| 1 | ELECTRICAL WORK |
| 2 | PUMPS AND APPURTENANCES Supplying, installation, testing and commissioning of Electric Motor Driven Pressurization Terrace Pump having discharge of 900 LPM at 35 Mtr head complete with Pump Set, Electric Motor suitable for operation on 415 V ,3 ph, 50 c/s AC supply , Base Frame.Make-Wilo/KSB/Kirloskar |
| 3 | Supply & fixing of Terrace tank (5000 ltr) Fiber Water tank triple layer unbrakable extra thick and flexible material for long life new UV threaded lid to keep dust particles out with all needed accessories. (Mukta/Sintex or Equivalent make) |
| 4 | Supply, Installation of structural steel like ( Beam , Channel, Angle, Plate & Sheet) for 2 nos terrace tank base & barricade . |
| 5 | Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of One (1)- 63 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB, Digital Voltmeter with selector switch. DOL starter with O/L and Single Phasing Preventor suitable for 7.5 HP motor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.as per direction of engineer in charge Control panel for fire pumps for auto action.make-Legrand/schneider/ Siemens/ABB/Hagar /C&S /L&T/ Havells |
| 6 | Supply, Installation of Pump protection shed on terrace made by structural steel & sheet |
| 7 | PIPE & VALVES ETC. Supplying, installing, testing and commissioning of MS Pipes, ERW confirming to IS 1239 Pt - I HEAVY grade up to 150mm dia and pipes 200mm dia and above shall be M.S as per IS: 3589 with painting, suitable type of supports, anchor fasteners, bolts nuts, clamps, \\"U\\" bolts, malleable specials such as Reducers,Tees, elbows, flanges. Including cutting, Welding, fixing in / on walls, ceiling by using suitable supports etc, complete.Make-TATA/SAIL/JINDAL 100mm NB |
| 8 | 80mm NB |
| 9 | 25mm NB |
| 10 | Providing, fixing, testing and commissioning of following size manually operated hand lever type cast iron double flanged slim seal wafer type Butterfly valves with EPDM iron disc as per IS-13095 having pressure ratting PN -1.60 including fixing the same with supply of required jointing materials like rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of E.I.C. Make-Zoloto/Leader/Audco 100mm NB |
| 11 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Make-Zoloto/Leader/Audco 100mm NB |
| 12 | Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge.Make-H.Guru/G.Guru |
| 13 | Supply,Installation,Testing & Commissioning of Pressure Switch with cut-off bronze ball valves with integral strainer & flare nut (mixed ends) of suitable size with all accessories as per direction of Engineer-in-charge.Make-Danfoss/Indfoss/ Grundfoss |
| 14 | Supply,Installation,Testing & Commissioning of stainless steel strainer fabricated out of 1.6 mm thick stainless steel sheet Y Stainer with 3 mm dia hloes with stainless steel flange as required. Make- -Zoloto/Leader/Audco 100mm NB |
| 15 | Supplying, installing, testing and commissioning of Gun metal chrome finished Ball valves with fittings of screwed end type.Make-Kartar/Zoloto/ Leader/Kirloskar/Eq 25mm NB |
| 16 | 15mm NB |
| 17 | DOWN COMER SYSTEM Supply,Installation,Testing & Commissioning of Stainless steel Hydrant Valve / Landing valve, of 63 mm NB size, type-A, single headed , oblique type, as per IS :5290/93 and as per direction of Engineer-in-charge.Make-Newage/Minimax/ Fireshield |
| 18 | Supply,Installation,Testing & Commissioning of SS short branch pipe with 63 mm male inlet and 19 mm outlet nozzle, as per IS:903 and as per direction of Engineer-in-charge. Make-Newage/Minimax/ Fireshield |
| 19 | Supply,Installation,Testing & Commissioning of 63 mm NB and 15meter long RRL Fire Hose fitted with 63mm intstantaneous stainless steel male & female SS coupling, complete by GI wire binding for Internal Hydrant as per direction of Engineer-in-charge. Make-Newage/Minimax/ Fireshield |
| 20 | Providing supply & fixing of MS Hose Box for of suitable size(750X600X250mm) to accomodate 2 nos. of 15/ 1 no of 30 mtr long fire hose and a branch pipe, wall mounted type as per direction of Engineer-in-charge. Make-Newage/Minimax/ Fireshield |
| 21 | Supply,Installation,Testing & Commissioning of Swinging pattern wall fixing first aid hose reel made from MS sheet and waterways and moving parts with rubber hose of 20 mm dia. and 30 mtrs. long with ABS(Plastic) shut-off nozzle as per IS: 444/IS: 12585 Type-I., complete with all accessories as per direction of Engineer-in-charge. Make-Newage/ Minimax / Fireshield |
| 22 | Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop cock confirming to IS:14845/2000 with ISI mark for water works purpose including fixing the same with hydrant riser including testing & commissioning the system etc. all complete as per approved specification & direction of Engineer-in-charge. Make-Zoloto/ Leader/Audco |
| 23 | Providing, fitting & fixing of 2-Way GM fire brigade connection consisting of 63 mm dia instantaneous type male couplings with built-in check valves, 150mm dia flanged outlet complete with bolts, nuts and rubber insertions confirming to IS:904 with ISI mark including testing & commissioning the system etc. all complete as per apporoved specification & direction of EIC. Make-Zoloto/ Leader/Audco |
| 24 | AEROSOL BASED FIRE EXTINGUISHERS Supply & Installation 8 gm Portable Aerosol based Automatic Fire Shield (Coverage: 0.008 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 25 | Supply & Installation of 20 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.2 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 26 | Supply & Installation of 30 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.3 m3) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 27 | Supply & Installation of 50 gm aerosol based Manual Fire Extinguisher (Duration:10-20 sec) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 5 years. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 28 | Fire buckets round bottom type enamel painted, white inside & Red out side and Letter \\"FIRE\\" in black out side and handle with mounting bracket. |
| 29 | Fire bucket stand fabricated by MS angles to install 3 Nos. of buckets. |
| 30 | SIGNAGES:-Providing and installing in position the following type of sign boards made out of 3mm thick flexyle photoluminescent based glow in dark sheeting with luminous properties enclosed in a weather proof Uvstabilized film with UV screen printing by imported links pasted over3 mm thick cast acrylic from front side with 6 mm thick acrylic, -20 to+80 deg C, Suitablefor indoor use, greenish yellow, glow visible upto 4-6 hr in total darkness.Make-Prolite/Bajaj |
| 31 | Illumination Glow light for Exit Indication with Battery Back-up. |
| 32 | FIRE ALARM SYSTEM Supplying, installation, testing and commissioning of Addressable Multi Detector(Smoke cum Heat) complete with base and isolator as per direction of Engineer-in-charge.Make-Morley IAS/Siemens/ Bosch/ Honeywell/Edward |
| 33 | Supply, Installation, testing and Commissioning of addressable manual call box made of polycarbonate with plastic break glass front and complete with monitor module MCB shall be recessed in wall .Make-Morley IAS/Siemens/Bosch/ Honeywell/Edward. |
| 34 | Supply Installation, Testing & Commissioning of wall mounting loop powered addressable type hooter with strobe and all accessories as per specification.Make-Morley IAS/Siemens/ Bosch/ Honeywell/Edward |
| 35 | Supply, Installation,Testing & Commisioning of Microprocessor based Addresable fire alarm control panel , fully networkable with each loop capable of taking 99 devices, 8 line x 40 character alpha- numeric liquid crystal display .The panel shall be soft addressable type . The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 8 hours with integral battery charger complete as required and as per specification. The fire alarm panel shall be suitable for software integration with BMS & PA system.Make-Morley IAS/ Siemens/ Bosch/ Honeywell/Edward 2 Loop Panel |
| 36 | Supply and installation of visual type response indicators with LED indicating lamp, housed in suitable MS enclosure with acrylic cover fixed in flush with wall to operate in conjunction with smoke/Heat detectors operating on 24 VDC installed above the false ceiling or below the false floor, complete with all accessories and fixing materials as required and as directed by Engineer-in-charge. |
| 37 | Supplying, installing, testing and commissioning of 2C x 1.5 mm², armoured, single stand, outer sheathed, FRLS, PVC insulated copper conductor cable confirming to specified IS standards .Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI 2 C x 1.5 Sqmm. |
| 38 | Supply of 16 sq.mm Single core core XLPE Al.Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster) |
| 39 | Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm on surface as required. |
| 40 | Supplying, installing, testing and commissioning approved make PVC FRLS conduits on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends etc. 25mm dia.Make-AKG/BEC/Precision/Norpack |
| 41 | DG Set Supply, Transportation, erection, testing and commissioning of 3 Phase, 415V, 50Hz, water cooled multi cylinder diesel generator set with alternator of 82.5KVA ( Make -Kirloskar / Jakson/Mahindra) out put contineous rating directly coupled Engine and Alternator with guard and mounted on a common base plate of Robust construction and complete with AMF panel having IP-52 protection, Acoustic Enclosure as per CPCB IV+ norms , sound absorbing material, to restrict sound level up to 75 dB up to 1 mtr distance and as per CPCB IV + norms etc as per following specifications mentioned below.Warranty period of panel must be 2 years ALTERNATOR:The alternator of the output rating shall be 3 Phase, 415V, 50Hz, Ac , 0.8 P.F. lagging at 1500 RPM. The alternator is self excited, self regulated, and shall confirm to IS: 13364 of 1992 with regulation of +5% from no load to full load. degree of protections shall be IP21. ENGINE:. Diesel Engine start, developing suitable BHP output at 1500 RPM with mechanical / electronic governing so as to enable the alternator to give 82.5KVA continuous output at 0.8 P.F. lagging at NTP conditions. The diesel engine shall be capable of providing 10% O/L for 1 Hr for every 11 Hrs of continuous running at full load. The engine with 1st filling of oil and Diesel etc.01. Exhaust pipe of required size and length with insulation or clading.02. Diesel tank suitable for 8 to 12 Hours running capacity.03. Industrial Silencer.04. SMF Batteries with leads as per the Manufacturer standards AMF PANEL: Cubical, Compartmentalized, AMF Panel Baord with all Power & Control Contractors,for both main & dg along with battery charger,relay,timer & all required accessories, Meters and other accessories, Internal Wiring, connection, inter-connection etc. for Trouble Free smooth function for 82.5KVA DG Set complete with Battery Charger & leads as required. BASE PLATE: Common Base Plate of required size for mounting of Engine Alternator Set fabricated from MS Channerl and vibration damping arrangement with cushy foor mounting including paintng etc. as required FOUNDATION: Suitable size Cement Concrete (1:2:4) foundation duly plastered and finished with neat coat Cement as required along with smoke exhaust system piping including base frame of structure & lightening protection system. *It also includes 2 nos copper plate earthing and 4 nos copper plate earthing for neutral, control cable of 15mtr 2.5sqmm 6core , civil foundation work.(The Manufacturing of DG set shall not in any case be more than six months old from the date of award of work) |
| 42 | Lightning Protection Supply of 8 mm Aluminum Round Conductor.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 43 | Supply of Roof conductor holder for parapet- Polyamide Conductor holder:With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.Weather and temperature resistant from -35 to +90 degree Celsius tested.Conductor holder @ 1 meter distance.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 44 | Supply of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 45 | Supply of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Tested as per IEC 62561.(2nos/expansion piece ).Make-OBO/Dehn/ABB |
| 46 | Supply of 1 mtr vertical air terminal with mounting accessories on the flat surface to meet the requirements of IS/IEC 62305.Tested for Electrical , mechanical and chemical as per IEC 62561. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 47 | Supply of Vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 Nominal size Ø10/16 mm aluminium rod: 3 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 48 | Supply for Providing of Stand for Fang Fix system 16 kg with base and clamp ,made up of frost resistant concrete and clamp testedupto 100KA lightning current . Make-OBO/Dehn/ABB |
| 49 | Supply for Providing of Stand for Fang Fix system 16 kg made up of frost resistant concrete. Make-OBO/Dehn/ABB |
| 50 | Supply of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer.Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 51 | Supply of IP 66 Poly Propylene Junction Box. Installation at 1Mtr Height For Test Joint .Internal dimensions: 100x100x48 mm Make-OBO/Dehn/ABB |
| 52 | Supply of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor Hot Dipped Galvanized. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 53 | Supply for Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 54 | Supply of flat conductor holder- Fit: FL 30, With mounting hole 6.2 x 22 mm, With 2 cylinder bolts M6 x 16 and over-piece from hot-dip galvanised steel, Bottom section from polyamide, black. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 55 | Supply for Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. Make-OBO/Dehn/ABB |
| 56 | Supply of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2mm with copper coating thickness of 250micron tested as per IEC 62561-2 Make-OBO/Dehn/ABB |
| 57 | Supply of universal clamp made of SS to connect rod with flat conductor Make-OBO/Dehn/ABB |
| 58 | Supply of Earth conductivity enhancing mineral compound shall be of 25kg/pit tested as per IEC 62561-7,TCLP tested Make-OBO/Dehn/ABB |
| 59 | Supply of The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Make-OBO/Dehn/ABB |
| 60 | Installation of The above arrangements including all accessories as per Direction of Engg. In charge. |
| 61 | S/F of 100A Onload Change Over with SS Enclosure.Make:Legrand/Hager/Schneider/Siemens/ABB/L&T |
| 62 | S/F of 250A Onload Change Over with SS Enclosure.Make:Legrand/Hager/Schneider/Siemens/ABB/L&T |
| 63 | Supply of 95 sq.mm Single core XLPE Al.Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster) |
| 64 | Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm on surface as required. |
| 65 | Supply, installation, testing and commissioning of UPVC pipes for filling line from existing tank to fire water tank on terrace floor with all accessories. |
| 66 | S/IT/C of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 67 | Supplying and laying 25 mm x 5 mm GI earth strip ISI marked on surface or in recess for connection etc as required. Please Enable Macros to View BoQ information |