| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Make:-ANCHOR /KEI/PLAZA. |
| 2 | Group C |
| 3 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm.FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required. Make:-ANCHOR /KEI/PLAZA. |
| 4 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.FRLS PVC insulated copper conductor single core cable etc as required.Make:- ANCHOR/KEI/PLAZA |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. Make:-ANCHOR ROMA CLASSIC/ANCHOR BY PANASONIC |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.Make:-ANCHOR ROMA CLASSIC/ANCHOR BY PANASONIC |
| 7 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Make:-ANCHOR ROMA CLASSIC/L&T |
| 8 | 5 amp modular switch |
| 9 | 5 amp modular socket |
| 10 | Bell Push |
| 11 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required. Make:- ANCHOR/KEI/PLAZA |
| 12 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 13 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 14 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 15 | 2 X 10sq. mm + 1 X 6 sq. mm earth wire |
| 16 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVCconduit as required. Make:- ANCHOR/KEI/PLAZA |
| 17 | S/D 3 X 1.5 sq. mm |
| 18 | S/D 2x4 sq. mm |
| 19 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.Make:-ANCHOR/KEI/PLAZA |
| 20 | Armoured cable 6 sq. mm (Two core) |
| 21 | Supplying and fixing Computer board comprising 3 nos 5 amp modular switches & Sockets , G.I box 2 module for jack box and G.I Box 12 module for 5 amp switchs and 5 amp sockets comprising frame and cover plate for each 2 module metal box and 12 module metal box , one no computer jack (RJ-45) with shutter including connections etc as required. Make:- ANCHOR/KEI/PLAZA |
| 22 | Supplying and fixing of fancy wall bracket of chrome finish colour with opal glass diffuser made of mild steel, with single holder containing thread type LED lamp holder(s) of all sizes and shapes, complete with all accessories but excluding led lamp including making connections, testing etc. as required. Make:-Jaquar/Wipro/Philips with five year warranty |
| 23 | fancy wall bracket |
| 24 | Supplying and fixing batten/ angle holder including connection etc. as required. Make:-Anchor/SSK as approved by Engineer-in -charge. |
| 25 | Providing and installation of following type of LED retrofit Lamp B-22 holder base with polycarbomate diffuser and aluminium heat sink including connections, testing and commissioning etc. as required. Make:- JAQUAR/Wipro/Philips as approved by Engineer-in-Charge |
| 26 | Providing and Fixing of IP20 LED fixture of 18 watt +/- 1 W LED Surface Mounted Downlighter Round Shape with minimum system lumen efficacy of 100 lm/W with Polycarbonate housing,pressure die cast heat sink and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 . The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K with CRI of minimum 80.The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. Make:- Jaquar/Wipro/Phillips. with five year warranty |
| 27 | Providing and fixing LED Batten Light of IP40 Led fixture 40 W+/- 1W with Surface Mounted 4 Feet with Polycarbonate diffuser with Extruded aluminium housing having minimum system lumen output 1000 lumens and system lumen efficacy of 100 lm/W with P.F.>0.95 with THD<20% ,CRI 80 .The LED with Useful life of 50000 Hrs at L70 . The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K with CRI of minimum 80.The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. Make:- Jaquar/Wipro/Phillips. with five year warranty |
| 28 | Providing, Installation, testing and commissioning of BLDC ceiling fan (5 star rating), including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required. Make:- Usha/Orient/Crompton. with five year warranty |
| 29 | Ceiling Fan 1200 mm sweep |
| 30 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.Make :-Anchor (Roma classic )/ L&T(Entice)/ Legrand(Myrius) as approved by Engineer-in -charge. |
| 31 | Providing and installation exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: Make:-USHA/BAJAJ/CROMPTON as approved by Engineer-in -charge. with five year warranty |
| 32 | Exhaust Fan, Light duty, (Domestic)300mm sweep |
| 33 | Providing and fixing following rating and breaking capacity Type FN S-D-F Suitable for DIN fuse -link (2P) in open execution with Terminal Shouds on both side and Phase Barriers included and Telescopic Shaft for depth adjustment door interlock & padlock facility including drilling holes in Enclosuer panel, making connections, etc. as required. Make :- L&T/ Anchor/ Havell's |
| 34 | FN TPN 100 Amp |
| 35 | Providing and fixing of Post Top Lantern LuxMax - GENIUS Small LED Post Top of suitable size, excluding with LED 40 watt complete with all accessories, connections, testing and commissioning etc.as required .Make :- Twinkle cat no LUXMAX-PT-153 / K-lite /Panasonic as approved by Engineer-in-charge. with five year warranty |
| 36 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)ANCHOR UNO/ L&T/ LEGRAND as approved by Engineer-in -charge. |
| 37 | 12 way, Double door |
| 38 | 16 way, Double door |
| 39 | Supplying and fixing 6 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Make:-ANCHOR/L&T/LEGRAND as approved by Engineer-in -charge. |
| 40 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make:-ANCHOR/L&T/LEGRAND as approved by Engineer-in -charge. |
| 41 | 63Amp |
| 42 | Providing and Fixing of 1200 mm X 300 mm LED fixture 36 W +/- 1W Surface mounted fixture with HET Plastic diffuser with CRCA Powder Coated housing having minimum system lumen efficacy 100lm/W with P.F.>0.95 with THD<10%. The LED with Useful life of 50000 Hrs at L70. The LEDs used in the luminaire shall have CCT of 5700 K with CRI of minimum 80. The Input voltage range shall be 150V to 270V , 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects.Make Philips/Wipro/panasonic or as approved by Engineer-in-Charge.(five year warranty) |
| 43 | LED Panel 4'x1' 36 watts |
| 44 | Providing and Fixing of LED fixture 600mmX600mm 36 Watt +/- 1W Recess mounted fixture with HET Plastic diffuser with minimum system lumen efficacy of 100 lm/W with CRCA housing having P.F.>0.95 with THD<10% ,CRI 80.The LED with Useful life of 50000 Hrs at L70. The LEDs used in the luminaire shall have CCT of 5700 K with CRI of minimum 80. The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. Make Philips/Wipro/panasonic or as approved by Engineer-in-Charge.(five year warranty) |
| 45 | LED Panel 2'x2' 36 watts |
| 46 | Supplying and fixing Wireless Ding Dong bell suitable for single phase, 230 volts, complete as required.Make:-Anchor/SSK as approved by Engineer-in -charge. Note:- The Credit of dismantle Material Amount to Rs. 2500/- bill be detected in the bill. Please Enable Macros to View BoQ information |