| 1 | Wiring for light point/fan point/exhaust fan point/call bell point with 1.5 sq.mm FR LS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch,modular plate, suitable size G.I/PVC box and earthing the point with 1.5 sq.mm. FR LS PVC insulated copper conductor single core cable etc as required. |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | a) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | b) 2 x 6 Sq.mm + 1 x 6 sq.mm earth wire |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 8 | Wiring for light / power plug with 2 x 4 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit alongwith 1 No. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 9 | Supplying of LED Batten Luminaire 20 watts comprises of extruded aluminium housing,polycarbonate diffuser Make Philips Model BN170CLED20S-6500 PSUL120 or Equivalent Make- Crompton, Bajaj, Havells |
| 10 | Supplying of BEE- 5 star energy efficient BLDC Ceiling fan (1200mm sweep) without Remote for operation of 230v, i/c wiring down rod standard length (upto 30Cm) with all accessories etc as required. Make:- Crompton, Energion Riviera (w/o Remote) or Equivalent Make Havells, Usha, Bajaj |
| 11 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 12 | Installation, testing and commissioning of ceiling fan, including wiring with the down rods of standard length (up to 30 cm) with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 13 | Installation, testing and commissioning of pre-wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc, directly on ceiling / wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 14 | Supplying and fixing 3 pin 5 Amps ceiling rose on the existing junction box/wooden block including connections etc as required. |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface / recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 16 | a) 8 way,Double door |
| 17 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 KA \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 18 | a) Single pole |
| 19 | Supplying and fixing following rating, double poles, 240 volts, isolater in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | a) 40 Amps |
| 21 | Supplying, Installation, testing and commissioning of ASHLOK make SEE brand safe earthing electro type-19, 50mm dia,length 2 mtrs and inner space to be filled with crystaline conductive mixture including filling up with electrodite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. |
| 22 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 23 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 24 | Supplying and ercetion of metering box made out of SMC of overall size 350mmx250mmx150mm with hinged cover and locking arrangement, viewing glass etc as required |
| 25 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 26 | (a). 5/6 amps switch. |
| 27 | (b). 3 pin 5/6 amps socket. Please Enable Macros to View BoQ information |