| 1 | Testing, checking & fault finding of Automatic Fire Detection, Fire Alarm system comprising of Fire control panels, Fire Detectors, Manual call points, Electronic Hooters etc. assessing the faults and material required for repairing and rectification of faults i/c rectification of minor faults, testing for proper functioning etc. complete as required. |
| 2 | Building with G+1 Floor having Main and Local Fire Alarm Control panels (Aska & Bhanja Nagr Telephone Exchange) |
| 3 | Building having One Floor only with Main Fire Alarm Control panel (Chhatrapur and Parlakhemundi Telephone Exchange) |
| 4 | Supply, installation testing and commissioning of following Zones UL listed Microprocessor based Fire Alarm Control Panel Made of 16/18 SWG CRCA sheet powder coated, finish suitable for operation with 220V 50HZ AC mains power supply with standby battery backup 24Volt DC power supply and built in charger (without batteries) , normal operating voltage 24 v DC, compatible with all types of conventional detectors, manual call points and normally opened dry contact devices, 16X2 Dot matrix display, fully compatible with UL-864 and NFPA-72 etc. complete as required as per details specifications. (make- Agni Instruments Engineers (P) Ltd /GST / Honeywell / System sensor / Ravel) |
| 5 | 6 Zone Main Fire Alarm Control panel without PA system (Bhanja Nagar & Chhatrapur) |
| 6 | 4 Zone Main Fire Alarm Control panel without PA system (Aska, Bhanja Nagar & Parlakhemundi)) |
| 7 | SITC of sealed maintenance free battery of capacity not less than the following capacities with all accessories etc as reqd. (Exide /Amco/Superior) |
| 8 | 2X7AH 12Volts |
| 9 | Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Photo electric / Ionization type Smoke detector with base (Blinking LED type) made of ABS plastic with all accessories, suitable for operation on 24V DC, internal protection class: IP23, dual pulsing LED with 3600 visibility, relative humidity: ≤95%; non-condensing and EN54 compliance of approved make etc. as required. (Make- Apollo / GST/ Honeywell / System sensor) |
| 10 | Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Multi detector (fixed cum rate of rise heat Detector using a thermistor, raises an alarm when the detector reaches 590C (Fixed) or when the change in temperature exceeds the rate of rise of 110C/min) with base (Blinking LED type) made of ABS plastic and all accessories, suitable for operation on 24 v DC, internal protection class: IP23, dual pulsing LED with 3600 visibility, relative humidity: ≤95%;non-condensing and EN54 compliance of approved make etc. as required. (Make- Apollo / GST / Honeywell / System sensor) |
| 11 | Supply, installation, testing and commissioning of electronic hooter cum speaker made of 16/18SWG CRCA sheet duly powder coated with PO red colour, output not less than 80db @25mtr, LMT with adjustable sound output of 2.5 watt,5 watt, suitable knock out for cable entry from top suitable for operation on 100/70 volt RMS AC supply etc. as required. (Make- Agni Instruments Engineers (P) Ltd/Apollo / Honeywell / GST/ system sensor/ Ravel ) |
| 12 | SITC of manual push button station (pill box) Manual Call Point in MS Housing for Conventional Fire Alarm System with glass for breaking up in case of fire and hammer with chain etc. (Make- Agni Instruments Engineers (P) Ltd/Apollo / Honeywell / GST/ system sensor/ Ravel ) |
| 13 | Supply and laying of 2core 1.5sqmm copper conductor FRLS PVC insulated and PVC sheathed Un Armoured Cable on surface/recess for looping the fire alarm devices & providing power supply to sounder cum strobes etc. as required. (ISI) |
| 14 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for 2 core, 1.5 Sq. mm (19mm) size of PVC insulated and sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 15 | S/F ABS round box / MS Box on ceiling for fixing the detectors etc as reqd. |
| 16 | Supplying & Fixing of wall mounted Auto glow Signage Fire Exit Sign Board 3mm PVC Sheet with high Glow intensity in total Darkness. (Red and Green colour with exit symbols as per requirements) |
| 17 | Dismantling the existing Fire alarm panels i/c disconnection of all cables, marking the terminals etc. etc. complete as required. |
| 18 | Refilling of 4.5 KG CO2 type Portable Fire Extinguisher with fresh /sufficient quantity / quality of CO2 with proper weight and measure, labeling with date of refilling and expiry date of refilling as per the ISI standards and as per the norms of Fire Authorities including transportation to workshop/factory and back, loading, unloading etc, re-fixing the same in proper position and location as per the requirement and direction of BSNL authority. |
| 19 | Hydraulic Pressure Testing of 4.5 capacity CO2 type Fire Extinguishers as per IS: 5844 -1970 (Reaffirmed 2006) and submission of Test certificates etc. as required. |
| 20 | Refilling of Dry chemical powder type 4/5 Kg capacity fire extinguisher (Powder + new CO2 gas cartridge/ gas as per BIS standard). |
| 21 | Providing and fixing of Gas Discharge Hose & Horn for Co2 type Fire Extinguisher of 4.5 Kg Capacity |
| 22 | Providing and fixing Gun metal regulating valve with safety washers for 4.5 Kg capacity Carbon Dioxide type Fire Extinguishers as per BIS specifications. {(IS: 3224:2002 (Reaffirmed 2007)} (The dismantled scrap material may be retained by the agency) |
| 23 | Providing and fixing Hose pipe/Nozzle for Dry Chemical Powder Type Fire Extinguisher of 5 Kg. Capacity |
| 24 | Providing and fixing MS clamp for fixing CO2 4.5 Kg capacity / DCP 5 Kg capacity fire extinguishers on wall etc. as required. |
| 25 | Painting the Fire Extinguisher cylinders with appropriate signal red colour as per the standards after removing the rust etc. and supply and fixing of operating instructions stickers on the extinguishers having instructions and use of fire extinguishers as per standards etc. as required. |
| 26 | Supply and Fixing of Carbon Dioxide based (as per IS 15222), Stored pressure type, 4.5 Kg capacity fire extinguisher confirming to IS: 15683:2018 (with latest amendments), cylinder body made of steel (as per latest IS:7285), operating temperature from -200C to +600C with carrying handle, hose assemblies, mounting brackets etc. suitable for Class A,B & C fire, minimum effective discharge time 11sec or higher, fire ratings of 55B or better, BIS marking etc. as required. (Test report from Central Govt. Laboratory/NABL accredited Laboratory/ILAC accredited Laboratory or higher shall be furnished) |
| 27 | Transportation of 4.5Kg (Net) CO2 and 5Kg (Net) DCP Fire Extinguisher cylinders from Telephone Exchanges to Factory at Bhubaneswar for pressure testing, refilling and repairing and back to respective sites i/c loading, unloading, escorting and paying toll charges etc. complete as required. |
| 28 | For Aska Telephone Exchange |
| 29 | For Bhanja Nagar Telephone Exchange |
| 30 | For Chhatrapur Telephone Exchange |
| 31 | For Parlakhemundi Telephone Exchange Please Enable Macros to View BoQ information |