| 1 | AUTOMATIC DETECTION AND ALARM SYSTEM |
| 2 | Panel |
| 3 | Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting not less than 250 devices and detectors per loop, with on-board LCD alphanumeric backlit display suitable for minimum 80 characters, operating at 230 V 50 Hz - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 minutes in alarm condition, The panel shall have suitable provision for network connectivity & compatible for third party integration(Open Protocol to communicate) via a MODBUS/BACNET interface etc. conforming to IS 15908:2021, IS 2189: 2008, NFPA-72, EN 54 / VdS/FM & UL 864(10th edition) with 3 years replacement warranty and inclusive of lifetime software license validity , as per specification noFF-AFAS/CP. |
| 4 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 5 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 6 | Supplying, installing, testing and commissioning of addressable fire monitor module for flow switches, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device complete as required. Module shall conforming to IS 5051 Part 2 (Sec 1 to 3) : 1982 Reed relays, EN 54/VdS / UL & FM approved with 3 years equipment replacement warranty, as per specification no FF-AFAS/MM |
| 7 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 8 | Supplying, installing, testing and commissioning of addressable firecontrol/ relay module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs etc., Module shall conforming to IS 5051 Part 2 (Sec 1 to 3) : 1982 reed relays / EN 54/VdS / UL & FM approved with 3 years equipment replacement warranty, as per specification no FFAFAS/CRM-FCM |
| 9 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 10 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 11 | Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVCinsulated wire laid in provided conduit/ trunking/ inside pole/ Bus bars or any other places. as per specification No: WG-MA/BW |
| 12 | PUBLIC ADDRESS (PA) SYSTEM |
| 13 | Supplying, installing, testing and commissioning of Supervised EN 60849 compliant rack mount Router for system expansion, connected to master controller by Cat 6+ cable by loop in loop out over 1000 m loop length with front & back mounted controls &indicators, 100V inputs from amplifiers, outputs for 6 speaker zones having capability of 700 W per zone, 50 VA consumption, 12 trigger inputs, programmable super vised EMG inputs, with controls & inputs, programmable super vised EMG inputs, with controls & indications at front & back, single or dual channel operation, 19\\" rack mounted in 2U size. |
| 14 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 15 | Supplying, installing, testing and commissioning 15W PA Column Speakers with 15W RMS power in aluminium extruded cabinet, Moulded Plastci Covers & Metal mesh grill, frequency response 150-15,000Hz, operates on 100V line with power taps of 15/10/5/2.5W in black or white color,With Mounting clamps & Necessary hardware, as per decesion by Engineer-in charge complete as per specification no. PA-CS |
| 16 | Supplying, erecting, testing & commissioning Mixer Amplifier 250W RMS Power with Built-in Digital Player, MP3 Player with USB/ SD/ MMC Card Reader, Bluetooth with remote and having min 6 Mic & 2 Aux Inputs with Box Speaker/Driver Unit selector switch. Frequency response 50-15,000Hz ±3dB. The unit shall have Preamplifier and Line Output for connecting to a Booster Amplifier and for recording the programme with Resettable circuit breaker for protection against overload and short circuit. The unit shall have speaker output range of 4Ω, 8Ω/(Low Impedence) and 70V & 100V/(High Impedence) & It caninstant transfer to DC power if AC power fails. Signal to noise ratio between 60dB to 65dB complete as per specification no. PA-MA |
| 17 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
| 18 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 19 | speaker cable Single pair, 2-core, 1.5 sqmm |
| 20 | 9U Rack |
| 21 | AUTOMATIC DETECTION AND ALARM SYSTEM |
| 22 | Panel |
| 23 | Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting not less than 250 devices and detectors per loop, with on-board LCD alphanumeric backlit display suitable for minimum 80 characters, operating at 230 V 50 Hz - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 minutes in alarm condition, The panel shall have suitable provision for network connectivity & compatible for third party integration(Open Protocol to communicate) via a MODBUS/BACNET interface etc. conforming to IS 15908:2021, IS 2189: 2008, NFPA-72, EN 54 / VdS/FM & UL 864(10th edition) with 3 years replacement warranty and inclusive of lifetime software license validity , as per specification noFF-AFAS/CP. |
| 24 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 25 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 26 | Supplying, installing, testing and commissioning of addressable fire monitor module for flow switches, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device complete as required. Module shall conforming to IS 5051 Part 2 (Sec 1 to 3) : 1982 Reed relays, EN 54/VdS / UL & FM approved with 3 years equipment replacement warranty, as per specification no FF-AFAS/MM |
| 27 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 28 | Supplying, installing, testing and commissioning of addressable firecontrol/ relay module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs etc., Module shall conforming to IS 5051 Part 2 (Sec 1 to 3) : 1982 reed relays / EN 54/VdS / UL & FM approved with 3 years equipment replacement warranty, as per specification no FFAFAS/CRM-FCM |
| 29 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 30 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 31 | Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVCinsulated wire laid in provided conduit/ trunking/ inside pole/ Bus bars or any other places. as per specification No: WG-MA/BW |
| 32 | PUBLIC ADDRESS (PA) SYSTEM |
| 33 | Supplying, installing, testing and commissioning of Supervised EN 60849 compliant rack mount Router for system expansion, connected to master controller by Cat 6+ cable by loop in loop out over 1000 m loop length with front & back mounted controls &indicators, 100V inputs from amplifiers, outputs for 6 speaker zones having capability of 700 W per zone, 50 VA consumption, 12 trigger inputs, programmable super vised EMG inputs, with controls & inputs, programmable super vised EMG inputs, with controls & indications at front & back, single or dual channel operation, 19\\" rack mounted in 2U size. |
| 34 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 35 | Supplying, installing, testing and commissioning 15W PA Column Speakers with 15W RMS power in aluminium extruded cabinet, Moulded Plastci Covers & Metal mesh grill, frequency response 150-15,000Hz, operates on 100V line with power taps of 15/10/5/2.5W in black or white color,With Mounting clamps & Necessary hardware, as per decesion by Engineer-in charge complete as per specification no. PA-CS |
| 36 | Supplying, erecting, testing & commissioning Mixer Amplifier 250W RMS Power with Built-in Digital Player, MP3 Player with USB/ SD/ MMC Card Reader, Bluetooth with remote and having min 6 Mic & 2 Aux Inputs with Box Speaker/Driver Unit selector switch. Frequency response 50-15,000Hz ±3dB. The unit shall have Preamplifier and Line Output for connecting to a Booster Amplifier and for recording the programme with Resettable circuit breaker for protection against overload and short circuit. The unit shall have speaker output range of 4Ω, 8Ω/(Low Impedence) and 70V & 100V/(High Impedence) & It caninstant transfer to DC power if AC power fails. Signal to noise ratio between 60dB to 65dB complete as per specification no. PA-MA |
| 37 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
| 38 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 39 | speaker cable Single pair, 2-core, 1.5 sqmm |
| 40 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. |
| 41 | 9U Rack Please Enable Macros to View BoQ information |