| 1 | ERECTION OF FOLLOWING AT 132 KV SUB-STATION FATEHGARH FOR INCREASING CAPACITY |
| 2 | Proper stacking and shifting of Main & auxiliary structure in open switchyard at erecting place as per norms. |
| 3 | Erection of Main & Auxiliary structure lattice type ATM,AXM,XPM,YMM,BBL,BCT,ALP,ABL etc. consisting of column, beam, peak, mast etc. and auxiliary structure for installation of isolator, CTs, PTs, LA etc. erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cutting and matching the member if required include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of main & auxiliary structure lattice type upon foundation and its proper tightening. |
| 4 | Making hole in part of GI Main/auxiliary structure / cutting of GI angle drilling of hole existing/ defective structure /plate/Angle and grinding machine with all cost of men, T&P etc. |
| 5 | Erection of following equipment as per instruction manual of various equipment’s and technical specification including shifting of material / equipment from store to erection site including all other associated works to complete the job satisfactorily. |
| 6 | Dismantling of 145 KV SF6 Circuit Breaker |
| 7 | Dismantling of 145 KV Current Transformer |
| 8 | Erection of 145 KV SF6 Circuit Breaker |
| 9 | Erection of 36 KV Vacuum Circuit Breaker |
| 10 | Erection of 145 KV Current Transformer |
| 11 | Erection of 36 KV Current Transformer |
| 12 | Erection and mounting of 145/36 KV CT junction box. |
| 13 | Erection of 145 KV bus Isolator without earth switch |
| 14 | Erection of 36 KV Bus Isolator. |
| 15 | Erection of 120 KV Lighting Arrestors |
| 16 | Erection of 30 KV Lighting Arrestors |
| 17 | Erection of 132KV PI |
| 18 | Erection of following control and relay Panels as per instruction manual and technical specification including shifting of panel from store to erection site including all other associated works to complete the job satisfactorily. |
| 19 | Erection of 132 KV control relay panel for 63 MVA Transformer. |
| 20 | Erection of 63 MVA RTCC Panel. |
| 21 | Bay wise interconnection of equipment with specified conductor of various 132 KV & 33 KV Equipment with Main /Transfer / jack Bus bar of ACSR Moose/Panther conductor. The work Includes cutting of conductor. Bending in proper shape .clamping with the help of clamp and all other associated work to complete job. |
| 22 | 132/33 KV,63 MVA Transformer Bay 132 KV side Bus |
| 23 | 33 KV side Transformer bay Twin Moose |
| 24 | Laying and Termination of following size control cable in trench/cable trays from different control room equipment to 132/33 KV Isolator, circuit breakers CT/PT & their junction boxes. Transformer marshaling box. Isolator box & other outdoor equipment’s installed in 132/33 KV switch yard as per cable schedule. Including carriage of cable drum from store and all other associated work. |
| 25 | Control cable of size 2 core x 2.5 mm2 |
| 26 | Control cable of size 4 core x 2.5 mm2 |
| 27 | Control cable of size 6 core x 2.5 mm2 |
| 28 | Control cable of size 10 core x 2.5 mm2 |
| 29 | Termination of control cable |
| 30 | Installation work of 63 MVA Transformer. |
| 31 | Shifting of main tank of 63 MVA Transformer from unloading point to the plinth up to 20 Mtr. distance (including turning of tank) including all T&P and labor required to complete the job satisfactorily, if required. |
| 32 | additional 5 meter shifting, if required |
| 33 | Complete erection of 63 MVA 132/33 KV Transformer by erection of radiator, conservator and all bushing oil pipe lines, cooling fans etc. to complete the job satisfactorily. |
| 34 | Circulation of complete Transformer oil in Transformer tank through centrifuging machine, centrifuging machine shall be provided by the contractor ,oil capacity (Approx 20 KL ) |
| 35 | Fabrication of 3 meter long electrode with 40 mm dia. M S round bar having 150 mm long conical shape by digging cutting, straightening etc. and then placing it vertical. inside the ground with Top 700mm below the ground level including shifting of MS round bar from storage place at the Sub-Station to switchyard. |
| 36 | Delta earthing of 120KV /33 KV LA's and132/33 KV 63 MVA Transformers neutral by consisting of 6/4/3Nos. 3.0 Mtr long electrode of 40mm dia. having 150mm long conical shape, its placing inside the ground in rectangular/triangular shape and connection all 6/4/3 Nos. electrodes with 75x10 mm MS flat laid on its edge and then this rectangle/triangle shape be connected to main earth mat at two place in opposite direction strictly as per drawing. |
| 37 | 120 KV Lighting Arrestors (Rectangle shape 6 electrode ) |
| 38 | 30 KV Lighting Arrestors (Rectangle shape 4 electrode ) |
| 39 | 132/33 KV 63 MVA Transformer (Triangular shape 3 electrode) |
| 40 | Painting of MS flat of different size after cleaning of rusted surface 1st coat of Red Oxide and 2 coat of Bus Green Paint to complete the work. |
| 41 | MS Flat of size 75x10 mm |
| 42 | MS Flat of size 50x6 mm |
| 43 | MS Flat of size 25x6 mm |
| 44 | Earthing of equipment’s by cutting straightening, bending, laying 700mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure, equipment’s structure. Transformer body and its neutral point including welding with main earthmat and with object to be earthed excavation of trenches its back filling. All other associated work as required to complete the work. MS Flat shall be provided by the contractor. |
| 45 | Laying of MS Flat of size 75x10 mm |
| 46 | Laying of MS Flat of size 50x6 mm |
| 47 | Laying of MS Flat of size 25x6 mm |
| 48 | Laying of 40 mm MS ROD earthmat in switchyard after digging of 0.5 mtr deep trench in earth and laying of MS Round will all associated work |
| 49 | Obtaining of NOC from office of electrical safety directorate lucknow for the first time energisation of 63 MVA 132/22 KV Transformer and associated bay (including payment of fee as per challan) payment shall be on actual basis |
| 50 | Installation of ABT meters at the panel and interconnection of these meters with DCU |
| 51 | Maintenance work on smoke detector alarm system installed at the substation control room |
| 52 | Vaccum cleaning of existing optical type smoke detectro installed inside control room. battery room and other associated areas. the work includes the removeal of smoke detector from its base and after cleaning of the detector refixing of the smoke detector to the vase along with keeping the connection of detector healthy including repair of lugs/terminals/wiring etc. |
| 53 | Checking of manual call point by breaking of the glass and then replacement of teh glass with new glass to ensure the proper functioning. |
| 54 | checking of the operation fo hooter installed inside and outside of teh control room for tis proper functioing by creating artificial faults |
| 55 | Replacement of SMF battery with suitable rating as required for 24 hour backup make exide/amco/standard make |
| 56 | Supply and installation of backlit facility for the control room building marking for various emergency and fire exit. |
| 57 | Work of cleaning of Control Panel, along with the cheking of each zone for its proper functionality, replacement of faulty connectors . The work includes proper functioning of AC/DC fuse indication by removing the fuse, functioning on Battery (AC fail) , checking of earth fault and checking of individual zone to ensure the working, replacement of any faulty wire and other item if needed. |
| 58 | Providing and fixing of different types of plates and boards |
| 59 | Providing and fixing of red, yellow and blue coloured name plates made of 2mm thick aluminium sheet of dimension 300mmX200mm covered with 3mm HIP retro reflective sheet with details of equipments written by 3M HIP retro reflective materials in white coloured letters to be fixed with the help of clamps, nuts and bolts at already installed equipment structures in the switchyard with all cost of plates, 3M sheets, nuts and bolts, miscellaneous material, including T&P and labour, |
| 60 | Providing, fixing and installation of 'R' Y' & 'B' Phase Plate consisting of red, yellow, blue colours, round in shape of diameter 150 mm duly made of 2 mm thick Aluminium Sheet with face to be fully covered in Red, Yellow, Blue Colours 3 M HIP Retro reflective sheet and the phase plate set to be fixed with the help of suitable size GI Bolts, Nuts on already installed equipment structures with all cost of plates, 3M sheets, nuts and bolts, miscellaneous material, including T&P and labour. |
| 61 | Providing and fixing of Danger Plate of size 300mm x 200mm displaying sign of Skull and Cross Bones Lettering of Caution as per direction of Engineer Incharge duly made of 2mm thick aluminium sheet with face to be fully covered with White Color 3M HIP retro reflective sheet and the letters shall be computer cut Red Color 3M HIP Retro reflective Sheet. The Danger Plate is to be fixed with the help of clamps, nuts and bolts at already installed equipments and various structures at the Sub-Station with all cost of plates, 3M sheets, nuts and bolts, miscellaneous material, including T&P and labour. |
| 62 | Providing, fixing & Installation of Reflective Sign Board of size 8ft x 6ft for Sub-Station and Division Office Name & Address to be fixed at the Entrance of Sub-Station. The Board shall be made of 4mm thick aluminium sheet covered with 3mm HIP retro reflective sheet and shall be provided with back support frame & fixing arrangement. The Board should be fixed on Frame made with 50mm x 6mm angle and angle fixed on ground with proper concreting with desired mixture of Stone Concrete, Cement & Coarse Sand for holding the board and frame at desired location as per direction of Engineer-in charge |
| 63 | Providing, fixing & Installation of Prohibited Area Sign Board of size 4ft x 3ft duly made of 2mm thick aluminium sheet with side border and with proper fixing arrangement. The face of the board shall be fully covered with 3M Vinyl Sheet in Red Color and having letters in computer cut self adhesive #M Vinyl Sheet in white color. |
| 64 | Glow sign Board of size 8 ft x 6 ft for sub station single line diagram to be fixed in the control toom building of the sub station the glow sign board illuminated using LED tube lights inthe sufficient quantity. the board shall be made of acrillic sheet and shll be provided with back support frame and fixing arrangement with name of substation |
| 65 | Providing and fixing and installation of following instruction boards of size 4ft x 3 ft duly made of wooden board with side beading with proper fixing arrangement to be fixed in the control room and the face to be convered with 3 M Vinyl sheet. |
| 66 | Fire Fighting instruction Display Board |
| 67 | General instruction Board |
| 68 | 110/48 Volt DC Battery operating instruction Board |
| 69 | Retro reflective sign board of size 2ft X 1.5 ft duly made of 2 mm thick aluminium sheet fully covered with 3 M DG Cube type retro reflective sheet of yellow colour. the leetrs and symbol shall be computer cut and blue colour, board is to be provide alongwith the back support Frame make of MS angle of size 35mm x 35 mm x 5 mm with provision of 2 legs for grouting duly painted in Black color enamel paint and backside of the aluminium sheet shall be painted with smoke grey paint, complete in all respect and to be grouted with casting of C.C (1:2:4) foundations at the substation. |
| 70 | Carriage of various material from other substations |
| 71 | Safe Carriage of 14 km control cable of various size from 220 KV S/S Farrukhabad to 132 kv S/S Fatehgarh including loading and unloading of material. |
| 72 | Safe carriage of 0.927 KM Moose conductor from 220 KV S/S Neebkarori to 132 KV S/S Fatehgarh, work include loading and unloading of the conductor |
| 73 | Safe carriage of 0.660 KM Moose conductor from 132 KV S/S Talgram to 132 KV S/S Fatehgarh, work include loading and unloading of the conductor |
| 74 | STRENTHENING OF 132 KV MAIN BUS FROM SINGLE ZEBRA TO TWIN MOOSE CONDUCTOR WORK SHALL BE CARRIED OUT AS DETAILED HERE UNDER. |
| 75 | Dismantling of 132 KV Old/ Damaged Main bus bar (R, Y, & B) of Single Zebra conductor and lowering down of conductor from sub-station gantry to complete dismantling work including dismantling of all associated Tension clamps, fittings & Disc insulators etc. and storage of old conductor at storage area.(1 job per phase per section) |
| 76 | Dismantling of single Panther conductor Jumpers of T/Fs isolators 132 KV feeders bay from main bus to BSI and 132 KV PT |
| 77 | Stringing and proper sagging of new 132 KV Main bus bar Sections (R, Y & B) by Twin Moose conductor the work includes fitting of tension clamps, Hoisting of 70 KN Disc, tension fittings, Spacers PG Clamps etc. and cutting of conductor as required.(1 job per phase per section) |
| 78 | Jumpering of Twin Panther conductor Jumpers of T/Fs isolators 132 KV feeders bay from main bus to BSI and PTs |
| 79 | Supply of following material for construction of 132/33 KV Bay for additional 63 MVA T/F 4 , Modification of existing 132 KV BAY of 40 MVA T/F and strengthening of 132 KV main bus from single Zebra conductor to twin Moose :- |
| 80 | PG Clamp Moose to Moose |
| 81 | PG Clamp Moose to Panther |
| 82 | PG Clamp Panther to Panther |
| 83 | Spacer for 250mm spacing for Twin Moose Conductor 02 bolted complete with hot dip galvanized nut, bolts & washer as per technical specification. |
| 84 | 33 KV Circuit Breaker clamp suitable for Twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification. |
| 85 | 33 KV Isolator clamp suitable for Twin Moose conductor one side connecting the Twin Moose conductor and another side a plate with 04 Nos. 12mm dia. hole as per technical specification with HDG nut & Bolt. |
| 86 | 33 KV CT clamp suitable for Twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification with HDG nut & Bolt. |
| 87 | 132 KV Isolator clamp suitable for Twin Panther conductor one side connecting the TWIN Panther conductor and another side a plate with 04 Nos. 12mm dia. hole as per technical specification with HDG nut & Bolt.(as per sample) |
| 88 | 132 KV section Isolator clamp suitable for Twin Moose conductor one side connecting the Twin Moose conductor and another side a plate with 04 Nos. 12mm dia. hole as per technical specification with HDG nut & Bolt.(as per sample) |
| 89 | Bolted type single Tension fitting with turn buckle for Twin ACST Moose Conductor suitable for 1x10 No Disc insulators complete with hardware set as per technical specification. |
| 90 | Bolted type single Tension fitting without turn buckle for Twin ACST Moose Conductor suitable for 1x10 No Disc insulators complete with hardware set as per technical specification. |
| 91 | 40 mm MS Rod for Main Earthmat |
| 92 | LED Flood light Luminaries type FL-1 (150W) as per technical specifications. Please Enable Macros to View BoQ information |