomodate the followings :- (a) Incomer - ACB 4 pole 630 Amp, 50 Hz 415 V AC with rupturing cap 50 KA - 01 Nos (b) Outgoing - (i) MCCB 4 pole 400 Amps 50Hz 415 Volt AC 25 KA -01 Nos (ii) MCCB 4 pole 125 Amps 50Hz 415 Volt AC 16 KA -02 Nos (iii) Aluminium bus bar 500 Amp 04 Nos -01 Set (iv) Voltmeter - 01 Nos (v) Ammeter - 01 Nos (vi) LED type indicator to indicate R,Y,B phase (Main LTP) |
| 38 | S & F and commissioning of outdoor factory made weather and vermin proof, CPRI approved, MS cubical LT panel, fabricated with 3.15 mm thick MS sheet for outer and 1.6 mm thick for inner shell & zinc metal powder coated paint over a coat of primer red oxide and reqd capacity of aluminium bus bar channel insulated with heat shrinkable sleaves and mounted on epoxy insulator of reqd size in conical type, double door be provided with proper hinged incl locking arrangements, provn of suitable cable ducts at bottom and control wire of 2.5 sqmm multi stranded copper conductor with adequate size of lugs be properly bunched. The cubical panel be fixed on PCC (1:2:4) type B1 foundation of reqd size. The compart-mentalized to accommodated to incomer and outgoing MCCBs, MCB's and measuring eqpt and separate door will cover to each MCCB incl suitable space for accomodate the followings :- (a) Incomer - MCCB 4 pole 400 Amp, 50 Hz 415 V AC with rupturing cap 50 KA - 01 Nos (b) Outgoing - (i) MCCB 4 pole 125 Amps 50Hz 415 Volt AC 16 KA -02 Nos (ii) MCCB 4 pole 63 Amps 50Hz 415 Volt AC 16 KA -02 Nos(iii) Aluminium bus bar 300 Amp 04 Nos -01 Set (iv) Voltmeter - 01 Nos (v) Ammeter - 01 Nos (vi) LED type indicator to indicate R,Y,B phase (Fire Fighting) |
| 39 | S & F and commissioning of outdoor factory made weather and vermin proof, CPRI approved, MS cubical LT panel, fabricated with 3.15 mm thick MS sheet for outer and 1.6 mm thick for inner shell & zinc metal powder coated paint over a coat of primer red oxide and reqd capacity of aluminium bus bar channel insulated with heat shrinkable sleaves and mounted on epoxy insulator of reqd size in conical type, double door be provided with proper hinged incl locking arrangements, provn of suitable cable ducts at bottom and control wire of 2.5 sqmm multi stranded copper conductor with adequate size of lugs be properly bunched. The cubical panel be fixed on PCC (1:2:4) type B1 foundation of reqd size. The compart-mentalized to accommodated to incomer and outgoing MCCBs, MCB's and measuring eqpt and separate door will cover to each MCCB incl suitable space for accomodate the followings :- (a) Incomming - MCCB 4 pole 125 Amp, 50 Hz 415 V AC with rupturing cap 50 KA - 01 Nos (b) Outgoing - (i) MCCB 4 pole 63 Amps 50Hz 415 Volt AC 16 KA -02 Nos (ii) MCCB 4 pole 40 Amps 50Hz 415 Volt AC 16 KA -02 Nos(iii) Aluminium bus bar 300 Amp 04 Nos -01 Set (iv) Voltmeter - 01 Nos (v) Ammeter - 01 Nos (vi) LED type indicator to indicate R,Y,B phase (For ESH) |
| 40 | S&F of kiosk box for luminaires ,weather proof made out of PVC/HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole mounting type comprising of 4 pole copper connectors of 16 Amps with 6 Amp MCB single pole , of minimum size of panel is 300x200x125mm, IP 54 fixed on pole with MS, clamps 30x5mm with necessary nuts, washer Make Sintex/Universal SG/Finplex/Hansel and incl. applying two coats of synthetic enamel paint over a red oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. Please Enable Macros to View BoQ information |
| 41 | S&F of kiosk box for luminaires ,weather proof made out of PVC/HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole mounting type comprising of 4 pole copper connectors of 16 Amps with 6 Amp MCB single pole , of minimum size of panel is 300x200x125mm, IP 54 fixed on pole with MS, clamps 30x5mm with necessary nuts, washer Make Sintex/Universal SG/Finplex/Hansel and incl. applying two coats of synthetic enamel paint over a red oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. Please Enable Macros to View BoQ information |