| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.: |
| 2 | Group C: |
| 3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.: |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.: |
| 5 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.: |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.: |
| 7 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire: |
| 8 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire: |
| 9 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire: |
| 10 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire: |
| 11 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required.: |
| 12 | Armoured cable 6 sq. mm (twin core): |
| 13 | Armoured cable 25 sq. mm (3.5 core): |
| 14 | Armoured cable 35 sq. mm (3.5 core): |
| 15 | Armoured cable 120 sq. mm (3.5 core): |
| 16 | Providing and laying of one number additional PVC insulated and PVC sheathed armoured / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.: |
| 17 | Armoured cable 6 sq. mm (twin core): |
| 18 | Armoured cable 25 sq. mm (3.5 core): |
| 19 | Armoured cable 35 sq. mm (3.5 core): |
| 20 | Armoured cable 120 sq. mm (3.5 core): |
| 21 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.: |
| 22 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.: |
| 23 | Supplying and fixing following Modular base & cover plate on modular metal boxes etc. as required.: |
| 24 | 8 Module: |
| 25 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.: |
| 26 | 5/6 amps switch: |
| 27 | 3 pin 5/6 A socket outlet: |
| 28 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.: |
| 29 | S/E of LED Downlighter surface square with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.: |
| 30 | Specification of LED fittings:: |
| 31 | Wattage of LED fittings :As per following parameter. |
| 32 | Lumen output of the fitting:as below |
| 33 | Diffuser : Polycarbonate diffuser/pmma |
| 34 | Operating voltage :140 V to 270 V, AC supply or better. |
| 35 | Input frequency :50 Hz + 1 Hz |
| 36 | Power factor :Minimum 0.90 |
| 37 | Luminaire efficacy :>85 lm/w |
| 38 | Color rendering index:CRI shall be greater than 80 |
| 39 | Working/ operating temperature :00 to + 450c or better |
| 40 | Color temperature :60000K + 10% |
| 41 | Electronic Driver : |
| 42 | Drive current (LED):As per OEM. |
| 43 | Operating voltage :140 V to 270 V AC supply or better |
| 44 | Type of driver :Constant current output driver |
| 45 | THD :Less than 10% |
| 46 | Surge Protection :2.5 KV minimum |
| 47 | Efficiency Driver:>85% |
| 48 | Protection:Shall have under voltage and over voltage protection. |
| 49 | Warranty of LED fittings including LED driver : 5 years against manufacturing defect. |
| 50 | Fixture :Should comply with LM 79 test from UL/NABL lab. |
| 51 | LED Type/ Make/ Model:Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 52 | Life of LED:50000 burning hours at 70% lumen maintenance |
| 53 | 1000 Lumen |
| 54 | 1500 Lumen |
| 55 | S/E of LED Panel with PDC body and prismatic diffuser to be mounted in recess /surface The job includes carriage, erection, making connections testing and commissioning of the fittings.2 * 2 feet: |
| 56 | Specification of LED fittings:: |
| 57 | Wattage of LED fittings :As per following parameter. |
| 58 | Total lumens of the fittings. :as below |
| 59 | Diffuser : Prismatic multilayer diffuser UGR <19 |
| 60 | Operating voltage :140 V to 270 V, AC supply or better. |
| 61 | Input frequency :50 Hz + 1 Hz |
| 62 | Power factor :Minimum 0.90 |
| 63 | Luminaire efficacy :>120 lm/w |
| 64 | Color rendering index:CRI shall be greater than 80 |
| 65 | Working/ operating temperature :00 to + 450c or better |
| 66 | Color temperature :60000K + 10% |
| 67 | Electronic Driver : |
| 68 | Drive current (LED):As per OEM. |
| 69 | Operating voltage :140 V to 270 V AC supply or better |
| 70 | Type of driver :Constant current output driver |
| 71 | THD :Less than 10% |
| 72 | Surge Protection : 2.5 KV minimum |
| 73 | Efficiency Driver:>85% |
| 74 | Protection:Shall have under voltage and over voltage protection. |
| 75 | Warranty of LED fittings including LED driver :5 years against manufacturing defect. |
| 76 | Fixture :Should comply with LM 79 test from UL/NABL lab. |
| 77 | LED Type/ Make/ Model:Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 78 | Life of LED:50000 burning hours at 70% lumen maintenance |
| 79 | Description: |
| 80 | Lumen output Of fitting:Rate |
| 81 | 2880:6158 Lumen |
| 82 | 3600:6365 Lumen |
| 83 | 4320:6573 Lumen |
| 84 | S/E of LED Bluk head fitting with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.: |
| 85 | Specification of LED fittings:: |
| 86 | Wattage of LED fittings :As per following parameter. |
| 87 | Total lumens of the fittings. :as below |
| 88 | Diffuser : Polycarbonate diffuser/PMMA |
| 89 | Operating voltage :140 V to 270 V, AC supply or better. |
| 90 | Input frequency :50 Hz + 1 Hz |
| 91 | Power factor :Minimum 0.90 |
| 92 | Luminaire efficacy :>80 lm/w |
| 93 | Color rendering index:CRI shall be greater than 80 |
| 94 | Working/ operating temperature :00 to + 450c or better |
| 95 | Color temperature :60000K + 10% |
| 96 | Electronic Driver : |
| 97 | Drive current (LED):As per OEM. |
| 98 | Operating voltage :140 V to 270 V AC supply or better |
| 99 | Type of driver :Constant current output driver |
| 100 | THD :Less than 10% |
| 101 | Surge Protection :2 KV minimum |
| 102 | Efficiency Driver:>85% |
| 103 | Protection:Shall have under voltage and over voltage protection. |
| 104 | Warranty of LED fittings including LED driver :5 years against manufacturing defect. |
| 105 | Fixture :Should comply with LM 79 test from UL/NABL lab. |
| 106 | LED Type/ Make/ Model:Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 107 | Life of LED:50000 burning hours at 70% lumen maintenance |
| 108 | Lumen output of the fitting: 800 |
| 109 | S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.: |
| 110 | Specification of LED fittings:: |
| 111 | Wattage of LED fittings :As per following parameter. |
| 112 | Total lumens of the fittings. :as below |
| 113 | Diffuser : Polycarbonate diffuser/PMMA |
| 114 | Operating voltage :140 V to 270 V, AC supply or better. |
| 115 | Input frequency :50 Hz + 1 Hz |
| 116 | Power factor :Minimum 0.90 |
| 117 | Luminaire efficacy :>100 lm/w |
| 118 | Color rendering index:CRI shall be greater than 80 |
| 119 | Working/ operating temperature :00 to + 450c or better |
| 120 | Color temperature :60000K + 10% |
| 121 | Electronic Driver : |
| 122 | Drive current (LED):As per OEM. |
| 123 | Operating voltage :140 V to 270 V AC supply or better |
| 124 | Type of driver :Constant current output driver |
| 125 | THD :Less than 10% |
| 126 | Surge Protection :2.5 KV minimum |
| 127 | Efficiency Driver:>85% |
| 128 | Protection:Shall have under voltage and over voltage protection. |
| 129 | Warranty of LED fittings including LED driver :5 years against manufacturing defect. |
| 130 | Fixture :Should comply with LM 79 test from UL/NABL lab. |
| 131 | LED Type/ Make/ Model:Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 132 | Life of LED:25000 burning hours at 70% lumen maintenance |
| 133 | 1000 Lumen |
| 134 | 2000 Lumen |
| 135 | Installation of ventilatinmg /exhaust fan in the existing opening, including making good BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor the damage, connection, testing, commissioning etc. as required.Supply & Erection of Ventilating Fan ) following size complete with motor,, with minimum power consumption, rigid frame with rubber mounting for silent operation, in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC.: |
| 136 | :Exhaust Fan, 150 mm sweep |
| 137 | Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Heavy Duty type.: |
| 138 | Exhaust Fan, Heavy duty, 300 mm sweep (900/1400rpm): |
| 139 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.: |
| 140 | Single pole : |
| 141 | Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.: |
| 142 | 40 amps DP : |
| 143 | 63 Amp DP: |
| 144 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator): |
| 145 | 8 way , Double door : |
| 146 | 12 way , Double door : |
| 147 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.: |
| 148 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.: |
| 149 | Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes with 8 bar pressure rating Five star BEE rating and safety valve installation by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:- : |
| 150 | 25 Liter capacity water heater (Cat-A): |
| 151 | Providing and installation of instant Electric water heater (Geyser) of various sizes with 8 bar pressure rating 3kw element and safety valve installation by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:- : |
| 152 | 3 Liter capacity water heater (Cat-A): |
| 153 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.: |
| 154 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.: |
| 155 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run): |
| 156 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run): |
| 157 | Supply & fixing of 5M hot dip galvanised Octagonal pole having 70mm top dia.A/F., 130mm bottom dia.A/F. , 3mm thick HT sheet, 200X200X12mm base plate; (without bracket & Foundation Bolt) suitable for standard bracket. Foundation bolts M16X450MM.A) Material grade should be S355JR/J0 as per BSEN 10025.B)B) In-house Galvanization as per BSEN ISO:1461C) Fusion Welding as per ISO 3824-2:2021Note: Following documents from manufacturer(OEM) are to be submitted to process the bills and avoid duplicity of Manufactures:1) Factory License of OEM (manufacture of Pole) with validity2) In-House NABL Accredited Certificate of OEM Like ISO 9001, 14001,45001(manufacture of Pole) with validity3) Raw Material Test Certificate of bracket Pipe (IS:1161 grade) .4) Raw Material Test Certificate of Zinc (Zn) Make- Hindustan Zinc(Vedanta)4) Raw Material Test Certificate of Foundation bolts (EN Grade EN-8 and UTS>600): |
| 158 | 5 mtrs 1000mm Double Arms Bracket : |
| 159 | Supplying and fixing of integral LED Street light fixture of following capacity, cast aluminium spigot, spun aluminium canopy, opal acrylic diffuser, complete with all accessories including making connections, testing etc. as required. : |
| 160 | LED 60watt street light fixture : |
| 161 | SITC of Main L.T. Panel 250amps 440 volts (As per enclosed Annexure)TTA 61439 type : |
| 162 | INCOMMING : |
| 163 | MCCB 250A 4P 36KA t.m Rel O/L S/C Prot. Make ABB Qty I nos : |
| 164 | Spreader Link MCCB 250A 4P Make ABB Qty 1 Nos : |
| 165 | ROH 250 A Make ABB Qty I nos : |
| 166 | AMP METER Make ABB Qty I nos : |
| 167 | VOLT METER Make ABB Qty I nos : |
| 168 | CT 250/5 A , CL 1.0 , 5VA Make NEWTEK / NIPPEN Qty 3 nos : |
| 169 | CT SHORTING LINK Make REPUTED Qty 4 nos: |
| 170 | PHASE INDICATION RED , YELLOW Make ESS BEE Qty 2nos: |
| 171 | PHASE INDICATION BLUE Make ESS BEE Qty I nos : |
| 172 | MCB SP 6 A Make ABB Qty 3 nos : |
| 173 | N. LINK Make REPUTED Qty I nos : |
| 174 | CHANGE OVER SWITCH 250 A Make ABB Qty I nos : |
| 175 | INDICATION ON ESS BEE Qty I nos : |
| 176 | OUTGOING: |
| 177 | MCCB 100 A 4P , 25 KA ,T.M Rel O/L,S/C Prot. ABB Qty 2 nos : |
| 178 | SPREADER LINK 100 4P ABB Qty 2 nos : |
| 179 | ROH 100 A ABB Qty 2 nos : |
| 180 | MCCB 63 A 4P , 25 KA ,T.M Rel O/L, S/C Prot. ABB Qty 2 nos : |
| 181 | SPREADER LINK 63 4P ABB Qty 2 nos : |
| 182 | ROH 63 A ABB Qty 2 nos : |
| 183 | CONTROL TERMINAL REPUTED Qty I0 nos : |
| 184 | POWER TERMINAL REPUTED Qty I6 nos : |
| 185 | PANEL ENCLOSURE 2275X1300X400MM ,TATA CRC 1.6MM FOR LOAD BEARING AND 2MM FOR NON LOAD BEARING,2 MM GLAND PLATES AND BASE FRAME 75X40X5 MM make SSPC Qty I nos : |
| 186 | ALU BUSBAR 300 A EN91 Qty I nos : |
| 187 | WIRING HARNESS {METERING,STARTERS} Make LAPP / POLYCAB/FINOLEXQty Qty I nos : |
| 188 | HARDWARE{LOCKS,GASKET,NUTBOLT ETC} Make REPUTED 1: |
| 189 | SITC of Distribution Board (As per enclosed Annexure-B)Incomer: TTA 61439. |
| 190 | MCCB 100A 4P 25KA TMR With O/L & S/C Protection: |
| 191 | MCCB 100A 4P 25KA TMR With O/L & S/C Protection- 1nos : |
| 192 | Spreader Link MCCB 100A 4P- 2nos : |
| 193 | Indication Lamps LED Type RY- 2nos : |
| 194 | Indication Lamps LED Type Blue- 1nos: |
| 195 | Control SP MCB 6A 10K -3nos: |
| 196 | Fabrication/ Painting & Assembly: |
| 197 | Fabrication charges of cubical type, indoor type,single door,wall mounted, fixed type, free standing single front, dust proof & compartmentalized Distribution Board made out of M.S. CRC Sheet 16G/18G,duly painted with Siemens Grey Powder Coated Paint as per Specification.Approximate Size (H)700mmX (W) 500mm X (D) 200mm 1Nos: |
| 198 | Assembly Charges of 100A 4Strip Copper Busbar ( Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.66 Amp.) Copper shall be Electric Grade , Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. 1Nos: |
| 199 | Assembly Charges of Copper solid/ Copper flexible wire interconnection Busbar to MCCB &MCCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables 1Nos: |
| 200 | Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. 1Nos: |
| 201 | Assembly Charges of Accessories like Neoprene Rubbar Gasket, Doorlocks, Copper Flexible door earth, legend plates etc. 1Nos: |
| 202 | Providing & fixing of Co2 type fire extinguisher cap 4.5 kg, duly lSl marked confirmingls:15583:2018 with ls 14509, complete with delivery hose, horn, sqeeze grip release valve, locking arrangement, operation manual, bracket with two screw and sleeve as required complete in all respects, to the entire satisfaction of the Engineer incharge. Ma ke-Lifeguard ,Minimax etc : |
| 203 | Providing & fixing of W /Co2 stored pressure type fire extinguisher cap 09 ltrs, duly lSl marked confirming ls:15583:20L8 with ls 4947, complete with delivery hose, sqeeze grip release valve, locking arrangement, operation manual, bracket with two screw and sleeve as required complete in all respects, to the entire satisfaction of the Engineer incharge. Ma ke-Lifeguard ,Minimax etc : |
| 204 | Providing & fixing of ABC stored pressure type fire extinguisher cap 09 ltrs, duly lSl marked confirming lS:15583:2018, complete with delivery hose, sqeeze grip release valve, locking arrangement, operation manual, bracket as required complete in all respects, to the entire satisfaction of the Engineer incharge. Make-Lifeguard ,Minimax etc : Please Enable Macros to View BoQ information |