| 1 | Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) of size 95 Sqmm 3.5 Core & laid in trenches/pipes or fixed on pole Complete all as per specified and directed by Engg-in-Charge. |
| 2 | Excavating in trenches not exc 1.5 metre wide and not exc 1.5 metre in depth for foundation etc or for laying of cables, pipes etc and getting out in soft/loose soil complete all as specified. |
| 3 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point all as specified and directed by engineer-in-charge |
| 4 | Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick. |
| 5 | M&L for tibba sand cushioning to under ground cable in trenches/existing cable trenches/ducts in layers of 8cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engr in charge |
| 6 | M&L Stone patti 40 to 50 mm thick rough dressed Jodhpur stone slab cover in trenches for protection of cable 25 to 35 cm wide and not less then 60 cm in length laid dry abutting each other with gap between adjacent slab not excedding 10mm over sand cushioning complete all as specified and directed |
| 7 | Supply and erecting cable route marker for LT Cable made of precast RCC (1:2:4) using 20mm graded stone aggregate cast in pillar of size 15x10x60cm including reinforcement with 4 nos 10mm dia deframed bars of 55 cm length and link/strapps of 8mm dia bras at 150mm C/C and in fixing in ground level duly pained & written LT .433 KV including PCC & earth work |
| 8 | M&L for GI Tubes, of size 40mm bore, light grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed. |
| 9 | M&L for GI Tubes, of size 50mm bore, light grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed. |
| 10 | M&L for GI Tubes, of size 80mm bore, light grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed. |
| 11 | Boring of Holes under road,Pavement,hard,standing by trenchless technology using ultra sounding techanique and necessary machine including HDPE pipe of 300 mm dia for 0.4 mpa working pressure |
| 12 | PCC (1:3:6) type C1 using 20 mm graded aggregate for making good the disturbed portion of road/floor/platform etc including form work compaction etc all as specfied and directed by Engineer-in-Charge. |
| 13 | Design, supply, erection, commissioning and testing KIOSK outdoor type LT feeder pillar box, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Copper bus bar for distribution system and type tested at CPRI, complete with bus bars and control wiring complete including dismantling of old LT panel and including the following, LT panel 1INCOMING : (a) On load change over switch, 415 Volts, 50 Hz, 4 pole - 01 Nos (b) MCCB 100 Amps, 4 pole , Thermal magnetic release, 16 KA adjustable 70 to 100%, 415 Volts, 50 Hz - 01 Nos OUTGOINGS : (a) MCCB 100 Amps, 4 pole , Thermal magnetic release, 16 KA adjustable 70 to 100%, 415 Volts, 50 Hz - 02 Nos |
| 14 | Supply, install, testing and Commissioning of APFC Panel of capacity 25 KVAR with relay 05 step auto/manual operation suitable for improving PF up to unity Double door Outdoor type CPRI Approved hut type top made out of 3 mm thickness CRCA sheet with channel / angle iron pedestral frame, compartmental type , dust free, vermin proof , IP 52 protection cable alley , cable entry hole at the bottom and mounting on ISMC 100 Channel duly grouted on in and including PCC (1:3:6) platform raised at 30 cm above Ground level Suitable for comprising and provision of the following Accessories :- (a) Incommer MCCB 4 pole 415 volts with Adjustable type 100 Amps with breaking capacity 36 KA complete - 01 Nos(b) Bus bar aluminimum of suitable capacity for phases and neutral -01 Set. (c) Capacitor duty contactor of MO C type of required capacity - 01 Nos (for each capacitor bank) (d) Digital Micro processor based power factor correction Relay of suitable step operation suitable for 25 KVAR capacity of APFC panel - 01 Nos (e) 25 KVAR capacitor bank consisting of 5 Steps of operation including of Capacitors of voltage 450V long life heavy duty type 5 x 05 KVAR with suitable MCCB as back up protection. (f) 5 KVAR fixed heavy duty type capacitor (f) Digital Ammeter with selector switch and CTs of suitable capacity. (g) Digital Voltmeter with selector switch of suitable capacity. (h) Internal power and control wiring with suitable size of PVC insulated copper wire and LED indicating lamps.. Please Enable Macros to View BoQ information |
| 15 | Supply, install, testing and Commissioning of APFC Panel of capacity 25 KVAR with relay 05 step auto/manual operation suitable for improving PF up to unity Double door Outdoor type CPRI Approved hut type top made out of 3 mm thickness CRCA sheet with channel / angle iron pedestral frame, compartmental type , dust free, vermin proof , IP 52 protection cable alley , cable entry hole at the bottom and mounting on ISMC 100 Channel duly grouted on in and including PCC (1:3:6) platform raised at 30 cm above Ground level Suitable for comprising and provision of the following Accessories :- (a) Incommer MCCB 4 pole 415 volts with Adjustable type 100 Amps with breaking capacity 36 KA complete - 01 Nos(b) Bus bar aluminimum of suitable capacity for phases and neutral -01 Set. (c) Capacitor duty contactor of MO C type of required capacity - 01 Nos (for each capacitor bank) (d) Digital Micro processor based power factor correction Relay of suitable step operation suitable for 25 KVAR capacity of APFC panel - 01 Nos (e) 25 KVAR capacitor bank consisting of 5 Steps of operation including of Capacitors of voltage 450V long life heavy duty type 5 x 05 KVAR with suitable MCCB as back up protection. (f) 5 KVAR fixed heavy duty type capacitor (f) Digital Ammeter with selector switch and CTs of suitable capacity. (g) Digital Voltmeter with selector switch of suitable capacity. (h) Internal power and control wiring with suitable size of PVC insulated copper wire and LED indicating lamps.. Please Enable Macros to View BoQ information |