| 1 | Taking down carefully any type of point wiring (light, fan, bell, socket or power), complete excluding fittings but including switches, ceiling roses, pendants, regulators, sockets, etc. and making good disturbed surfaces of walls, ceiling, floors etc to match with existing surface complete all as specified and as directed. |
| 2 | M&L for point wiring with 1.5 sqmm, single core, PVC insulated and PVC unsheathed FR-LSH cable, 1100 volts grade IS-694 marked, with multistranded copper conductors and earth continuity wire with 1.5 Sqmm copper conductor cable (including connecting to earth dolly) laid/fixed with and including PVC Casing and Caping on walls/ceiling, and with PVC switch board for mounting switches/socket etc for one light/bell/fan/exhaust fan point controlled by one number one way 5 Amp switch complete all as specified and as directed. |
| 3 | All as per item serial No 02 here-in-before but for One 3 pin 5 Amp socket outlet on same board with other switches. |
| 4 | All as per item serial No 02 here-in-before but for One 3 pin 5 Amp switch socket outlet on independent board. |
| 5 | All as per item serial No 02 here-in-before but with 2.5 Sqmm single core multistranded copper conductor cable and earth continuity wire with 2.5 Sqmm cable for 6 pin 15 Amp socket outlet on independent board. |
| 6 | All as per item serial No 02 here-in-before but for One switch 5 Amps bell push. |
| 7 | S & F switch piano, flush type single pole one way 5 Amps 230 volt complete all as specified and as directed. |
| 8 | S&F socket outlet 3 pin, 2-in-1, 5 Amps, flush type complete all as specified and as directed. |
| 9 | S & F switch socket combination outlet 3 pin, 2-in-1, 5 Amp flush type complete all as specified and as directed. |
| 10 | S & F switch socket combination, multipurpose, 2 in 1, 3 pin, 5 & 16 Amp flush type complete all as specified and as directed. |
| 11 | S & F ceiling rose surface bakelite, 65x50mm three terminal complete all as specified and as directed. |
| 12 | S & F lamp holder, insulated, PVC / polycarbonate /bakelite body cord grip cap suitable for pendent fitting complete all as specified and as directed. |
| 13 | S & F stepped type electronic fan regulator, two module size, flush type complete all as specified and as directed. |
| 14 | Fixing only serviceable fan regulator obtain from taking out of point wiring complete all as specified and as directed. |
| 15 | S&F bell push, flush type, 5 Amps complete all as specified and as directed. |
| 16 | S & F call bell Ding Dong AC ,230 volts single pole complete all as specified and as directed. |
| 17 | S&F in repairs, LED luminaire 600mm x 600 mm,35/36 watt, 220V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed. |
| 18 | S&F in repairs, LED light fittings 1x20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed. |
| 19 | S&F in repairs, LED lamp 9W(NU BULB PLUS 9W 865 b22 3Star suitable for lamp holder PVC/polycabonate/backelite body with cord grip pendant type omplete all as specified and as directed. |
| 20 | S & F in repairs switch piano, flush type single pole one way 5 Amps 230 volt complete all as specified and as directed. |
| 21 | S & F in repairs switch socket combination, multipurpose, 2 in 1, 3 pin, 5 & 16 Amp flush type complete all as specified and as directed. |
| 22 | S&F in repairs, LED light fitting 1 x 9W / 1 x 10W blukhead luminaries including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed. |
| 23 | S&Fin repair PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 250 mm x 200 mm and 50 mm deep complete all as specified and as directed. |
| 24 | S&F in repair PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mmthick plastic laminated sheet cover of size 100 mm x 100 mm and 50 mm deep complete all as specified and as directed. |
| 25 | S & F in repairs, single pole & neutral DBs 8 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 100 Amp rating copper bus bar complete all as specified and as directed. |
| 26 | S & F in repairs single pole & neutral DBs 4 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 100 Amp rating copper bus bar complete all as specified and as directed. |
| 27 | S & F in repairs sheet metal enclosure when MCB to be used 2 way, Single pole & neutral without bus bar complete all as specified and asdirected. |
| 28 | S&F MCBs, SPN 6 to 40 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed. |
| 29 | S&F MCBs, SP 6 to 32 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed. |
| 30 | M&L for Sub main wiring with 2 runs of 4.0 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dia non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 4.0 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and type of conduit complete all as specified and directed. (Note for Item No 29&30: For payment purposes, 2 runs of main cable (each of 1RM) 1 run of earth continuity cable (1RM) and one run of conduit (1RM) all together shall be considered as \\"1RM\\". |
| 31 | M&L for Sub main wiring with 2 runs of 6.0 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dia non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 6.0 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and type of conduit complete all as specified and directed. (Note: 2 run of 6 Sqmm cable and 1 run of 6 Sqmm cable along with conduit altogether shall be measured as one unit.) |
| 32 | S&F 1100 volts grade heavy duty flat cable of size 6 Sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including replacing 4mm suspension wire including taking down old cable of any description complete all as specified and as directed. |
| 33 | S&F 1100 volts grade heavy duty flat cable of size 10 Sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including replacing 4mm suspension wire including taking down old cable of any description complete all as specified and as directed. |
| 34 | Taking down fan of any type/make and size of AC ceiling fan, carefully from fan hook, dismantling of blades and transporting from any location inside army area to MES E/M store yard and hanging the same carefully in hook and connecting up including provision of cable from ceiling rose or connector to ceiling fan complete all as specified and as directed. |
| 35 | M&L for GI bracket made out of 40 mm bore medium grade GI Pipe with two sets clamps, with nuts and bolts, two Nos 90 degree bends all as directed, length of GI Pipe shall not be less than 3.0 metre for fixing of light fittings including taking out old bracket complete all as specified and as directed. |
| 36 | M&L for plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth lead wire 4 mm dia or 8 SWG bolted (with GI nuts, bolts & check nuts) and earth plate electrode at one end and connected to main switch board/ DBs etc. at the other, earth strip encased(protected) in and including 15 mm bore GI pipe medium grade with all fittings from top of electrode to main switch board/ DBs etc fixed with and including 25 x 6mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-2 using 12 mm graded crushed stone aggregate, RCC cover, funnel, wire mesh including necessary excavation and earth work complete all as specified and shown in electrical plate No 3 of SSR Pt-I including dismantling of old earthing complete all as specified and directed. Please Enable Macros to View BoQ information |