| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. i). 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. i). 2 X 6 sq. mm + 1 X 6 sq. mm earth wire. |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. i. 3x1.5 sq mm. |
| 6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. i. 3x4 sq mm. |
| 7 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. i. 6x6 sq mm. |
| 8 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. i). 32 mm. |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. i. 5/6 A switch. |
| 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. i. 15/16 A switch. |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. i. 3 pin 5/6 A socket outlet. |
| 12 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. i. 6 pin 15/16 A socket outlet. |
| 13 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 14 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. i). 1 or 2 Module (75mmX75mm). |
| 15 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. i). 4 Module (125mmX75mm). |
| 16 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. i). 12 Module (200mmX150mm). |
| 17 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. i). 100 A,30KA,FPMCCB. |
| 18 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. i). 125 A,36KA,FPMCCB. |
| 19 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. i). 250 A,36KA,FPMCCB. |
| 20 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).12 way , Double door. |
| 21 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MOB DB complete with connections, testing and commissioning etc. as required. i). Single pole. |
| 22 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MOB DB complete with connections, testing and commissioning etc. as required. i). Single pole and neutral. |
| 23 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MOB DB complete with connections, testing and commissioning etc. as required. i). Triple pole and neutral. |
| 24 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. i). 63 A |
| 25 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 26 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 27 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 28 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 29 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 30 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 31 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. i). Above 35 sq. mm and upto 95 sq. mm. |
| 32 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. i). Above 95 sq. mm and upto 185 sq. mm. |
| 33 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. i). Above 35 sq. mm and upto 95 sq. mm |
| 34 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. i). Above 95 sq. mm and upto 185 sq. mm |
| 35 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. i). Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 36 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required.100 mm dia. |
| 37 | Supply, Installation, Testing and Commissioning of ceiling fan (withoutRemote) with Brush Less Direct Current (BLDC) |
| 38 | Motor, class of insulation: B, 3 nos. metal ( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. (I) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum). |
| 39 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 40 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. i). 3½ X 95 sq. mm (45mm). |
| 41 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. i). 3½ X 120 sq. mm (45mm). |
| 42 | Supplying and fixing of 36 Watt, 230 V , 2 x 2 square Led panel light fixture, aesthetically designed LED flat panel for recess mounting which provide soft light and glare free symmetrical illumination including fixing in the existing ceiling including connection testing commissioning etc as required as per direction of engg-in-charge. Model- Plano 2x2/ venus Neo of Havells make or equivalent of Philips/bajaj/CG/wipro including connection etc as required. |
| 43 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.. (ISI marked Make Havells /Polycab/ Finolex /KEI /RR Kabel) (i) 3.5 x 240 sqmm. |
| 44 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing HDPE/RCC/ HUME/ METAL pipe as required. (ISI marked Make Havells /Polycab/ Finolex /KEI /RR Kabel) (i) 3.5 x 240 sqmm. |
| 45 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing masonry open duct / along pole / loose/loop for connections etc as required. (ISI marked Make Havells /Polycab/ Finolex /CCI / /RR Kabel) (i)3.5 x240 sqmm. |
| 46 | Supplying and fixing of 6 Ways (4+18) Double Door surface/ recess mounting, vertical loadline , 415 volts, TPN vertical loadline MCB distribution board of CRAC sheet steel, dust protected, duly powder coated, Confirms to IS 8623-1 & 3, IEC 61439-1 & 3, ready to use DBs with -i. 125 Amp Insulated vertical phase bus-bars.ii. Neutral bar/s with shroud/s.iii. Earth bar/s.iv. Sticking saddles.v. Cement spill protector.vi. Color-coded interconnecting wire set.vii. Cable ties.viii. Blanking plates and circuit identification labels.But without MCB's and incomer as MCCB) as required of L&T Model No. DBVTL006DD or equivalent specification. |
| 47 | Desigining,Fabrication Supply/installation/testing and commissioning of compartmentalised type outdoor feeder piller, double door made out of 2.03 mm thick CRCA powdered coated sheet having 200 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front & back openable door, R-Y-B LED indicators and P & F of internal connection with suitable size of copper wires, following accessories & angle iron frame of size 1000 mm x 400 mm with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming & outgoing cables, cable termination, earthing, locking, interconnection etc. as required. (CPRI Approved builder). The feeder pillar should have Indicating lamp (LED type) 22.5 mm 230 volt AC Red, Yellow and blue make L&T/Havells/simens- 03 nos, CT Ratio (Amp) 100/05, accuracy class 1, burden 05 VA - make L&T/AE/Trinity -03 nos, Digital Multifunction meter (VAF + PF) make L&T Cat no. WC411011OOOO or equivalent in AE/Siemns- 01 No. .The design of the feeder pillar should get approved by Competent Technical authority before fabrication. The feeder pillar should have provision to acccomodate 250 Amp as an incomer, 125 Amp 4 Pole MCCB-3 Nos (As outgoing).The feeder pillar will be of size 750 mm (height) x 1200 mm (width) x 400 mm deep appx or as per site requirement. |
| 48 | S/I/T/C of 230V, 50 Hz, 2.0 Ton Split AC, Energy saver 5 Star rating, Eco friendly having technical specificaton:- i. Capacity - 2.0 Ton, ii. Refrigerant-R32/R410A iii. Copper condenser, iv. Inverter AC v. Cooling only.vi. Nominal Cooling Capacity (in Watt) - 6331-7736.vii. Material of Evaporator & Condenser - Copper.viii. Warranty on Air Conditioner/Machine - 1 Year.ix. Warranty on Compressor - 5 Years.with metallic mount suitable for 2 TON outdoor of AC, Wall mountable, Powder coated with fastner, 1 m (PVC Insulated sheathed cables as per IS:694),3 m Refrigerant Copper pipe set + connecting cable (Installation Kit), 3m drainage pipe, Remote, User Manual, Warranty card, making holl etc as required. Make-LLYod/ LG/ Carrier/ Voltas/ Samsung Havells/Haier/Deikin make. |
| 49 | S/I/T/C of 4 TON Floor/Tower type Inverter Air conditioner, conforming to - IS 1391)part-2), Self Clean, 3D and Long Distance Airflow, having technical specificaton:- i). Classification by function - Cooling only.ii). Cooling capacity - 12001 to 13500 watt/ 45000 Blu/hr. iii.) Refrigerant - R410A. iv). Material for evaporator and condenser - copper.v). Warranty of AC Machine - 1 Year.vi). Warranty of Compressor - 5 Years.vii). Power source - 415V/3 Phase/50 Hz.viii). Air Flow (H/M/L/Q) - 1118/1059/941/765/706 CFM.ix). BEE starrating -5 star.x). Inverter ACxi). Sound pressure level (H/M/L/Q) - 50/48/46 dBA.xii). Dimentions indoor (H/W/D) - 1800x600x350 MMxiii). Dimentions outdoor (H/W/D) - 852x1030x400 MMxiv). Compressure roataty type with metallic mount suitable for 4 TON outdoor of AC, Wall mountable, Powder coated with fastner 1 m (PVC Insulated sheathed cables as per IS:694),3 m Refrigerant Copper pipe set + connecting cable (Installation Kit), 3m drainage pipe, Remote, User Manual, Warranty card, making holl etc as required. Make-LLYod/ LG/ Carrier/ Voltas/ Samsung Havells/Haier/Deikin make. Please Enable Macros to View BoQ information |