| 1 | Supply and laying of insulated 2 core x 16mm2 aluminium multi conductor twin core flat unarmoured cable to fixed on the suitable clamps and nuts /bolts etc make finolex/ lapp/ polycab/ havell's/Cirtina or its equivalent of ISI marked. The work shall be executed to the entire satisfaction of engineer-in-charge. |
| 2 | Supply and laying of insulated 2 core x 10mm2 aluminium multi conductor twin core flat unarmoured cable to fixed on the suitable clamps and nuts /bolts etc make finolex/ lapp/ polycab/ havell's/Cirtina or its equivalent of ISI marked. The work shall be executed to the entire satisfaction of engineer-in-charge. |
| 3 | Supply & Erection of 1x18 watt retrofit LED tube rod with batten Supply & Erection of 1x18 watt retrofit LED tube rod with batten made of aluminium housing with PC diffuser Lumen out put should be more than 100 lumens per watt (1800 LUM) with LM 79 report from NABL. The make of the fittings should beHavells/ Wipro/ Twinkle/ Surya/ Phillips/ Bajaj . The work shall be executed to the entire satisfaction of Engineer-in-Charge. |
| 4 | P/F of LED luminarie of size 2'x2' of 30-36 watt (595x595 mm) surface type including driver with system Lumens 3600-4000 Im having efficacy of minimum 100 lm/W. THD <10%, PF > 0.95, Having coloured temperature 4000-6500 K recess type suitable to be fixed in Armstrong/ grid ceiling. The fitting should provides soft light and glare free symmetrical illumination and is to be fixed in the existing false ceiling frame of make Havells/ Wipro/ Twinkle/ Surya/ Phillips/ Bajaj alongwith connection, testing and commissioning erc. This job also includes all petty material required to be entire satisfaction of Engineer-in-charge. Warranty:- The fixture should be comprehensively warranted to be repaired or replaced for any defect within 2 years of installations. |
| 5 | Supplying and fixing brass batten/ angle holder including connection etc. as required. DSR 1.34 |
| 6 | Supply and Installation of MS bracket for installation of flood light. The work shall be executed to the entire satisfaction of Engineer-in-charge. |
| 7 | S/E of 32mm dia X1m Long GI Pipe (Medium Class) Bracket for mounting of LED Street Lighting/Fitting on wall including bending the pipe of suitable size to the required shape (90 to 105 deg), 2 Nos M.S. Clamps with Nut, Bolts and Washer. GI Coating/Painting the flat iron with primer and finish paint as per relevant tender specifications |
| 8 | Supply & Erection of high power approx 18-20 Watt LED Street Light luminaries:High-brightness White LEDs sources with high transmittance LENS on each LEDs, system lumen output of Minimum 1800 lumens, in Maximum 18 watt System Watt Consumption with 100 lms/Watt system luminous efficacy, 4000 K to 6000 K color temperature & 70 CRI value for ensuring good quality light output. Life of at least 50,000 hours at 70% lumen maintenance & LED driver efficiency >95% Power factor greater than 0.90, THD<15% & min 6KV surge protection with operating voltage range from 120-270 V for ensuring lifelong high performance of luminaire, having in built protection against short circuit mis wiring, over voltage protection, the fixture is made of LM-6 Pressure die-cast aluminum with engraved company name & have IK05 & IP66 Class I protection with NABL Accredited LM-79 & LM-80 Report. The fixture should be comprehensively warranted to be repaired or replaced for any defect within 5 years of installations. The luminary should not be over power derived. The fitting shall be mounted on the plate bracket on existing pole including making connection, testing & energizing complete in all respect to the entire satisfaction of Engineer-in-charge The luminary should be make Philips/ Crompton/ Havell's/ Surya/ Wipro/Legero/HQ Lamps. |
| 9 | Supply & Erection of high power120 Watt LED Flood Light luminaries:High-brightness White LEDs sources with high transmittance LENS on each LEDs with peanut lens with toughened glass, secondary lens optics, system lumen output of system luminous efficacy of ≥120 lm/W, 4000 K color temperature & CRI<70 value for ensuring good quality light output. Life of at least 50,000 hours & LED driver efficiency >95%, potted driver and driver should comply cispr-15 and EMI/EMC compliance, Power factor greater than 0.90, THD<15% & min 4KV internal surge protection and 10KV External surge protection with operating voltage range from 120-270 V for ensuring lifelong high performance of luminaire, having in built protection against short circuit, over voltage protection, the fixture is made of LM-6 Pressure die-cast aluminum with engraved company name & have IK05 & IP66 Class I protection with NABL Accredited LM-79 & LM-80 Report. The fixture should be comprehensively warranted to be repaired or replaced for any defect within 2 years of installations. The luminary should not be over power derived. The fitting shall be mounted on the plate bracket on existing pole including making connection, testing & energizing complete in all respect to the entire satisfaction of Engineer-in-charge. The LED Street Light Fixture shall be installed on 7.5/9 mtr long pole. The luminary should be make Philips/ Crompton/ Havells/ Surya/ Wipro/Bajaj.The detailed specification for supply of LED Street light luminaries is as under (with 05 years warranty). 1. Thermal Management system Good Thermal Management system Management of LED should be provided and LED must be Mounted on heat sink conductive Aluminum with suitable large area Surface by means of fins to disciple Heat to ambient air.2. Applicable standard The fixture should confirm to Application BIS/IES standard/ IESNA LM 20 |
| 10 | Providing & Fixing Cable Junction box of size 250x200x100mm complete in all respect. The job included fixing of Junction box on the wall with all petty material as required. The work shall be executed to the entire satisfaction of Engineer-in-Charge. Make: Sintex |
| 11 | Supplying and fixing of following size of heavy duty ISI marked PVC conduit alongwith accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. Make: Diplast, BEC,AKG. 25mm |
| 12 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required... Make: ABB, Havells,Legrand, Northwest Wipro, Norysis, Captree (Murano), Schneider. |
| 13 | 3 Module DSR1.27.2 |
| 14 | 6 Module DSR1.27.4 |
| 15 | 12 Module DSR1.27.6 |
| 16 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connectioN.S (M.R) but excluding modular plate etc. as per existing installaed model as required. Make: Legrand, Northwest Wipro, Norysis, Captree (Murano), Schneider. |
| 17 | 3 pin 5/6 amp switch outlet DSR 1.24.1 |
| 18 | 15/16 amps switch outlet DSR1.24.3 |
| 19 | 3 pin 5/6 amp socket outlet DSR1.24.4 |
| 20 | 15/16 amps socket outlet DSR 1.24.5 |
| 21 | Wiring for circuit/ submain wiring along with earth wire with following szes of FRLS, PVC inslated copper conductor, single core cable in surface/recessed heavy duty PVC conduit ISI marked as required. Make: Finolex/Polycab/Havells/KEI. 2 x 2.5 sq mm + 1 x 2.5 sq mm as earth wire |
| 22 | Fabrication & erection of steel shutters for electrical niches as per following specifications FRAME: The shutter of suitable dimensions for electrical nitch shall be made out of 16 G.M.S.sheet. The shutter frame shall be 1-1/2”x1-1/2”x1-1/2” channel frame 4 Nos. ‘L’ type holdfasts for fixing the same on the wall. The size of the shutter frame should be suitable for 2Nos. door panels/single panel depending upon the size of nitchesDOOR PANEL: The door panel shall have support in U-Shape formation made from 16G.M.S. sheet with 4”x3/4”M.S. channel duly spot welded to give additional strength. The door panel shall be fixed with frame with the help of concealed M.S. hinges of suitable size having good strength. The door panel shall be provided with a bolting arrangement either of Godrej type or such type so as to interlock the door panel with frame. The handle shall be of superior quality and nickel plated to facilitate its opening. The door panel must have as arrangement to provide a pad lock. FINISHING: The frame & the door panel should be given anti-rust, anti-grease and phosphate treatment with 3 in 1 paste and then spray painted with two coats of paint of superior quality. The shutter should be earthed properly with the existing earth with No.8SWG wire after erasing the paint from the body of the Shutter. The rate includes cost of all labor and material reqd. to complete the job to the satisfaction of the Engineer-in-charge. |
| 23 | S / E of ceiling fans complete with aluminium blades, plastic canopies 2 Nos. double bal bearing, MS hanging rods, condenser, reels, clamps etc. The body of fan and blades should be white in colour. The job includes the cost of making necessary connections from the adjacent light point with 1.5sq.mm single core copper conductor cable. The sample of fans shall be gotapproved from the Engineer-in-charge of work before installation at site. The job also includes the cost of carriage, erection, testing, commissioning of fan, all labour and petty material required to complete the job to the entire satisfaction of the Engineer-in-Charge.[Size56\\" 1400mm sweep ceiling fan of Havells make Velocity White / Orient make Summer Breeze Crompton make Cool Breeze / Usha make Apollo Bajaj make Sabse. Tez only |
| 24 | Supplying and fixing two module stepped type electronic fan regulator on the existingmodular plate switch box including connections but excluding modular plate etc.as required.Make: ABB, Havells,Legrand, Northwest Wipro, Norysis, Captree (Murano), Schneider. DSR 1.25 |
| 25 | Supply and Erection of Exhaust fan of Size 12\\" Sweep 900 RPM with copper wound metallic body complete with motor, mettalic blades, double ball bearing with minimum power consumption, rigid frame with rubber mounting for silent operation,epoxy powder coating along with mettalic louver to be installed in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. |
| 26 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ woodenblock including connection etc. as required. |
| 27 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface/ recessed steel/ PVC conduit as required.Make: Finolex/Polycab/Havells/KEI |
| 28 | 3x 1.5 sq. mm DSR 1.17.3 |
| 29 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 40/63amps 240 volts \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 30 | Wiring for light point/ fan point/ exhaust fan point with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable in recessed heavy duty PVC conduit ISI marked with modular switch, modular plate, blanking plate if required, suitable size GI box and earthing the point with 1.5 sq mm FRLS PVC insulated copper conductor single core cable Iincluding GI Box, Concealed Light Box, Modular switch socket & 5/6A Switch single pole etc complete as required. Make: Legrand, Northwest Wipro, Norysis, Captree (Murano), Schneider, ABB, Havells.Group - C Cable: Finolex/Polycab/Havells/KEI |
| 31 | Supply & Erection of Brick Masonry Haudi of internal finished size 1.5’x1.5’x1.5’ (deep) with 1st class burnt bricks in cement sand mortar 1:5 ratio having 4.5” thick wall. The top of the haudi will be provided at the floor level with angle frame of size 40mmx40mmx6mm and shall be covered with the cover fabricated with angle iron frame of size 35mmx35mmx5mm. RCC casted with 8 Nos. MS Bar of suitable size. The haudi will be provided with 12.5mm thick cement plaster in 1:4 ratio complete in all respect as approved by the Engineer-in-Charge. The job also includes curing of the cemented/brick masonary work as per CPWD specification. |
| 32 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required Make: ABB, L&T, Schenider, Legrand 63 Amp |
| 33 | Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copper busbar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) Make: ABB, L&T, Schenider, Legrand, Havells 8 way, Double door |
| 34 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. ABB, L&T, Schenider, Legrand Single Pole |
| 35 | G.I. Earth pipe electrode with salt/ Charcoal: Supply and laying of earth electrode made out of ISI marked 'B' class G.I. pipe 4.5 Mtr. long 40 mm dia including accessories. GI pipe electrode shall be cut tapered at the bottom and provided with holes of 12mm dia, drilled not less than 7.5 cm from each other upto 2 Mtr. of length from bottom. The earth electode shall be laid in ground after boring as per CPWD specificationscomplete in all respect and to the entire satification of the engineer-in-charge. |
| 36 | P/F 6 SWG GI earth wire in pipe: Providing & laying earth connection from earth bottom of the electrode with 6 SWG dia G.I. wire and from top of the electrode upto pole or pedestal with proper connection with nuts and bolts in 15mm dia GI pipe from earth electrode, as required complete in all respects. The work shall be executed to the entire satisfaction of Engineer-in-Charge. Please Enable Macros to View BoQ information |