| 1 | Daikin MAKE Outdoor Unit-20 HP (Outdoor unit model no. RXYQ20ARY6) |
| 2 | Lifting and shifting old unit from terrace of Ayush Block to terrace of Night Shelter/Nursing college |
| 3 | Positioning, vaccumising, installation, testing & commissioning of outdoor unit at terrace of Night shelter/Nursing college |
| 4 | Indoor Unit (Daikin MAKE)Lifting, shifting, positioning & installation of Indoor-Cassette indoor alongwith remote controller intallation & commsioning (to be installed for indoor units) |
| 5 | 1 TR (Indoor Unit Model NO. FXFSQ32ARV16) |
| 6 | 2.6 TR (Indoor Unit Model NO. FXFSQ80ARV16) |
| 7 | 3.2 TR (Indoor Unit Model NO. FXFSQ100ARV16) |
| 8 | COPPER REFRIGERANT PIPINGSupplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 9 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 10 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 11 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 12 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 13 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 14 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 15 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 16 | Drain PipingSupply and installation of 6 mm thk nitrile rubber insulated UPVC piping from indoor unit drain pans to nearest floor drain / nearest drain complete with interconnection, flanges, elbows, tees, nuts, U-trap , Union Connection ,etc.The contractor has the whole side responsibility of terminating to nearest drain point with complete leakage proof. |
| 17 | 32 mm dia |
| 18 | 25 mm dia |
| 19 | Refrigerant Joints / Headers/ RefnetSupply, Installation, testing and commissioning of important Y joint fittings/refnet & header to all indoor units at all floors including alignment of joints complete as required |
| 20 | Control & Transmission Wiring |
| 21 | Supply, laying and commissioning of of control cum transmission cable of Size 2 C x 1 Sqmm PVC Insulated sheathered unarmoured industrial flexible bright annealed copper conductor for voltage grade 1100 Volts as per IS:694:2010 in suitable PVC conduits between indoor & outdoor units on cable tray as per the site requirement |
| 22 | Supply, laying and commissioning of power cable PVC insulated & sheathered unarmoured flexible 3 core x 2.5 Sqmm copper conductor cable voltage grade 1100V as per IS:694-2010 on cable tray as per the site requirement |
| 23 | Supply, laying and commissioning of power cable of Size 4C x 10 Sqmm PVC insulated and PVC sheathed XLPE armoured with aluminium conductor 1100 V grade conforming to IS:7098 (Pt-1) 1988 on cable tray as per the site requirement |
| 24 | Providing and fixing M.S. angle 50x50x5 mm to act as nosing with lugs of M.S. flat 10x5 mm, 10 cm long, forked at end 60cm apart (minimum three lugs to be provided), including necessary welding and applying a priming coat of approved primer on exposed surface etc. complete. |
| 25 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : |
| 26 | Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 27 | Refrigerant R-410Supply and filling the VRV unit with and making ready for use as required. |
| 28 | Cable TraysSupplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, layed on surface as per the site requirement i/c base/support of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 29 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 30 | MCBSupplying, fixing and commissioning of 63A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of 4 poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. IP 20 protected terminals & as per IS/IEC 60898-1 2002 |
| 31 | Supplying and fixing 3 Module PVC box of size 100mmX75mm along with modular base & cover plate for modular switches as per the site requirement. |
| 32 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as per the site requirement |
| 33 | 15/16 A switch |
| 34 | Supply and installation of FP enclosure box with cover complete as required on site |
| 35 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 36 | For Outdoor Unit-50 HPRepair,Testing and ensuring ready for use of Condenser Coil/AHU DX Coil of the following size:No. of rows-6No. Of Sections-2Connection of Supply/Return-2*28 dia/2*54 dia |
| 37 | Refrigerant Gas - R 410Supply and filling the VRV unit with and making ready for use as required. |
| 38 | Outdoor UnitSupplying, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed invertertype twin Rotary/Scroll Compressor(s),minimum two compressors (with individual separate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load.The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39°C. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building) For Heating & Coolibg both |
| 39 | Indoor UnitSupplying, Installation, Testing and Commissioning of following minimum capacity 4 way Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement in auto mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature. (Make will be same as of Outdoor) |
| 40 | 3.6 TR |
| 41 | Refrigerant PipingSupplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 42 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 43 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 44 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 45 | Supply and installation of 6 mm thk nitrile rubber insulated UPVC piping from indoor unit drain pans to nearest floor drain / nearest drain complete with interconnection, flanges, elbows, tees, nuts, U-trap , Union Connection ,etc.The contractor has the whole side responsibility of terminating to nearest drain point with complete leakage proof. |
| 46 | 32 mm dia |
| 47 | Control & Transmission Wiring |
| 48 | Supply, laying and commissioning of of control cum transmission cable of Size 2 C x 1 Sqmm PVC Insulated sheathered unarmoured industrial flexible bright annealed copper conductor for voltage grade 1100 Volts as per IS:694:2010 in suitable PVC conduits between indoor & outdoor units on cable tray as per the site requirement |
| 49 | Supply, laying and commissioning of power cable PVC insulated & sheathered unarmoured flexible 3 core x 2.5 Sqmm copper conductor cable voltage grade 1100V as per IS:694-2010 on cable tray as per the site requirement |
| 50 | Supply, laying and commissioning of power cable of Size 4C x 6 Sqmm PVC insulated and PVC sheathed XLPE armoured with aluminium conductor 1100 V grade conforming to IS:7098 (Pt-1) 1988 on cable tray as per the site requirement |
| 51 | Providing and fixing M.S. angle 50x50x5 mm to act as nosing with lugs of M.S. flat 10x5 mm, 10 cm long, forked at end 60cm apart (minimum three lugs to be provided), including necessary welding and applying a priming coat of approved primer on exposed surface etc. complete. |
| 52 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : |
| 53 | Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 54 | Cable TraysSupplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, layed on surface as per the site requirement i/c base/support of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 55 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 56 | MCBSupplying, fixing and commissioning of 63A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of 4 poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. IP 20 protected terminals & as per IS/IEC 60898-1 2002 |
| 57 | Supplying and fixing modular switch 1 module and 2M frame (65mm)to be installed on DLP trunking as per site requirement |
| 58 | Supply and installation of IP 55 plexo box with PVC membrane & Adaptor-4 Module as per site requirement |
| 59 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 60 | Testing & Commissioning of Central Temperature Remote Controller (Daikin Make) with integration with BMS complete in all respect Please Enable Macros to View BoQ information |