| 1 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 2 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 3 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 4 | Surface Mounting (with extruded alumn. Housing ) |
| 5 | Minimum lumen output 1950 lm |
| 6 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing and secondary lens on each LED/ integrated lens diffuser without cover & should be High power LED of 3 to 5 watt each . The System efficacy >=135 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 7 | LED Street Light fixture with Minimum lumen output 9450 lm |
| 8 | SITC of energy efficient /energy saving IP 20 LED direct retrofit Bulb in existing holder or fixture as required with system lumen efficacy ≥100 lm/Watt output ,pf 0.95 , CRI >70, minimum life time of minimum 25000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 9 | 9 Watt |
| 10 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size , 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 11 | Short point (up to 3 mtr.) |
| 12 | Medium point (up to 6 mtr.) |
| 13 | Long point (up to 10 mtr.) |
| 14 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 15 | On board |
| 16 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 17 | 20 mm |
| 18 | 25 mm |
| 19 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 20 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 21 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 22 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 23 | Single pole MCB (With B / C curve tripping characteristics) |
| 24 | 6 A to 32 A rating |
| 25 | Double pole MCB (With B / C curve tripping characteristics) |
| 26 | 6 A to 32 A rating |
| 27 | Four pole MCB (With B / C curve tripping characteristics) |
| 28 | 50/63 A rating |
| 29 | P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 30 | Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 31 | P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 32 | Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 33 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 34 | Providing and fixing of power plug point with non modular accessories with Galvanized box of 1.2 mm thick with earth terminal with suitable size 3.0 mm thick phenolic laminated sheet (IS : 2036 - 1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin 16 amp. socket outlet making connection , testing , etc. as required. |
| 35 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. |
| 36 | 3.0 mm thick |
| 37 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 38 | 100 mm x 50 mm |
| 39 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. |
| 40 | 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 41 | Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required. |
| 42 | 300 mm sweep Minimum air delivery 1600 Cum / hour |
| 43 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 44 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 45 | 20mm x 3mm G.I. ( Hot Dipped ) Strip Please Enable Macros to View BoQ information |