| 1 | GENERAL SUMMARY |
| 2 | Lump sum price worked out by contractor for 'BUILDING WORKS' as listed in Schedule 'A' Part I |
| 3 | Lump sum price worked out by contractor for 'ADDN/ALTN TO BUILDING P-13 AND ALLIED WORKS' as listed in Schedule A Part II |
| 4 | Lump sum price worked out by contractor for 'INTERNAL ELECTRIFICATION WORKS' as listed in Schedule A Part III |
| 5 | Lump sum price worked out by contractor for 'SEWAGE DISPOSAL WORKS' as listed in Schedule A Part IV |
| 6 | Lump sum price worked out by contractor for 'AREA DRAINAGE WORKS' as listed in Schedule 'A' Part V |
| 7 | Lump sum price worked out by contractor for 'STEEL GATE & FENCING WORKS ' as listed in Schedule A Part VI |
| 8 | Lump sum price worked out by contractor for 'PATH WORKS' as listed in Schedule A Part VII |
| 9 | Lump sum price worked out by contractor for ' EXTERNAL WATER SUPPLY WORKS' as listed in Schedule A Part VIII |
| 10 | Lump sum price worked out by contractor for 'EXTERNAL ELECTRIFICATION WORKS' as listed in Schedule A Part IX |
| 11 | Lump sum price worked out by contractor for 'EXCAVATION AND EARTH WORKS' as listed in Schedule A Part X |
| 12 | Schedule 'A' Part XI \\"MISC ITEMS OF WORKS\\" Note:- This Schedule is not pre priced by MES and Pre-Priced rate as \\"Rs 0.00\\" under Column 5 signifies this fact only |
| 13 | External Electrification |
| 14 | Taking down existing fixed Rifle rack of length less than 10m & refixing/relocating to same or other location fixed with and including sufficient number of anchor bolts and grouting complete all as directed by Engineer-in-Charge. |
| 15 | S&F factory made precast circular/square manhole cover of size 600mm with collar medium duty capacity not less than 10 metric ton, complete all as specified as directed. |
| 16 | Dismantling old barbed wire fixed to posts and making coils etc., complete all as specified. |
| 17 | Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5 m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized earth lead wire 4.0 mm dia (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 15 mm dia bore, watering pipe 20 mm bore GI light grade pipe with funnel & wire mesh, with and including including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, as in repair/replacement complete all as specified and as directed.Note(s) :-(i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm.(ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit.(iii) Rate shall include GI strip and protection pipe of length 7.5m, GI pipe beyond 7.5m length required at site shall be measured and paid separately.(iv) Earth resistance should be less than 1 Ohm. In case the test results are not found below 1 Ohm, complete earthing will be redone without any extra cost to Govt. |
| 18 | Supply and fixing flame proof, Water proof push button 10 A , 240 Volts, cast aluminium alloy LM6, IP66, gasket with 2 Nos cable entry gland complete all as specified and directed. |
| 19 | Supply and fixing flame proof, Water proof wall mounted fans blade size 18 Inch, single phase, 50 HZ , 1440 RPM, aluminium, non Oscilliation, non rotable fixed to wall including flexible wire complete all as specified and durected. |
| 20 | Material & labour for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6.00mm thick, burried directly in ground vertically (depth of pit not less than 2.25m below normal ground level), with top edge of the plate not less than 1.5m below normal ground level, earth plate surrounded by 15cm thick and packed alternate layers of charcoal dust and common salt, electrode connection using galvanised iron strip of size 32mmx6mm thick by means of bolts, nuts, check nuts and washers of galvanized iron connected to main switch board and protected by galvanized iron pipe light grade 40mm dia bore including watering pipe 20mm dia bore GI medium grade (ISI marked) with funnel and wire mesh, including all necessary excavation and earth work, PCC chamber in plain cement concrete (1:2:4) type B-1 and pit cover of presast RCC with MS frame etc and all as shown in electrical plate No 3 of MES Sch Part-I (2009), complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm.(ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit.(iii) Rate shall include earth lead and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately.(iv) Earth resistance should be less than 1Ohm. In case the test results are not found below 1 Ohm, complete earthing will be redone without any extra cost by the contractor. |
| 21 | Supply and fixing 40mm/dia bore 1.2 metre long GI pipe light grade bracket for fixing street light bent to shape (120 degree) including MS clamps 02 Nos made of minimum FI 25x3mm and nut and bolts duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 22 | Supply and laying PVC insulated flexible unarmoured cable three core with copper conductor 4sqmm size 1100 volt grade from junction box to security light through PVC conduit including connection as in repair/replacement complete all as specified and as directed. Note: PVC conduit shall be measured and paid separately. |
| 23 | Supply & fixing or laying HDPE (DWC) pipe of outer dia not less 50 mm including all accessories , bend, joints, nut bolts, clamps fixing on poles, walls, laying in trench , under floors, road, drain crossing, laying on surface etc as reqd at site and as per direction of Engr-in-Charge . |
| 24 | Note: The Total amount of contract will be subject to deduction of credit of Rs. 13704.00 for old Materials becoming contractor's property as per Schedule of Credit here in after. Please Enable Macros to View BoQ information |