| 1 | Excavation in post holes (or similar holes) each not exc. 0.50 Cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm in any type of soil complete all as specified and as directed. |
| 2 | M&L for Plain Cement Concrete, 1:3:6, type C2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed |
| 3 | M&L for Steel work in tubular trusses including special shaped washer etc, complete using ERW or induction butt welded tubes conforming to IS-1161-1979 grade St-240 complete all as specified and as directed. |
| 4 | M&L for Plates (plain or chequered) channels. Square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment complete all as specified and as directed. |
| 5 | M&L for Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc. 5cm and not exc. 10cm long complete all as specified and as directed. |
| 6 | M&L for Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed. |
| 7 | M&L for Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof ridge/cladding to wall, fixed with self tapping screws complete all as specified and as directed. |
| 8 | M&L for hard core of broken stone or boulders of gauge n.exc.63mm, deposited, spread, levelled in layers n.exc.15cm thick, watered and rammed to a true surface complete all as specified and as directed. |
| 9 | M&L for 100mm thick PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in sub base complete all as specified and as directed. |
| 10 | M&L for 100mm thick Cement Concrete 1:2:4 type B1 (using 20mm graded stone aggregate) as in floor finish cement concrete surface even and smooth without using extra cement complete all as specified and as directed. |
| 11 | Forming 12mm thick & 150mm deep expansion joints filled with pre-formed bituminous filler and top 30 mm primed and sealed with sealing compound, Grade ‘B’ complete all as specified and as directed. |
| 12 | Forming Contraction (Dummy) joints 65mm deep x 10mm wide, filled with sealing compound Grade ‘B’ complete all as specified and as directed. |
| 13 | M&L for Precast Cement Concrete Type C1 1:3:6 (20mm graded aggregate) block masonry with solid blocks, exc. 10cm in width and setting in mortar 1:6, complete all as specified and as directed. |
| 14 | M&L for Rendering 10mm thick on RCC surfaces or concrete surfaces in CM 1:4 finished even and smooth surface without using extra cement complete all as specified and as directed. |
| 15 | M&L for preparation of newly plastered surfaces and applying two coats of cement base paint over a coat of primer complete all as specified and as directed. |
| 16 | M&L for painting to steel surfaces of any description over 10 cm width or girth not otherwise described and painting two coats of synthetic enamel paint over one coat of Red oxide primer including preparation of new steel surfaces complete all as specified and as directed. |
| 17 | M&L for Mild steel sheet eaves gutters, galvanised class 3, half round with rounded edges 150mm dia & 1.25 mm thick sheet complete all as specified and as directed. |
| 18 | M&L for PVC (SWR) pipes 110mm single socketed in any length with rubber ring joints fixed to walls complete all as specified and as directed. |
| 19 | M&L for 75mm thick PCC 1:3:6 , type C-2 using (40mm graded stone aggregate) as in plinth protection finished even & smooth without using extra cement making 10mm wide joints at every 3m interval and at every corner, filled with hot mix of bitumen complete all as specified and as directed. |
| 20 | S&F flat iron as in wind ties for roof including securing bolts including cutting and all necessary drilling , bolting or riveting etc and similar work conforming to Fe-290 Gde- E- 165, complete all as specified and directed. |
| 21 | M&L for submain wiring with FRLSH copper cable in concealed type 2x1.5 sqmm and 1x .5 sqmm earth wire drawn in PVC conduit of 20mm dia and making good after completion of wiring complete all as specified and directedNote : 3 runs of cable and one run of PVC conduit shall be measured as one unit. |
| 22 | Supply, lay and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core (From existing panel to DB) complete all as specified and as directed. |
| 23 | Excavation in trenches, n. exc. 1.5m wide and n.exc. 1.5m in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n.exc. 10 sq m on plan and n. exc. 1.5m in depth and getting out in any type of soil complete all as specified and directed. |
| 24 | Returing, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25cm. Complete all as specified and directed. |
| 25 | Removing excavated material to distance n. exc. 50m and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and directed. |
| 26 | Supply and lay of DWC (Double corrugated) HDPE pipe ISI marked IS-14390 Part-II, of outer dia 40mm and inner dia 32mm with smooth internal and profied external surface for non pressure under ground cable including all connected accessories like coupler \\"O\\" ring etc, for protection of cable complete all as specified and directed. |
| 27 | S&F sheet metal enclosure for DBs (double door verticle type) when MCB's to be used, Single Pole and Neutral, 8 ways including locking plate with 200 amps rated bus bar, 240 volts fixed sunk/flush to the wall complete all as specified and directed. |
| 28 | S&F MCB SP 5 to 32 Amps rating 240V, 10KA with connection and commissioning complete all as specified and directed. |
| 29 | S&F MCB SPN 32 Amps rating 240V, 10KA with connection and commissioning complete all as specified and directed. |
| 30 | S&F LED flood light 50 watt, 6500K, 230 V AC outdoor type with thermal management in multiple optics and equipped with IP65 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed. |
| 31 | M&L for testing and Earthing complete with galvanised steel earth plate elecrode of size 600×600cm× 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to GI earth lead wire of size 4.00mm dia by means of bolts, nuts, check nuts and washers ofwashers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work PCC (1:2:6) type C-1 with suitable size of CI cover plate with angle iron frame and opening arrangement ) incl providing copper sulphate and salt in alternate layer of 15 cm compacted thickness all around the earth electrode with funnel and 20 mm bore galvanized iron watering pipe ( light grade) wire mesh, copper lugs, complete in all respect,protected by 40 mm bore (light grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc 50 mtr and necessary testing on completion complete all as specified and as directed. Please Enable Macros to View BoQ information |