| 1 | Excavation in trenches in soft/ loose soil n.exc 1.5 Mtr deep and n.exc 1.5 mtr wide for laying of cable and getting out including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed. |
| 2 | Returning, filling, including leveling, watering and well ramming excavated soil in layers n.exc 25cm thick in trenches after cable have been laid complete all as specified and directed. |
| 3 | Removing of excavated surplus soil obtained from excavation to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr of the starting point complete all as specified and directed . |
| 4 | M&L for sub class 'B' old size of Brick in trenches for cable protection of LT Cables, complete all as specified and directed. |
| 5 | M&L for Sand filling under floors or in foundations including watering and consolidation for UG cable complete all as specified and directed. |
| 6 | Taking down/ out unserviceable UG cables of any cross sectional area and connections including Bricks, GI Pipes, etc of any descriptions, laid in trenches and/or fixing with walls/poles including segregating of serviceable materials viz Bricks, cables, GI Pipes etc complete all as specefied and directed. |
| 7 | Supply, laying, jointing and testing of cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade of size 25 Sqmm 4 core confirming to IS: 7098 (Part - I) laid in trenches, under road or passing through pipes/ducts or fixed to walls/poles complete with proper thimbles complete all as specified and directed. |
| 8 | Supply, laying, jointing and testing of cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade of size 10 Sqmm 2 core confirming to IS: 7098 (Part - I) laid in trenches, under road or passing through pipes/ ducts or fixed to walls/ poles complete with proper thimbles complete all as specified and directed. |
| 9 | S&F in repair 1100 volts grade heavy duty 10 Sqmm two core service cable PVC insulated aluminium Stranded conductor, served with inner shething of PVC sheathed in service conections suspended by insulating hangers and procelean beat not more than I metre apart including 4Sq mm suspension wire, one twin core cable flat or circular, complete all as specified and directed.Make: KEI/ Havells/ Polycab or equivalent as approved. |
| 10 | S&F in repair 1100 volts grade heavy duty 16 Sq mm two core service cable PVC insulated aluminium Stranded conductor, served with inner shething of PVC sheathed in service conections suspended by insulating hangers and procelean beat not more than I metre apart including 4Sqmm suspension wire, one twin core cable flat or circular, complete all as specified and directed.Make: KEI/ Havells/ Polycab or equivalent as approved. |
| 11 | S&F in repair for GI pipe light grade of size 80mm dia laying in trenches/ under floor/on walls for protection of UG cables complete all as specified and directed |
| 12 | S&F in repair for GI pipe light grade of size 40mm dia laying in trenches/ under floor/ on Poles for protection of UG cables with and 02 pair of MS clamps made out 40x5mm MS flat iron bolts, nuts to be fitted on pole (Only), complete all as specified and directed. |
| 13 | S&F of ACB 4 Pole, 415 V, with thermal magnetic release (Manual Fixed type) of capacity 630 Amps AC, 50 C/S, fixed in repair, complete all as specified and directed. |
| 14 | S&F of MCCB capacity of 100 Amps, Adjustable Type 4 pole, 415volt, 50Hz, rupturing capacity 16 KA (minimum) or higher, AC, 50 C/S, fixed in repairs, complete all as specified and directed. |
| 15 | S&F of MCCB capacity of 60 Amps, Adjustable Type 4 pole, 415volt, 50Hz, rupturing capacity 16 KA (minimum) or higher, AC, 50 C/S, fixed in repairs, complete all as specified and directed. |
| 16 | M&L for painting of LT Panel of size 1sqm to 1.8sqm, complete with two coats of synthetic enamel paints over a coat of red oxide as per required at site complete all as specified and directed. |
| 17 | Supply, installation, testing and commissioning factory made, LT bus bar panel board cubical, Outdoor type, floor/ground mounted double door, 3 phase 4 wire, 50 cycles, 415 Volts.The panel board shall be made of 3.15 thick CRCA sheet of suitable size as per requirement, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY Structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plate with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof. Base frame of the panel shall be made of angle iron of size 50 x50 x 6mm of upto 1/2 mtr height from GL& 1/2 mtr for Below GL in PCC 1:3:6, type C-2, using 40mm graded crushed stone aggregate comprising of following:- |
| 18 | The panel board shall be suitable for AC, 415 Volt, 50 Hz, 3 phase, 4 wire supply complete with and comprising of the following:- (i) Epoxy insulated common aluminium bus bar of capacity 630 Amp TPN each with Color Coding , including aluminium lugs to connect the cable. (ii) MCCB 4 Pole, 415 V, Adjustable type, 350 Amps with breaking capacity 36 KA - 01 No (For main Incomming )(iii) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA - 01 No (For main Incomming )(iv) Onload Changeover Switch 250 Amps 4 pole with handle to be fitted properly inside Panel - 01 No (v) Volt Meter 0 - 500 Volts digital type square shape flush mounted with selector switch - 1 No(vi) Ammeter 0 - 400 Amps digital type square shape 96mm flush mounted with selector switch and CT's 400/5 A - 1 No.(vii) Indicator lamp RYB : 01 Set of three complete |
| 19 | S&F Bus bar chamber made out of from CRCA sheet 2 mm thick including making concealed in the wall with nuts and bolts and color wash to match with exsting, powder coated of size 600x450x150mm in IP-65 consisting of the following :- (a) Incoming MCCB 125 Amp 4 pole 16 KA, 415 V- 01 No (b) Outgoing Alluminium Bus bar duly insulated RBY and Black- 01 Set (c) LED indicator RYB - 01 Set of three complete Please Enable Macros to View BoQ information |
| 20 | S&F Bus bar chamber made out of from CRCA sheet 2 mm thick including making concealed in the wall with nuts and bolts and color wash to match with exsting, powder coated of size 600x450x150mm in IP-65 consisting of the following :- (a) Incoming MCCB 125 Amp 4 pole 16 KA, 415 V- 01 No (b) Outgoing Alluminium Bus bar duly insulated RBY and Black- 01 Set (c) LED indicator RYB - 01 Set of three complete Please Enable Macros to View BoQ information |