| 1 | \\" BOQ \\" BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : Chief Engineer Shillong Zone NAME OF WORK: PROVISION OF OTM ACCN FOR ARO AT JORHAT UNDER GE JORHAT Contract No: CESZ/JOR/ OF 2025-2026 Bidder Name : GENERAL SUMMARY (SCHEDULE OF WORKS) (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # NUMBER # Sl.No. Description of Parts/ Item Item Code / Make No. orQty. Unit Pre Priced Rate (in. Rs.) as Defined by MES Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Ps. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Figure TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates. |
| 3 | SCHEDULE ‘A’ Part-I(A) (BUILDING & STRUCTURE WORKS) |
| 4 | Construction of OFFICE AND ADMINISTRATION ACCN ,(G+1),RCC framed structure, brick wall construction with ATT and water proofing roof treatment including built in furniture complete all as specified and shown on drawings. |
| 5 | Construction of JCO SINGLE LIVING ACCN, ORs & HAV ETC single storey,RCC framed structure, brick wall construction with ATT and water proofing roof treatment including built in furniture complete all as specified and shown on drawings. |
| 6 | Construction of RELIGIOUS INSTITUTE single storey,RCC framed structure, brick wall construction with ATT and water proofing roof treatment including built in furniture complete all as specified and shown on drawings. |
| 7 | Construction of GARAGE & PETROL STORE single storey,RCC framed structure, brick wall construction with ATT and water proofing roof treatment including built in furniture complete all as specified and shown on drawings. |
| 8 | Construction of CBET, TRADE ALLOCATION TEST & BARRACK FOR CANDIDATE,(G+1),RCC framed structure, brick wall construction with ATT and water proofing roof treatment including built in furniture complete all as specified and shown on drawings. |
| 9 | Construction of PARADE CUM ENROLLING SHED single storey with MS truss and roof sheet complete all as specified and shown on drawings.Note for serial item No. 1.01 to 1.06:(i) Boring of pile and cast-in-situ of pile including its concrete and reinforcement shall be measured and paid separately under relevant Schedule.(ii) Cost of pile cap including RCC, reinforcement and form work & its earthwork are included in the quoted amount of building. |
| 10 | Lumpsum price workedout by the tenderer for CAST-IN-SITU PILE as listed in Schedule ‘A’ Part-I(B) |
| 11 | Lumpsum price worked out by the bidder/ tenderer for SITE CLEARANCE, SITE DEVELOPMENTS & EARTH WORKS as listed in Schedule 'A' Part-II. |
| 12 | Lumpsum price worked out by the bidder/ tenderer for ROAD, PATH AND CULVERT as listed in Schedule 'A' Part-III. |
| 13 | Lumpsum price worked out by the bidder/ tenderer for INTERNAL WATER SUPPLY as listed in Schedule 'A' Part-IV. |
| 14 | Lumpsum price worked out by the bidder/ tenderer for EXTERNAL WATER SUPPLY as listed in Schedule 'A' Part-V. |
| 15 | Lumpsum price worked out by the bidder/ tenderer for INTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-VI. |
| 16 | Lumpsum price worked out by the bidder/ tenderer for EXTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-VII. |
| 17 | Lumpsum price worked out by the bidder/ tenderer for SEWAGE DISPOSAL as listed in Schedule 'A' Part-VIII. |
| 18 | Lumpsum price worked out by the bidder/ tenderer for AREA DRAINAGE as listed in Schedule 'A' Part-IX. |
| 19 | Lumpsum price worked out by the bidder/ tenderer for BOUNDRY WALL, SECURITY WALL, FENCING AND GATE as listed in Schedule 'A' Part-X. |
| 20 | Sch 'A' Sec-XI (Miscellaneous Items) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col. 5 siginifies this fact only. |
| 21 | Bringing approved earth (As approved by GE) from sources outside defence land including all costs such as royalty if any, transportation, taxes etc for area filling / forming including rising earth spreading in layers not exceeding 30 cm thick each layer watering and compaction with 8 tonne to 12 tonne power roller and finished to required size and shape etc up to any high / depth from existing ground level complete all as specified and directed.Note:(i) Earth required for this item shall be supplied by the contractor from outdide of the MOD land of any lead at his own cost and arrangement.(ii) All cost of procurement of earth including cost of transportation , royalties and tax shall deemed to be included in the quoted rate for this item.(iii) With reference to the clause 3.6 of SSR part II on serial page No. 21, it is clarified that measurement of this item shall be finished embankment / traverse of filled earth after consolidation / compaction and 5% deduction shall be made from measured and calculated volume to allow for increase in bulk.(iv) The total quantity or partial quantity of earth may not be available in Jorhat area. The contractor shall bring the earth from outside the Dinjan area. Therefore it is advised to contractor to check the availability of earth and its lead involved before quoting his rate against this item. |
| 22 | M&L for Construction of brick masonry valve pit of size 90 cm x 90 cm x 90 cm (internal dimensions) including concrete work with one brick thick wall in cement mortar (1:4) on 100 mm thick PCC (1:4:8) type D2 (using 40 mm graded crushed stone aggregate) lean concrete, including PCC (1:3:6) type C-1 (using 20mm graded crushed stone aggregate) as in benching and coping and 10 mm thick cement plaster in CM (1:4) internally and externally upto 15 cm below ground level providing valve pit cover made out of 40x40x6mm angle iron frame all-round fixed by means of 4 Nos holdfast 150 mm long made out of flat iron 40x6 mm embedded in PCC block (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) of size 230x200x100 mm including provisionn of hinges welded with angle iron frame and MS cover of 3 mm thck sheet, MS handle of suitable length and size welded with MS cover and suitable locking arrangement and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 23 | S&F cable entry terminal Box for bollard light made oF PVC of size - 155 x 210 x 92 mm, IP 55/65 degree of protection, with DP6-32 AMps Brackets provided inside to facilitate DIN rail along with cable entry incl bracket for mounting , incl necessary DIN channel fixed and connection alongiwth connector for incoming cable complete all as specified and directed. |
| 24 | Design, fabricate ,supply , installation, testing and commissioning of factory made powder coated (CPRI approved) out door type, dust & vermin proof feeder pillar box made out of 3.15mm CRCA steel sheet of suitable size and angle iron 1100mm x 1100mm x 600mm powder coated over a coat of red oxide primer suitably grouted in PCC (1:3:6) type C1 (20mm graded crushed stone aggregate) including bus bar, internal wiring with PVC insulated single core cables of copper conductor of suitable size duly numbered with tags for the circuits with hinged double door shutters (front and rear) cubical type, locking arrangement and slanted roof. The size of panel board shall be suitable for housing the accessories given here-in-under and also suitable for operation on AC 415 volts, 3 phase, 50Hz supply system including disconnecting of electric connection both incoming and out going from existing unserviceable indoor/ outdoor feeder pillar boxes/ bus bar enclosers alongwith taking out panel from the foundation complete all as specified and directed. The feeder box shall comprises of following |
| 25 | Serial item No. 12.004 continued….(a) INCOMING(i) MCCB 500 Amps, 4 pole, 415 V, 36 kA - 01 No (Microprocessor based)(ii) CT Operated Smart Meter Class 0.5 S - 01 No.(iii) LED indicator R-Y-B, set of 3 - 01 No(b) OUTGOING(i) MCCB 250 Amps, 4 pole, 415 volts, 36 kA - 03 Nos (Thermal magnetic)(ii) MCB DP 6-32 Amps, 240 volts, 'C' curve, 10 KA - 01 No.(iii) Time switches 415 V, 3 phase of 10 Amp Rating with contactor fitted inside the enclosure - 01 No |
| 26 | Supply, installation, testing and commissioning of factory made powder coated (CPRI approved) out door type, dust & vermin proof feeder pillar box made out of 3.15mm CRCA steel sheet of suitable size and angle iron 1200 x 1200x 6mm powder coated over a coat of red oxide primer suitably grouted in PCC (1:3:6) type C1 (20mm graded crushed stone aggregate) including bus bar, internal wiring with PVC insulated single core cables of copper conductor of suitable size duly numbered with tags for the circuits with hinged double door shutters (front and rear) cubical type, locking arrangement and slanted roof. The size of panel board shall be suitable for housing the accessories given here-in-under and also suitable for operation on AC 415 volts, 3 phase, 50Hz supply system including disconnecting of electric connection both incoming and out going from existing unserviceable indoor/ outdoor feeder pillar boxes/ bus bar enclosers alongwith taking out panel from the foundation complete all as specified and directed. The feeder box shall comprises of following accessories:- |
| 27 | Serial item No. 12.005 continued….(a) INCOMING(i) MCCB 250 Amps, 4 pole, 415 V, 36 kA - 01 No (Thermal magnetic)(ii) CT Operated Smart Meter Class 0.5 S - 01 No.(iii) LED indicator R-Y-B, set of 3 - 01 No(b) OUTGOING(i) MCCB 200 Amps, 4 pole, 415 volts, 36 kA - 02 Nos (Thermal magnetic)(ii) MCCB 63 Amps, 4 pole, 415 volts, 25 kA - 01 No (iii) MCB DP 6-32 Amps, 240 volts, 'C' curve, 10 KA - 03 Nos.(iii) Time switches 415 V, 3 phase of 10 Amp Rating with contactor fitted inside the enclosure - 01 No |
| 28 | M&L for construction of transformer platform with PCC (1:2:4) type B2 using 40 mm graded crushed stone aggregate of size 2.00 m x 2.00 m x 1.20 m over 150 mm thick PCC(1:4:8) type D2 using 40 mm graded crushed stone aggregate including necessary formwork and excavation complete all as specified and directed |
| 29 | Supply , installation, testing and comission of Smart energy prepaid Meter confirming to IS-16444: 2015 (Reaffirmed 2020) and as ammended time to time, AC whole current, three phase, 4 wires Smart Energy Meter of rating 415 Volt, 10-100 Amps,50 Hz , Class 1, enclosed in polycarbonate box complete as specified in CEA notification. The meter shall communicate with Head End System (HES) on any of the communication technologies mentioned in IS-16444 Part-I. The slection of communication technology should be as per the site conditions and as per design consideration of AMI Implementing agency to meet the performance. The smart meters should be based on RF Mesh communication technology or Cellular communication technology and carry min 5 yrs warranty complete all as specified and directed. |
| 30 | S&F LED type decorative wall mounted light fitting sutable for LED lamp 9-20 W , housing- glass, frosted type, metallic frame and including one LED lamp 12 watt complete all as specified and directed. |
| 31 | S&F LED type bed side wall mounted light fitting 9/10 Watt , housing- glass, frosted type, metallic frame, adjustable type complete all as specified and directed. |
| 32 | S&F power unit suitable for upto 2.0 ton Air Conditioner having push ON-OFF push button switch, motor starter type, single phase, 4 module with and including mudular metal flush box with cover plates complete all as specified and directed. (For AC) |
| 33 | S&F modular type TV socket. RJ46, 1 module complete all as specified and directed. |
| 34 | S&F modular type Tele socket. RJ45, 1 module complete all as specified and directed. |
| 35 | S&F Modular blanking plate modular type suitable for fixing in modular switch board, complete all as specified and directed. |
| 36 | S&F Surge Protection Device (SPD) 4 module, 25 KA, 3Ph+N Right, T1+T2, limp 12,5 KA per pole, T2-60KA, complete and making connections by using necessary thimble/washersetc of copper/brass material complete all as specified and directed. (For Main DB) |
| 37 | Boring for bored cast-in-situ piles 450 mm dia. in any type of soil using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed. |
| 38 | Boring for bored cast-in-situ piles 600 mm dia. in any type of soil using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed. |
| 39 | M&L for Reinforced cement concrete (design mix) M-30 grade design mix as in Cast-in-situ piles etc., complete all as specified and as directed. Note: Pile shall be casted as mentioned in drawings. However, for payment purpose the length of pile shall be measured up to cut off level only. The unit rate quoted shall be deemed to included this aspect. |
| 40 | Carrying out initial pile load tests for 450 mm dia pile as per IS: 2911- Part 4 with carrying out necessary calibrated measuring devices like load/pressure guage, hydraulic jack, dial gauges and magnetic stands, submitting all the test reports to GE with proper presentation complete all as specified and directed. |
| 41 | Carrying out initial pile load tests for 600 mm dia pile as per IS: 2911- Part 4 with carrying out necessary calibrated measuring devices like load/pressure guage, hydraulic jack, dial gauges and magnetic stands, submitting all the test reports to GE with proper presentation complete all as specified and directed. |
| 42 | Conducting low strain integrity test on 450 mm diameter RCC cast-in-citu piles, data analysis and submission of report. (min 10 piles per visit) complete all as specified and directed. |
| 43 | Conducting low strain integrity test on 600 mm diameter RCC cast-in-citu piles, data analysis and submission of report. (min 10 piles per visit) complete all as specified and directed. |
| 44 | Carrying out routine pile load tests for 450 mm dia pile as per IS: 2911- Part 4 with carrying out necessary calibrated measuring devices like load/pressure guage, hydraulic jack, dial gauges and magnetic stands, submitting all the test reports to GE with proper presentation complete all as specified and directed. |
| 45 | Carrying out routine pile load tests for 600 mm dia pile as per IS: 2911- Part 4 with carrying out necessary calibrated measuring devices like load/pressure guage, hydraulic jack, dial gauges and magnetic stands, submitting all the test reports to GE with proper presentation complete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |