| 1 | Carrying out preventive maintenance of heavy duty electrically operated Hangar gate of size 10.00 m X 5.00 m to make it in serviceable conditions alongwith complete servicing of the mechanism of door for Remote / Manual operated Gate comprising of motor, gear box, chain, contactor, relay, hooter, timer and control panel etc., installed at main panel & wiring, limit switch / MCB of the gate with and including dismantling and replacement of all unserviceable parts of Gear box, motor and panel with new parts at its installed locations complete all as specified and directed. Note: - Cost of Oiling, Greasing and labour charge of the replacement of various spare parts shall be deemed included in the unit rate of this item. Spare parts shall be measured and paid separately under respective items of this schedule. |
| 2 | Supply and fix following spare parts and accessories of Hangar Gate having same specifications of existing spares complete all as specified and directed: - |
| 3 | Supply only 4 core, 2.50 Sqmm size flexible copper conductor cable, PVC insulated and sheathed, 1100 volts grade multi stranded suitable for box girder between control panel to all motors medium grade PVC conduit ISI Marked not less than 25 mm dia for Hangar door complete all as specified and directed |
| 4 | Supply only 4 core, 4.00 Sqmm size flexible copper conductor cable, PVC insulated and sheathed, 1100 volts grade multi stranded suitable for box girder between control panel to all motors in medium grade PVC conduit ISI Marked not less than 25 mm dia for Hangar door complete all as specified and directed |
| 5 | Material and Labour for sub main wiring complete with 2 single core multi stranded copper conductor 6 sqmm (Nominal area) PVC insulated unsheathed cable drawn in and including medium grade PVC conduit ISI Marked not less than 25 mm dia concealed, including making good disturbed surface, of wall, including single core multi stranded copper conductor 6 sqmm size as earth wire drawn in same conduit complete all as specified and directed .Note: One run of 02 single core copper wire and 01 run of 6 Sqmm copper wire and 01 run of conduit 01 run of earth conductor 6 Sqmm wire shall be measured as one unit. |
| 6 | Supply only 3 HP motor starter capacity for suitable complete all as specified and directed. |
| 7 | Supply only geared rotary limit switch 3 phase, 415 volts, 50 Hz, 10 Ampere, No. 22-1210-2 KV suitable for hangar doors any capacity and any motion complete all as specified and directed |
| 8 | Supply only Triple Pole contactor, 3 phase, 20 Amperes with coil complete all as specified and directed |
| 9 | Supply only Teeth gear of chain required for operating of Hanger Gate complete all as specified and directed |
| 10 | Supply only Chain of teeth gear required for operating of Hanger Gate complete all as specified and directed |
| 11 | Supply only Drive End Ball bearing and Non Drive End Ball bearing having No. 6205 suitable for 3 phase induction motor, 1.5 KW, AC complete all as specified and directed |
| 12 | Supply only MCB TP 20 Ampere, 'C' curve complete all as specified and directed |
| 13 | Supply only Motor protection circuit Breaker switch, 415 volts suitable for 3 phase 1.5 KW Induction motor with thermal protection adjusting range 2.5-4.0 complete all as specified and directed |
| 14 | Supply only MCB single pole 240 volts, 6 to 32 amps, 50HZ, 10 KA. , ‘C’ series complete all as specified and directed. |
| 15 | Supply only MCB TPN 415 Volts, 40 Amps, 50 Hz, 10 KA 'C' series complete all as specified and directed. |
| 16 | Supply only Mini contactor AC, 3 pole upto 6 Ampere, 415 volts, 50 Hz. complete all as specified and directed. Make : ABB/Siemens/Indo asian |
| 17 | S&F flexible cable carrier complete all as specified and directed |
| 18 | Supply only push button switch for hangar doors with elements 6 Amp, 415 volts, 50 Hz complete all as specified and directed |
| 19 | Cutting and removing of old unserviceable / burnt winding wire and M & L for rewinding of stator of 3 phase, 1.5 KW , AC motor, by using super enamelled copper wire as per existing size with and including varnishing thereof and insulation of class \\"F\\" complete all as specified and directed. |
| 20 | Cutting and removing of old unserviceable / burnt winding wire and M & L for rewinding of stator of 3 phase, 2.5 KW , AC motor, by using super enamelled copper wire as per existing size with and including varnishing thereof and insulation of class \\"F\\" complete all as specified and directed. |
| 21 | Cutting and removing of old unserviceable / burnt winding wire and M & L for rewinding of stator of 3 phase, 4 KW , AC motor, by using super enamelled copper wire as per existing size with and including varnishing thereof and insulation of class \\"F\\" complete all as specified and directed. |
| 22 | Cutting and removing of old unserviceable / burnt winding wire and M & L for rewinding of F100 rotor of 3 phase, 1.5 KW , AC motor, by using super enamelled copper wire as per existing size with and including varnishing thereof and insulation of class \\"F\\" complete all as specified and directed. |
| 23 | Cutting and removing of old unserviceable / burnt winding wire and M & L for rewinding of F100 rotor of 3 phase, 2.5 KW, AC motor, by using super enamelled copper wire as per existing size with and including varnishing thereof and insulation of class \\"F\\" complete all as specified and directed. |
| 24 | Cutting and removing of old unserviceable / burnt winding wire and M & L for rewinding of F100 rotor of 3 phase, 4 KW , AC motor, by using super enamelled copper wire as per existing size with and including varnishing thereof and insulation of class \\"F\\" complete all as specified and directed. |
| 25 | FIRE ALARM |
| 26 | Carrying out preventive maintenance of fire alarm control panel (2 loop DC) complete with mounting battery of as per existing make and capacity including dismantling and replacement of minor spare parts complete all as specified and directed. Note: - Cost of spare parts shall be deemed included in the unit rate of this item. |
| 27 | Supply and fixing following spare parts and accessories of Fire alarm system having same specifications of existing spare complete all as specified and directed: - |
| 28 | Supply, commissioning and testing of analogue addressable Multi-Detector as per existing make having removable high performance chamber with Twin fire LEDs allow 360° viewing, lock mechanism (sensor to base), Variable sensitivity, Electronically addressed along with mounting base duly approved by LPCB including taking out old unserviceable necessary connections complete all as specified and directed. |
| 29 | Supply, commissioning and testing of analogue addressable Manual Call point as per existing make ESP Analogue Addressable Protocol having status LED for Alarming and standby mode, Electronically addressed, resettable type duly approved by LPCB including taking out old unserviceable necessary connections complete all as specified and directed. |
| 30 | Supply, commissioning and testing of analogue Addressable loop powered wall sounder as per existing make with flasher providing multi Volume levels and multi Tones with a maximum output of up to 102 dB(A) with low current consumption, fitted on Isolator Type Base which is fully compatible with ESP Analogue Addressable Protocol, User selectable modes, Electronically addressed duly approved by LPCB including taking out old unserviceable necessary connections complete all as specified and directed. |
| 31 | Supply and fixing of replacement of maintenance free 12 volt 7 AH battery complete all as specified and directed. |
| 32 | Supply, commissioning and testing of response Indicator complete all as specified and directed including taking out old unserviceable necessary connections complete all as specified and directed. |
| 33 | Supply and laying submain FRLS electric cable 02 run of two Core 1.50 Sqmm multi-stranded armoured copper conductor for wiring of fire detectors with all accessories and cable pointers or shall be painted with FIRE RED tags at an interval of every 1.00 Metre in PVC conduit complete all as specified and directed. |
| 34 | Supply and laying of rigid non - metallic PVC conduit including of all tees, bends, elbow, reducer, bellmouth tube ends and fixing accessories such as couplers, locks nuts, saddles, pipe hooks etc of size 25 mm complete all as specified and directed. |
| 35 | Supply, commissioning and testing of addressable control module complete as per existing make mounting wall/roof/ceiling including taking out old unserviceable necessary connections complete all as specified and directed. |
| 36 | Supply, commissioning and testing of addressable fault detector complete as per existing make mounting wall/roof/ceiling including taking out old unserviceable necessary connections complete all as specified and directed. |
| 37 | Supply, commissioning and testing of addressable fire alarm control panel (2 loop DC) complete with mounting battery of suitable capacity in hydraulic lab & RT Cabin including taking out old unserviceable necessary connections complete all as specified and directed. |
| 38 | Supply, commissioning and testing of addressable fire alarm control panel (4 loop DC) complete with mounting battery of suitable capacity in signal section including taking out old unserviceable necessary connections complete all as specified and directed. Please Enable Macros to View BoQ information |