| 1 | Wiring for light point /fan point/exhaust fan point /call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit,with modular type switch,phenolic laminated sheet, suitable size M.S.box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.Group-C |
| 2 | S/F of 3 pin 5 A ceiling rose on the existing junction box/wodden block including connection etc.as required |
| 3 | S/F of PVC batten/angle holder including connection etc.as required |
| 4 | S/F Suitable size GI Box with moduler plate and cover in front on surface/recess including providing the fixing 6 pin 5/6 A modular socket outlet and 5/6 A modular switch, connection etc. as required. |
| 5 | S/F Suitable size GI Box with moduler plate and cover in front on surface/recess including providing the fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connection etc. as required. |
| 6 | S/F of suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 Amp modular socket outlet and 25 Amp modular SP MCB \\"C\\" curve including connection etc. as required. |
| 7 | S/F 16Amp 3 phase 415V Industrial Solution with Insulated Plug and Socket.Complete as per site required. |
| 8 | S/F of Computer Board 01 No 16 Amp Power Switch And Socket and 6 Amp 3 No’s Switch and Socket Complete. |
| 9 | S/F of Call bell |
| 10 | S/F of 4 way (4+12),double door Vertical type three pole and neutral,sheet steel,MCB DB,415Volt,on Surface/recess mounting including earthing etc. as required as required.(But without MCB/RCCB/Isolator) |
| 11 | S/F of 4 way (4+12),double door horizontal type three pole and neutral,sheet steel,MCB DB,415Volt,on Surface/recess mounting including earthing etc. as required as required.(But without MCB/RCCB/Isolator) |
| 12 | S/F following way,single pole and neutral,sheet steel,MCB DB,240Volt,on Surface/recess mounting including earthing etc. as required as required.(But without MCB/RCCB/Isolator) |
| 13 | 16 way, Double door |
| 14 | 12 way, Double Door |
| 15 | 8 way, Double Door |
| 16 | P/F following rating and breaking capacity and pole MCCB with thermomagnetic release etc. as required. |
| 17 | 100 ,30KA, FPMCCB |
| 18 | S/F of 32/40 amp FP MCCB (16KA) thermal magnetic release |
| 19 | S/F Following way rating, four pole,415 V, MCB etc. as required. |
| 20 | 40A (10KA) |
| 21 | 32A (10KA) |
| 22 | S/F 16-32 A rating, 240/415V, 10KA, \\"C\\" curve, TPN MCB with connection as required. |
| 23 | 40 A TP MCB |
| 24 | 16 A TP MCB |
| 25 | S/F 5 to 32 A rating, 240/415,10KA, \\"C\\" curve MCB etc. as required. |
| 26 | 32 Amp DPMCB |
| 27 | 16 Amp DPMCB |
| 28 | S/F of 5 to 32 Amp MCB |
| 29 | Wiring for circuit/submain wiring along with the following size of FRLS PVC insulated copper conducter,single core cable medimum class PVC conduit as required |
| 30 | 2 x 1.5 sqmm +1 x 1.5 sqmm earth wire |
| 31 | 2 x 2.5 sqmm +1 x 2.5 sqmm earth wire |
| 32 | 2 x 4 sqmm +1 x 4 sqmm earth wire |
| 33 | 2 x 6 sqmm +1 x 6 sqmm earth wire |
| 34 | 2 x 10 sqmm +1 x 6 sqmm earth wire |
| 35 | 4 x 10 sqmm +2 x 6 sqmm earth wire |
| 36 | 4 x 16 sqmm +2 x 6 sqmm earth wire |
| 37 | S/F single pole blanking plate in the existing MCB DB complete etc. as required |
| 38 | Earthing with G.I. earth plate 600mm x 600mm x 6mm thick including accessories and providing masonary enclosure with cover plate having locking arrangment and watering pipe of 2.7 meter long etc.with charcoal/coke and salt) as required. |
| 39 | S/L 25mm x 5mm GI Strip in 40 mm dia in G.I.pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and refilling etc. as required. complete. |
| 40 | Supply and fixing of LED Tube Light with heavy duty Metal box type Tube Light Fitting suitable for up to 1 X 22 watt LED tube light fitting on Surface 120 lm / watt with,P.F.>0.95.THD <10% at full load CRI>80,aluminium sheet thickness 0.8 mm ,3 year warrantee.complete in all respect. |
| 41 | S/F of IP 20 Front lit,Mid Power SMD type LED Light ,recess/surface mounting round 10 watt to 15 watt cutt outmin 125 mm,height min 40 mm, LED Down lighter having powder coated dia cost alumminium housing etc.complet in all respect. 1200-1800 system lumens 70mm height with fully coverd diffuser type 120 Lm/W,PF>0.95 THD<10%>80CRI 80 with 3 year warrantee.. |
| 42 | S/F of LED Street having dia cast AL Body and Diffuser/Reflector with driver set Suitable for 90 Watt confirming ti IP-6600-8920 system lumens high power LED with With Lense ,pottet Driver set Face to Face protection at 440v &>300V auto cut & restart fetures 5 year Waranty. |
| 43 | Supply and fixing of IP20,Mid Power SMD type LED Light 2´x 2´ 36W to 46Watt indoor recesses mounting LED Squre fitting etc.3960-5060 system lumens with fuuly covered 110lm/watt with,P.F.>0.95.THD<10% at full load CRI>80,aluminium sheet thickness 0.8 mm, 3 year warrantee.. complete in all respect. |
| 44 | S/F of water tight oblong 10 watt LED Bulkhead diacost housing with driver set conforming to IP65 and above protection etc. 110lm/watt with,P.F.>0.95.THD<10% at full load CRI>80,aluminium sheet thickness 0.8 mm, 3 year warrantee complet in all respect. |
| 45 | S/F of LED Bulb 9 Watt Lumen 850 to 945 complet. |
| 46 | S/L of 185 Sqmm 3½ coreAlumminium Conducter PVC insulated Armoured Served Sheathed Cable Complete in all respect. |
| 47 | Supply &Laying and Fixing of one no Pvc insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size of wall surface as required |
| 48 | 50 Sqmm 3½ core |
| 49 | 10 Sqmm 4 core |
| 50 | 6 Sqmm 2 core |
| 51 | S/F of Gland and Aluminium lugs for following size |
| 52 | (a) 185 Sqmm 3½ core (57mm) |
| 53 | (b) 50 Sqmm 3½ core (57mm) |
| 54 | S/R of fire extinguisher ABC type 6.00 Kg. capacity (ISI Marked IS:15683& A.C. approved) complete with internal charge and wall bracket alongwith supply of all material and labour complete in all respect. |
| 55 | S/R of CO2 type fire extinguisher 4.5 Kg. capacity (ISI marked : 2878 & TAC approved) with intal changed and wall bracket along with supply of all material and labour for Proper complete of work. |
| 56 | S/L of Electrical Insulation Rubber sheet size 2mm x 1mtr x 2mtr complete |
| 57 | SITC of 1200mm sweep BEE 5 star ceiling fan brush less DC(BLDC)MOTOR,CLASS of insulattion B,3 nos blades,30 cm long rod 2 nos canopies,sakel kit,safety rod,copper winding,PF not less than 0.9service value(CM/M/W)Mminimum6.00,air delivery minimum 210 Cum/Min,350 RPM(tolerance as per)IS:374-2019),etc Suitable for 230 V,50Hz,single phase AC Supply,earthing complete. |
| 58 | S/F of Fresh Air fan 300mm Sweep (Metalic) etc. complete in all respect. |
| 59 | S/F of Exhaust fan Heavy duty 300mm sweep 900/1400rpm etc copmlete in all respect. |
| 60 | Supply, Installation, Testing amd Commissioning of LT Panel vermin proof floor mounting , M.S. channel base with bottom and Fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating.The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit of 50kA for panels having ACB as Incomer & 36kA for panels having MCCB Incomers. Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be completed in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering. |
| 61 | All Incomer Feeders shall be provided with Multifunction Metering along with Phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. and all Outgoing Feeders 100A & above shall be provided with 3 phase Ammeter along with phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. The Feeders above shall be provided ac accommodated all Measuring Instruments shall be Digital type & all Indicating Lights shall be LED type.Wiring shall be done from 1100V Grade PVC Insulated copper flexible wire. All ACB shall be Electrically operated Draw-out type with Microprocessor Based O/L, S/C & E/F Release of Breaking/ Withstand Capacity (ICU/ICs/Icw) 50kA or more All MCCB shall be Thermal Magneetic/Microprocessor with O/L & S/C Protection along with Required Spreaders & Extended Rotary Handle with pad Locking facility of Breaking capacity (ICU/ICS) 36kA or more All MCB shall be Thermal 10kA 'C' Curve. Cubicle type switch board shall be Cat-A and B only. |
| 62 | I/C - 250A,415V FPMCCB- 02 N0. |
| 63 | C/O - 160A,415V FPMCCB - 01 nos. |
| 64 | O/G - 100A,415V FPMCCB- 02 Nos. |
| 65 | - 40A,415V FPMCCB- 05 N0s. (01 No. Spare) |
| 66 | Dismantaling charges of old electrical wiring and equipment and shifted suitable place. |
| 67 | Add : GST @18% Please Enable Macros to View BoQ information |