| 1 | Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP |
| 2 | Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP |
| 3 | Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-PP |
| 4 | Supplying and erecting 100 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV |
| 5 | Supplying and erecting 150 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV |
| 6 | Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 7 | Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV |
| 8 | Supplying and erecting 100 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 9 | Supplying and erecting 150 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV |
| 10 | Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV |
| 11 | Supplying and erecting 25 mm Ball Valve complete with PN16 pressure rating, as per specification no. FF-VL/BV |
| 12 | Supplying and installing one piece moulded HDP/ fibre water tank for negative suction only, having capacity 1000 litres fitted with necessary accessories complete as per specification no. FF-FFA/PT |
| 13 | Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL |
| 14 | Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FF-FFA/NZ |
| 15 | Supplying and erecting 150 mm dia fire brigade header suitable for supplying water in fire tank complete as per specification no. FF-FA/FBC |
| 16 | Supplying and erecting fire brigade header ( Siamese connection )of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FMC |
| 17 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG |
| 18 | Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS |
| 19 | Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\\"x6\\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) |
| 20 | Making trench in Hard murum/Tar road having 0.9m depth and minimum 0.3m width for laying provided cables of voltage range 3.3kV to 11kV complete as per specification no. CW-EXN-CTR |
| 21 | Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose) |
| 22 | Carrying out core cutting of size 3\\" to 5\\" dia x 15\\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 23 | Supplying & erecting MS pole bracket for guarding/LT OH line, fabricated from angle iron 50x50x6mm and 550mm long for necessary nos. of provided insulators, and erecting on pole with 50x6mm clamp complete as per specification no. OH-PL/BKT |
| 24 | Supplying, installation, testing and commissioning of main fire pump (MFP / EP) suitable for water discharge of 1800 to 2280 LPM at 80 to 60 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 37kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/EP |
| 25 | Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 90 to 70 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 9.3 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003)complete, as per specification no. FF-MFP/JP |
| 26 | Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 90 to 60 m head driven by 76 HP or suitable HP capacity diesel engine at required working speed suitable for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP |
| 27 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring & cabling along with allied accessories with following incoming and outgoings, suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specifications the capacity of electric motor driven pump are as follows a. Main fire pump(MFP) having capacity of 22kW 1no (1 working) b. Jockey pump(JP) capacity of suitable capacity 2 nos(1 working +1 standby, alternate run per start in auto mode) comprises of the following features & switchgears: 1. Main incomer FP SFU having rotary handle with HRC fuses of suitable rating. 2. Electrolytic grade copper strips for busbar of suitable sizes for main incomer and branches to motor SFU's, starters & outgoing terminals with necessary accessories like stainless steel nut bolts with spring washers for connections, mounted on required no of epoxy or porcelain support insulators of suitable ratings etc. 3. Individual pump TPN SFU having rotary handle with HRC fuses of suitable rating. 4. Digital voltmeter & ammeter & RYB indicating lamps & push buttons & SPP, O/L & phase reversal protection with emergency stop switch. 5. TPN SPD 100kA Type 1 +2 tested. 6. Required pressure transducer with pressure indication on panel with cabling required for monitoring & automatic operation of fire pumps. 7. System controller to control operation of main electric fire pump, jockey (pressurization) pumps in sequence with interlocking for operation of pumps as per specification with automatic/manual operation with selector switch & alternate run of standby Pumps consisting of relays, timers. sensors, annunciation window for fault indication, complete as per specification. 8.Suitable capacity electric motor starters for all individual pumps with necessary push buttons & indications. 9. Siren of required capacity to be activated when main pump starts & allied accessories as per requirements of local CFO or as directed by engineer in charge. 10. Danger board as per IS. 11. Spare HRC fuses minimum 2 nos of each individual rating with required bakelite fuse holder for main & jockey fire pumps MFP=(1working), JP = (1working+1standby, alternate run per start in auto mode) complete panel, as per specification no. FF-MFP/ECP |
| 28 | Supplying, installing, testing and commissioning of 2 Zone Microprocessor based, conventional fire alarm control panel (FACP) with standard accessories , 16x2 Character LCD Display, provision for zone wise contact and beep sound alarm, suitable to operate on 120-220 V AC, complete as per specification no. FF-FAAS/FACP |
| 29 | Rebate for existing jockey pump, disel engine and fire existing hydrants. Please Enable Macros to View BoQ information |