| 1 | Taking down carefully copper/ aluminum point wiring of any size and description for taking credit and making good disturbed surface of walls, floors, etc. complete all as specified and directed. |
| 2 | Material and labour for point wiring for one light point or one fan point or one bell point controlled by one switch with using 1.5 Sqmm (nominal area) stranded copper conductor, single core,FRLS PVC insulated & unsheathed cable, 1100 volts grade drawn through concealed PVC conduit and using 1.5 Sqmm (nominal area) stranded copper conductor single core conductor, FRLS PVC insulated & unsheathed cable as in earth wire connected to common earth dolly factory made GI sheet sunken box with modular cover plate complete all as specified and directed. |
| 3 | All as per Serial item No. 2 here-in-before but point wiring for 3/ 5 pin switch socket outlet combination, 5 amps on same board. |
| 4 | All as per Serial item No. 2 here-in-before but point wiring for 3/ 5 pin switch socket outlet combination, 5 amps on independent board. |
| 5 | All as per Serial item No. 2 here-in-before but point wiring for one 6 pin switch socket outlet combination, 5/15 amps (independent) with using 2.5 sq.mm (nominal area) copper PVC insulated unsheathed stranded copper conductor as continuous earth wire on independent board for one socket outlet 3 pin 15 amps |
| 6 | M&L for point wiring for one light or one fan or one bell point controlled by one switch with using 1.5 Sqmm single core FRLS PVC insulated unsheathed multi stranded copper conductor cable 1100V grade drawn through with incl PVC casing in capping /conduit (size of as required at site but not less than 20mm) with accessories like bends tees, junction boxes and terminal boxes for mounting fittings etc. fixed on recessed in wall or ceiling etc including 1.5 Sqmm single core FRLS PVC insulated but unsheathed multistrandard copper conductor cable 1100V grade as earth continuity wire connected to common earth dolly with incl PVC board size as required at site complete all as specified and directed. |
| 7 | All as per Serial item No. 6 here-in-before but point wiring for 3/ 5 pin switch socket outlet combination, 5 amps on same board. |
| 8 | All as per Serial item No. 6 here-in-before but point wiring for 3/ 5 pin switch socket outlet combination, 5 amps on independent board. |
| 9 | All as per Serial item No. 6 here-in-before but point wiring with using 2.5 sq.mm (nominal area) copper PVC insulated unsheathed stranded copper conductor incl same size continuous earth wire on independent board for one 5/6 pin switch socket outlet combination, 5 &15 amps (independent) |
| 10 | All as per Serial item No. 6 here-in-before but point wiring with using 4.0 sq.mm (nominal area) copper PVC insulated unsheathed stranded copper conductor incl same size continuous earth wire on independent board for one 5/6 pin switch socket outlet combination, 5 &15 amps (independent) |
| 11 | S & F in replacement Modular switch 1 way 10A, 1 module complete all as specified and directed. |
| 12 | S & F in replacement Modular switch 1 way 20A, 1 module complete all as specified and directed. |
| 13 | S & F in replacement Modular Socket, 10A - 3 pin, 2 module complete all as specified and directed. |
| 14 | S & F in replacement Socket 10A/20A - 2/3 pin combined, 2 module complete all as specified and directed. |
| 15 | S & F in replacement Bell Buzzer, Ding Dong AC. 230 volts complete all as specified and directed. |
| 16 | S & F in replacement bell push 230 volts, 5 Amps, single pole complete all as specified and directed. |
| 17 | S & F in replacement switch piano type 230 volts, 5 Amps, single pole complete all as specified and directed. |
| 18 | S & F in replacement switch piano type 230 volts, 15 Amps, single pole complete all as specified and directed. |
| 19 | S & F in replacement Socket out let 2 in 1, 3 pin, 5 Amps flush type 230 volts complete all as specified and directed. |
| 20 | S & F in replacement Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type complete all as specified and directed. |
| 21 | S & F in replacement switch Socket out let combination 2 in 1, 3 pin, 5 Amps flush type 230 volts complete all as specified and directed. |
| 22 | S & F in replacement switch Socket out let combination 2 in 1, 6/5 pin, 5 &15 Amps flush type 230 volts complete all as specified and directed. |
| 23 | S & F in replacement ceiling rose surface bakelite, three terminals complete all as specified and directed. |
| 24 | S & F in replacement angle type Lamp holder, PVC/Polycarbonate with back plate complete all as specified & directed. |
| 25 | S & F in replacement switch socket outlet combination, three pin, 6 amps, flush type, 230 volts AC with PVC encloser box complete all as specified and directed. |
| 26 | S & F in replacement switch socket outlet combination, multipurpose, 5/6 pin, 6 & 16 amps controlled by one switch, flush type, 230 volts AC with PVC encloser box complete all as specified and directed.Note for Item No 1 to 25: Unwanted delay in attending/ rectification of day to day complaint if noticed the recovery shall be made Rs 500/- per day from contractor bill till complete the job. |
| 27 | M & L for in replacement of sub main wiring using two single core FRLS PVC insulated, unsheathed stranded copper conductor cable of size 4 Sq.mm of 1100 Volts voltage rating drawn through and including PVC casing caping of size not less than 25mm with standard accessories, along-with one run of FRLS PVC (green colour) insulated, unsheathed, stranded copper conductor of size 4.0 Sq.mm as earth continuity conductor complete all as specified and directed.Note : Two run of single core FRLS PVC cable with one run of earth conductor and conduit shall be measured as one unit. |
| 28 | All as per Serial item No. 27 here-in-before but sub main wiring with using two single core 6.0 sqmm FRLS PVC insulated stranded copper conductor cable |
| 29 | Supply & Fixing in replacement industrial type sheet metal enclosures with a two pin and earth plug and socket, 250 volts with including 20 Amp SP MCB complete all as specified and directed. |
| 30 | S & F for PVC insulated aluminium stranded conductor of size 10.0 sq.mm twin core flat or circular cable 1100 volt grade, heavy duty cable , served with inner sheathed cable complete all as specified and directed. |
| 31 | S & F for PVC insulated aluminium stranded conductor of size 4.0 sq.mm twin core flat or circular cable 1100 volt grade, heavy duty cable , served with inner sheathed cable complete all as specified and directed. |
| 32 | Supply, fixing, connecting and testing sheet metal enclosures double door type for using MCBs suitable for single pole and neutral, 16 way with having copper bus bars suitable for 200 amps rating including taking down old unserviceable one complete all as specified & as directed |
| 33 | All as per item No 32 above but 12 way |
| 34 | All as per item No 32 above but 8 way |
| 35 | All as per item No 32 above but 4 way |
| 36 | Supply, fixing, connecting and testing sheet metal enclosures double door type for using MCBs suitable for single pole and neutral, 4 way TPN with having copper bus bars suitable for 200 amps rating including taking down old unserviceable one complete all as specified & as directed |
| 37 | S & F for MCCB 4 Pole, 415 V, fixed type, 100 Amps with breaking capacity 16 KA with including IP 65 sheet metal encloser complete all as specified and directed. |
| 38 | S & F in replacement MCB Triple pole & neutral (TPN), 32 to 63 Amps, 240 volts, 10KA, ‘C’ series, with proper size lugs and connections complete all as specified & as directed |
| 39 | S & F in replacement MCB Triple pole (TP), 25 to 63 Amps, 240 volts, 10KA, ‘C’ series, with proper size lugs and connections complete all as specified & as directed |
| 40 | S & F in replacement MCB single pole & neutral (SP&N), 16 to 32 Amps, 240 volts, 10KA, ‘C’ series, with proper size lugs and connections complete all as specified & as directed |
| 41 | S & F in replacement MCB single pole (SP) 6 to 32 Amps, 240 volts, 10KA, ‘B’ series, with proper size lugs and connections complete all as specified & as directed |
| 42 | S & F in replacement LED light fitting mirror type with high out put diffuser 2 feet, 10/12 watt 220 V AC Self Ballasted LED Batten. Extruded Thermoplastic body with PC Diffuser in square shape, CRI >80, Beam Angle 120° including connecting up with twin core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 43 | S & F in replacement round or Square shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 44 | S & F in replacement LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 45 | S & F in replacement LED light fitting 1x9W/1X10W bulkhead luminaires including LED light holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 46 | S & F in replacement for outdoor type IP66, Energy saving LED street light fitting 30 Watt 230 V AC with PDC Aluminium body & Secondary optical lens for superior light distribution. Efficacy >110 Lm/W. with high pressure die cast aluminum hosing and heat resistant LED street light fitting with driver, complete all as specified and directed. |
| 47 | S & F in replacement Surface and wall mounted high efficacy 1x20 watt LED LED lighting fixture with extruded polycarbonate, environmental friendly, complete with all accessories internally pre wired and including connection up with twin core flexible copper conductior cable complete all as specified and directed. |
| 48 | S & F in replacement 10 Watt LED focussed light adjustable with continuous track rail ,wiring to individual light position suitable for roof ceiling including connecting up with suitable size three core flexible copper conductor cable complete all as specified and directed. |
| 49 | S & F in replacement LED 10 watt inverter polycarbonate channel batten , Lithium Ion battery with charging time 8hours-10 hours and back up time upto 4 hours suitable for 180 volt to 250 AC volt, complete all as specified and directed |
| 50 | S & F in replacement LED 20 watt inverter polycarbonate channel batten , Lithium Ion battery with charging time 8hours-10 hours and back up time upto 4 hours suitable for 180 volt to 250 AC volt, complete all as specified and directed. |
| 51 | S & F in replacement for Decorative, wall mounting, brushed nickel finish fixture with dual Opal Glass diffuser suitable for LED lamp B22 Base complete all as specified and directed. |
| 52 | S&F in replacement intrigal decorative LED bollard with opal acrylic 10 watt LED 3000K with IP 65 protection as per existing sample complete all as specified and directed |
| 53 | S& F in replacement decorative 50 watt, , 240 volt, 50 HZ coloured flood light , suitable for focasing of tree / buildings of capacity complete all as specified and directed |
| 54 | S& F in replacement spike light LED 10 watt, , 240 volt, 50 HZ , suitable for focasing of tree / buildings of capacity complete all as specified and directed |
| 55 | S& F in replacement Post top lanterned 20 watt suitable for 180 volt to 280 volt complete all as specified and directed |
| 56 | S&F in replacement (Saffron-White-Green) tricolour LED rope light , water proof, with adaptor ,18 meter length suitable for 180 volt to 280 volt complete all as specified and directed |
| 57 | Supply & Fixing in repair 20 watt LED Square Batten-Tiranga colour of saffron, white and Green complete all as specified and directed |
| 58 | S & F in replacement LED 9 watt inverter bulb B22 CDL efficacy 100 Lm/W suitable for 180 volt to 280 volt, complete all as specified and directed |
| 59 | Supply & fixing in replacement LED bulb retrofit type15 watt, efficacy 100 Lm/W suitable for 180 volt to 280 volt complete all as specified and directed. |
| 60 | Supply & fixing in replacement LED bulb retrofit type 0.5 watt, Red/ Green colour suitable for 180 volt to 280 volt complete all as specified and directed. |
| 61 | Supply & fixing in replacement of Decorative post top lantern doom made up of high grade unbreakable polycarbonate material suitable for retrofit LED lamp B22 base as per existing sample complete all as specified and directed. |
| 62 | S & F in replacement of multi stranded copper conductor cable of size 0.5 sq.mm, 2 core including taking down of existing unserviceable one complete all as specified and directed. |
| 63 | S & F in replacement of multi stranded copper conductor cable of size 1.0 sq.mm, 3 core including taking down of existing unserviceable one complete all as specified and directed. |
| 64 | S & F in replacement of multi stranded copper conductor cable of size 2.5 sq.mm, 3 core including taking down of existing unserviceable one complete all as specified and directed. |
| 65 | S & F in replacement of for Rigid non-metallic PVC conduit/ PVC casing caping inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed. |
| 66 | S & F light fitting 1x30 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed. |
| 67 | M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe orfixed to poles or any other indicated situation for loop earthing etc. asrequired 4.0 mm dia galvanised iron or steel wire complete all as specified and directed. |
| 68 | All as per Serial item No. 67 here-in-before but using 32 x 6mm GI strip |
| 69 | All as per Serial item No. 67 here-in-before but using 20x3mm copper strip |
| 70 | All as per Serial item No. 67 here-in-before but using 25 x 3mm aluminium strip |
| 71 | S & F in replacement of GI pipe 40 mm dia light grade for earth strip protection all as specified and directed. |
| 72 | S & F in replacement of GI pipe 15 mm dia light grade for earth strip protection complete all as specified and directed. |
| 73 | Supply & fix single pointed air termination Aluminium rod, 12 mm dia, 300 mm long complete all as specified and directed. |
| 74 | M & L for replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed. |
| 75 | M & L for maintenance free GI earthing Electrode 2 mtr length shall be based on ready capsule type, Pipe-in-Cage technology concept in which, One Galvanized hollow pipe (Electrode) 50 mm dia filled with a specially developed earth enhancement material (EEM) made up of Conductive Cement, Graphite carbon powder, Sodium montmorillonite/ Sodium Bentonite Powder, Hydrous aluminum silicate etc. to reduce earth resistivity, 50kg Chemical , GI earthing Electrode buried directly in ground vertically to a depth not less than 2.0 meter below normal ground level and connected by means of galvanized bolts, nuts and washers with including necessary earth work and PVC moulded earth pit with cover and dismantling/taking out of old unserviceable earthing of any position complete all as specified and directed |
| 76 | All as per Serial item No. 75 here-in-before but copper earthing Electrode |
| 77 | M & L for colour coding of earthing pit cover with the following colour Red for Chemical earthing and yellow for conventional earth pit complete all as specified and directed. |
| 78 | M&L for recharging of chemical earth pit by using liquid chemical earthing solution (not less than 10 Kg) and mixing with water and filling into the chemical earth pit to achieve result earth value less than 1 Ohm, complete all as specified and directed. |
| 79 | M&L for recharging of conventional earth pit by using salt (not less than 20 Kg) and mixing with water and filling into the earth pit to achieve result earth value less than 5 Ohm, complete all as specified and directed. |
| 80 | S & F Pre- cast RCC earth pit with cover incl watering funel and wire mesh as per sample and including dismantling/taking out of old unserviceable of any position complete all as specified and directed. |
| 81 | M & L for rewinding of 300/450mm sweep Exhaust fan motor with appropriate size super enameled copper wire including insulating material such as illuminous paper, letherized paper, cotton tape, glass sleeving, insulating varnish, etc. connecting to electric source and testing on full load to the entire satisfaction of Engineer-in-Charge |
| 82 | All as per Serial item No. 81 here-in-before but for wall fan motor of 400mm sweep any type. |
| 83 | S& F in replacement of Ball bearing suitable size to the existing Exaust fan, wall fan of any type complete all as specified and directed. |
| 84 | S& F in replacement Exaust fan capacitor 3.25/ 4.0 MFD capacity complete all as specified and directed. |
| 85 | S & F in replacement wall/exhaust fan blade any sweep as per existing sample complete all as specified and directed. |
| 86 | Supply & fixing in replacement thermostat for water heater (Geyser) 25/50 Ltrs capacity as per sample complete all as specified and directed. |
| 87 | Supply & fixing in replacement heating element for water heater (Geyser) 25/50 Ltrs capacity as per sample complete all as specified and directed. |
| 88 | M& L for Painting of old ceiling fans/Exhaust fan of any size complete, in situ with synthetic enamel paint by praying including filling cavities with filler, one coat after cleaning all dust etc. writing the fan numbers/MES numbers etc with black paints complete all as specified and as directed |
| 89 | S& F in replacement PVC body 200/250 mm sweep exhaust fan 230 volt complete all as specified and directed |
| 90 | S& F in replacement steel body 300 mm sweep exhaust fan , heavy duty 230 volt complete all as specified and directed |
| 91 | S& F in replacement steel body 450 mm sweep exhaust fan , heavy duty 230 volt complete all as specified and directed |
| 92 | S & F in replacement geysers PVC pipe connection hot/ cold type, 15mm bore 600mm long having brass nuts and washers on both ends complete all as directed |
| 93 | Supply, laying and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminium conductor, 1100 Volts grade, of size 10 Sqmm 2 Core complete all as specified and as directed. |
| 94 | All description as per Serial item No. 93 here-in-before but cable of size 10 Sqmm 4 Core |
| 95 | All description as per Serial item No. 93 here-in-before but cable of size 16 Sqmm 4 Core |
| 96 | Excavation in hard/ dense soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable complete all as specified and directed. |
| 97 | Returning filling using excavated soil including spreading leveling, watering and well ramming in layers n exc 25 cms complete all as specified and directed. |
| 98 | Removal of surplus excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point complete all as specified and directed. |
| 99 | Supply and laying 50 mm outer dia HDPE pipe (DWC) Double wall corrugated outer surface and smooth inner wall, ISI marked and as per IS : 16205 (part-24) or latest IS 14930 (part-II), 450N compressive strength with snap fit coupler with rubber ring for underground electrical cable protection conduits Orange colour complete all as specified and directed. |
| 100 | Supply and installed factory made, cubicle compartmentalised outdoor type LT Panel feeer pillar box, front and rear opening with locking arrangement, dust and vermin proof, fabricated out of 3.15 mm thick CRCA sheet with canopy and base frame & mild steel angle iron stand, over all finished with epoxy powder coating, suitable for operation on 415 Volts, 50 Hz, AC supply, including earthing stud, feeder labeling, danger plates etc. and feeder pillar box grouting in suitable size PCC foundation, and connection the existing LT UG cable or new LT UG cable with new cable lugs, gland complete all as specified and directed by EIC including taking out old LT panel. The new LT panel comprising of the following switchgear & controls Incoming(a) Bus bar chamber having Main aluminium Bus bar for 3 phase and neutral not less than 200 A Capacity.(b) MCCB 4 pole, 415V with thermal magnetic release adjustable setting of Capacity 100 Amps with ruputring capacity 25 kA 01 No (c ) LED dispay 3 line Multimeter class 0.5 with suitable size CT ratio(d) LED RYB Phase indicater - 01 SetOut going (a) MCB SPN, 32 Amps - 05 Nos |
| 101 | S& F in replacement 500 ltr capacity humam water heating system made of 304 grade stainless steel boiler tank incl water funnel, exhaust air Vent Pipe, drain valve, stands for hamam, burner, diesel/kerosene tank 10 ltr with fuel pipe connecting to burner, Air blower motor 230 V , boiler Inner sheet made of 10 SWG 304 grade stainless steel sheet and outer sheet shall be made of 16 SWG . Glass wool insulatiuon of 25mm thickness to be provided between outer and inner sheet. 100mm dia MS pipes is to be be fitted in centre , One input water pipe , One over flow pipe, two output hot water connections with bib taps to be provided. External steel surface are to be painted with two coats of synthetic enamel paint over a coat of red oxide ccomplete all as specified and directed. |
| 102 | All description as per Serial item No. 101 here-in-before but 1000 ltr capacity humam water heating system |
| 103 | S& F in replacement 230 volt blower motor with empeller for humam water heating system complete all as specified and directed. |
| 104 | Supply only Self adhesive PVC electrical insulation tape 6 meter length complete all as specified and directed. |
| 105 | S & F in replacement RCCB double pole 40 Amps , 100 mA, 240 volts complete all as specified and directed. |
| 106 | Deduct Schedule of Credit of as listed in Schedule 'A' Part-II. Contract Sum shall be arrived after deducting the credit amount.Note :- Tenderers will not quote against this item Please Enable Macros to View BoQ information |