Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Building workSCHEDULE 'A' PART-ICompletion of incomplete/ balance work in Construction of block of Hospital Building (Double storey) complete all as specified and shown on drawings.(Refer Annexure-I) |
| 2 | Completion of incomplete/ balance work in Construction of block of Generator room (Single storey) 120Sqm complete all as specified and shown on drawings. (Refer Annexure-II) |
| 3 | Completion of incomplete/ balance work in Construction of block of Garrage (08 Vehs) for hospital (Single storey) complete all as specified and shown on drawings.(Refer Annexure-III) |
| 4 | Completion of incomplete/ balance work in Construction of block of single living accn for MNS officers (03 Nos) (double storey) complete all as specified and shown on drawings.(Refer Annexure-IV) |
| 5 | Completion of incomplete/ balance work in Construction of block of single living accn for Medical officers (03 Nos) (double storey) complete all as specified and shown on drawings.(Refer Annexure-V) |
| 6 | Completion of incomplete/ balance work in Construction of block of single living accn for Ors (56 Nos) (double storey) complete all as specified and shown on drawings.(Refer Annexure-VI) |
| 7 | Completion of incomplete/ balance work in Construction of block of single living acc for Civilians (24 Nos) (Single storey) complete all as specified and shown on drawings.(Refer Annexure-VII) |
| 8 | Completion of incomplete/ balance work in Construction of block of Cook house and Dining hall for 80 Nos (Ors/Civilian Staff) (Single storey) complete all as specified and shown on drawings.(Refer Annexure-VIII) |
| 9 | Completion of incomplete/ balance work in Construction of block of single living accn for Civilians (08 Person) (Single storey) complete all as specified and shown on drawings.(Refer Annexure-IX) |
| 10 | Completion of incomplete/ balance work in Construction of block for Hot Water Plant room (80 Sqm) complete all as specified and shown on drawings.(Refer Annexure-X) |
| 11 | Construction of block for Hot Water Plant room (80 Sqm) complete all as specified and shown on drawings.(Refer Annexure-XI) |
| 12 | Completion of incomplete/ balance work in Construction of fire point complete all as specified and shown on drawings. |
| 13 | Completion of incomplete/ balance work in Construction of block of storage accn (Single story) complete all as specified and shown on drawings.(Refer Annexure-XII) |
| 14 | Construction of RCC under ground sump of 30,000 litre capacity complete all as specified and shown on drawings. |
| 15 | Construction of Plant room (60 Sqm) complete all as specified and shown on drawings.(Refer Annexure-XIII) |
| 16 | Completion of incomplete/ balance work in Construction of covered garbage bin with steel gate complete all as specified and shown on drawings. |
| 17 | Construction of septic tank for 10 users (Stone masonry) including all other relevant works complete all as specified and shown on drawings. |
| 18 | Construction of septic tank for 100 users (Stone masonry) including all other relevant works complete all as specified and shown on drawings. |
| 19 | Construction of soakage well (stone construction) of size 1.8m internal dia and 3 metre deep below inlet pipe complete all as specified and shown on drawings. |
| 20 | Construction of soakage well (stone construction) of size 3.0m internal dia and 4.5 metre deep below inlet pipe complete all as specified and shown on drawings. |
| 21 | Construction of steel gate 5.5 metre wide and 3 metre high with wicket gate (0.90 M eide) and RCC pillars with granite finishes, painting etc complete all as specified and shown on drawings. |
| 22 | Note for Srl Item No.1.16 to 1.19:- Top of RCC Slab of septic tank and soakage weills shall be 1.6M below normal ground level (i.e below defrost line) and manholes of septic tanks shall be raised to 2.10M above slab. Rest of the area abvove the slab of septic tanks and soakage wells shall be filled with approved earth. |
| 23 | Internal Water Supply WORKSSCHEDULE 'A' PART-II Sch ‘A’ Part-II is prepriced by MES and pre priced rates indicated under Col 5 signifies this fact only. Bidders shall insert their rates in green field under Col 6 |
| 24 | Internal ElectrificationSCHEDULE 'A' PART-III Sec-I Sch ‘A’ Part-III Sec-I is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall inserted their rates in green field under Col 6 |
| 25 | Internal ElectrificationSCHEDULE 'A' PART-III Sec-II SCHEDULE 'A' PART-III Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 26 | Supply and fixing lamp holder, insulated body with back plate for batten fitting including CFL 15 watt, complete all as specified |
| 27 | Supply and fixing 2 pin socket outlet with 2 pin plug for telephone complete all as specified and directed |
| 28 | Supply and fixing socket outlet for telephone cable connection, complete all as specified and directed |
| 29 | Supply and fix recessed mounting luminaires for ceiling 4x 14 watt T5 indirect light all acccessories prewired and complete all as specified and directed. Make : Bajaj Cat Part No 530235BTMM414 Cat 2 or equavalent of Philips /Havells |
| 30 | Supply and fixing ultraslim recessed mounting luminaires with perforated sheet for separating lamp compartment of 3x 14 watts T5 direct light , all acccessories prewired complete all as specified and directed.Make : Crompton Greaves Cat Part No T5 CQ 11314 EB or equavalent of Philips /Havells. |
| 31 | Supply and fixing dectorative recessed mounted mirror optic for indirect light applications of 2 x 36 w light, all accessories prewired, completed all as specified and directed. Make: Crompton Greaves Cat Part No CFTT11236/ P5 or equivalent of Philips/ Havells |
| 32 | Supply and fixing recessed mounted downlighter with curved glass of 2x 26 WPL-C , all accessories prewired, complete all as specified.Make : Havells Cat Part No LHOC34226399 or equivalent of Philips /Crompton Greeves |
| 33 | Supply and fixing recessed mounted CFL luminaires with P5 paralite louvers for low glare application of 2x 26 watt CFL, all accessories prewired and complete all as specified and directed.Make : Crompton Greaves Cat Part No TLD 11218/P5 or equivalent of Philips /Havells. |
| 34 | Supply and fixing recessed mounted downlighter with curved glass of 2x 18 WPL-C , all accessories prewired, complete all as specified and directed.Make : Havells Cat Part No LHOC33218399 or equivalent of Philips /Crompton Greeves |
| 35 | Supply and fixing recessed mounted downlighter with curved glass of 2x 36 w FTL , all accessories prewired, complete all as specified and directed.Make : Havells Cat Part No LHCCN2236411 or equivalent of Philips /Crompton Greeves. |
| 36 | Supply and fixing recessed wall washer downlighter with angle adjustment arrangment of 1x 70 w MH SEQ. all accessories prewired, completed all as specified and directed .Make : Havells Cat Part No LHOM76115399 or equivalent of Philips /Bajaj Note for item No 4 to 11: The rate quoted against the items of light fitting shall incl the provn of required type and Nos of lamps for the fitting |
| 37 | Supply and fixing modular type information outlet RJ-45 CAT 6 Data socket complete with front plate and suitable size metal box on surface or in recess including connection etc complete all as specified and directed . |
| 38 | Sub main wiring with two single core PVC insulated cable 1100 volt grade with copper stranded FRLS conductor of size 6 sqmm (2 single run) with one continous FRLS copper earthing lead wire PVC insulated unsheathed cable in green colour of size 4 Sqmm and Drawn into concealed PVC conduit and connected to common earth dolly , complete and directed. |
| 39 | Sub main wiring with two single core PVC insulated cable 1100 volt grade with copper stranded FRLS conductor of size 10 sqmm with one continous FRLS copper earthing lead wire PVC insulated unsheathed cable in green colour of size 6 Sqmm and Drawn into concealed PVC conduit and connected to common earth doll, complete all as directed. (Note for item No 4.13 and 4.14:- PVC conduit and conduit accessories shall be measured and paid separetly) |
| 40 | Supply and fixing call beep system with LED indicator light alongwith wiring of suitable size copper conductor from patient bed to call beep indicator provided at nursing station.The unit should consists of 12 LED lights on the standard call beep system panel board and call bell switch for 12 Nos patients, complete all as specified and directed. |
| 41 | Supply and fixing epoxy black powder coated sheet aluminium housing with epoxy white powder coated CRCA sheet steel grey tray, clear acrylic cover,aluminium reflector and accessories complete with 'S' type CFL 2x18 watt suitable for security light purposes, as specified, including provisions of GI bracket of 40mm bore, bend to shape,medium grade pipe of 1.5m length for fixing on walls,clamps of flat iron 40x6mm and provisions of 2.5 sqmm PVC insulated, sheathed aluminium weather proof cable for making connections complete all as specified |
| 42 | Supply and fixing flame proof non integral well glass luminair, eporxy finished LM 6 aluminium alloy or cast iron housing with heat resistant and toughned glass cover,painted MS glass wire gurd and eye bolt complete all as specified and directed.Make: Bajaj CAT Part No. 022701 or equivalent of Phillips/Havells |
| 43 | Earthing complete with galvanised steel earth plate electrode 60cm x60 cmx6mm thick buried directly in ground ( earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connecting to the GI wire 4.0 mm dia by means of bolts, nuts check nuts and washer of GI and earth wire protection by provision of GI pipe light grade pipe 15 mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates wth 40 mm thick cover of RCC (1:2:4) reinforced with XPM ( weight not less than 4 Kg /Sqm ) and frame of angle iron 25x25x3 mm with 2 Nos lugs and handle made of 6mm dia MS bar made to shape, GI medium grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate ,charcoal and common salt filling, funnel, wire mesh and earth work in hard/ dense soil returning filling in and removal of surplus soil to a distance not exceeding 50 mtr, all as per electrical plate No 5 of SSR Part-I and connection to earth test point all as specified including and testing on completion. Note:- Items of Earthing including cost of 7.5 m long galvanised iron wire 4.00 mm dia and protection pipe of 15 mm bore GI light grade . Any varitation in length shall be adjusted with quoted % of Sch'A' Prt-III ( Sec-I) |
| 44 | Supply and fix, MCCB,63 Amp, 4 Pole, 25 KA complete all as specified. |
| 45 | Supply and fix RCCB,63 Amp , DP complete all as specified. |
| 46 | Supply and fix MCCB 40 Amp 4 Pole,25 KA ,complete all as specified. |
| 47 | Supply and fix ELCB,40 Amp, DP complete all as specified. |
| 48 | Supply and fix FTL fitting 1x28 watt TS surface/wall mounted with TS tube rod including MS body duly painted with synthetic white enamelled paint,prewired with all accessories, electronic ballast complete all as specified and directed. |
| 49 | All as per Item No 4.23 above, but with hanging arrangement from ceiling complete all as specified and directed. |
| 50 | Supply and fix galvanised fan hook and pressed steel fan box suitable for hanging ceiling fan of any sweep complete all as specified and directed. |
| 51 | Supply, installation, testing and commissioning of LT distribution switch board panel, factory made dust and verm in proof,indoor type mounted,fabricated out of 16 SWG mild steel sheet and angle iron of size 50x50x6mm complete with openable shutters in front and back having proper locking arrangment including busbar chamber and aluminium busbar of suitable length of size 40mmx10mm mounted on porcelain insulator to receive three phases and spray painted internally and externally with two coats of synthetic enamel paint over a cost of red oxide primer, outgoing MCCB shall be connected to bus bar with aluminium strip of suitable size including wiring to panel with suitable size PVC insulated and sheathed copper cable and with the following accessories :- (a) On line changeover switch 4 pole, 400 Amp, 415 Volt-01 No (Incoming) (b) MCCB, 4 pole, 160 Amp, 415 Volt with breaking capacity 35 KA-01 No (outgoing). (c) MCCB, 4 pole, 125 Amp, 415 Volt with breaking capacity 35 KA-03 No (outgoing). (d) Digital voltmeter with selector switch 0-500 Volts 01 No, 415 Volts, 50HZ flush mounted square pattern. (e) Digital ammeter with selector switch 0-500 Amp,flush mounted square pattern with set of three CTs of suitable rating. |
| 52 | Sub Total |
| 53 | Sewage DisposalSCHEDULE 'A' PART-IVSch ‘A’ Part-IV is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall insert their rates in green field under Col 6 |
| 54 | Area Drainage WorksSCHEDULE 'A' PART-V Sch ‘A’ Part-V is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall insert their rates in green field under Col 6 |
| 55 | Road Path and Culverts SCHEDULE 'A' PART-VI Sec-ISch ‘A’ Part-VI is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall insert their rates in green field under Col 6 |
| 56 | Road Path and Culverts SCHEDULE 'A' PART-VI Sec-II SCHEDULE 'A' PART-VI Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 57 | Supply only paving bitumen any penetration for incorporation in road work under Sch 'A' Part-VI Sec-I |
| 58 | Sub Total |
| 59 | Hot Water SupplySCHEDULE 'A' PART-VII SEC-ISCHEDULE 'A' PART-VII Sec-I) is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall insert their rates in green field under Col 6 |
| 60 | Hot Water SupplySCHEDULE 'A' PART-VII SEC-IISCHEDULE 'A' PART-VII Sec-II) is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 61 | Only fixing and installation of hot water generator suitable for out put 1,00,000 kilo calorie per hour complete with all accessories and comprising of following technical specifications :- Make :- Alfa Term Equipment, Acqua Therm, Thermax, Nestler Boiler, Heiza Boilers Pvt Ltd. (a) Water outlet temperature 60 ˚C. (b) Water pump of discharge 9000 ltrs per hrs. (c) Calorie fier working pressure 4 Kg/Hours. (d) Effeciency 93% plus or minus 2%. (e) Power supply 415 Volts 50Hz, 3 phase 4 wire completed with water storage and circulating MS tanks 3500 ltrs capacity and suitable size GI pipe and fuel supply tank 300 lts capacity with provn of pipe line network, fuel lifting pumping set including PUF insulation to tanks, pipe lines, chimney of height not less than 15M from ground level etc of suitable thickness to avoid freezing of water fuel upto - 35˚C. NOTE :- 1. Insulation and erection of tanks will be carried out all as per direction of manufacture of hot water generator on appropriate designed steel staging as per manufacture's instructions. 2. The item has been paid to previous contractor as material lying at site, presently the same is inserted in Sch of credit to be given for fixing.3.The rates to be quoted by contractor are for making the boiler fully functional & serviceable in all respect which may include replacement of unserviceable/worn-out parts, replenishment of oil, supply and fixing of any damaged or missing component/item etc. to make the boiler fully functional to the entire satisfaction of the Engr-in-Charge. |
| 62 | Supply and fix insulation tubing of size 60mm inner dia and 19mm thick insulation complete all as specified and directed. Make : Kaiflex marketed by carewell pipes, 102 Usha Kiran Building, Commercial Complex AZADPUR Delhi/Superion/Vadia Flex. |
| 63 | All as per items No 9.02 here in before, but tubing of size 48mm inner dia and 19mm thick insulation. |
| 64 | All as per items No 9.02 here in before, but tubing of size 35mm inner dia and 19mm thick insulation. |
| 65 | All as per items No 9.02 here in before, but tubing of size 28mm inner dia and 19mm thick insulation. |
| 66 | All as per items No 9.02 here in before, but tubing of size 22mm inner dia and 19mm thick insulation. |
| 67 | Earthing complete with galvanised steel earth plate electrode 600mm x600 mm thickness not less than 6 mm buried directly in ground (earh pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to and including GI earth lead using galvanised iron strip 32mm X 6mm size by means of nut & bolts, check nuts and washers of galvanised including PCC pit of 1:2:4 type B-1 cover reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle excavation and earth work in any type of soil, charcoal dust, salt, medium grade GI watering pipe of 20mm dia with funnel and wire mesh and light grade GI protection pipe of 40mm bore from top edge of earth plate upto main distrubution board complete all to as shown in electrical plate no 3 of MES Sch 2009 connected main switch board all as specified. NOTE : Items of Earthing includes cost of 7.5m long galvanised iron earth strip 32X6mm size and protection pipe of 40mm bore GI light grade. Variation in length will be measured and paid separately. |
| 68 | Supply and instalation electric water heater storage type, 230 Volt as per IS 2082 complete of capacity 25 ltrs Model Majesty IQ 25 L, code 155828 of Make : Recold or equivalent. |
| 69 | Sub Total |
| 70 | External ElectrificationSCHEDULE 'A' PART-VIII Sec-I Sch ‘A’ Part-VIII Sec-I is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall inserted their rates in green field under Col 6 |
| 71 | External ElectrificationSCHEDULE 'A' PART-VIII Sec-II SCHEDULE 'A' PART-VIII Sec-II) is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 72 | Earthing complete with galvanised steel earth plate electrode 600mm x600mm thickness not less than 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including GI earth lead using galvanised iron strip 32mm X 6mm size by means of nuts & bolts, check nuts and washers of galvanised including PCC pit of 1:2:4 type B-1 cover reinforced with XPM weight not less than 4kg/Sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal dust, salt, medium grade GI watering pipe of 20mm dia with funnel and wire mesh and light grade GI protection pipe of 40mm bore from top edge of earth plate upto main distribution board complete all to as shown in eletctrical plate No 3 of MES SSR 2009 (Part-I) connected main switch board all as specified and testing on completion.NOTE : Item of Earthing includes cost of 7.5m long galvanised iron earth strip 32x6mm size and protection pipe of 40mm bore GI light grade. Any variation in length shall be measured and paid seperaterly. |
| 73 | Earthing complete with galvanised steel earth plate electrode 600mm x600mm thickness not less than 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including galvanised earth wire of size 4mm dia by means of nuts & bolts, check nuts and washers of galvanised including PCC pit of 1:2:4 type B-1 cover reinforced with XPM weight not less than 4kg/Sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal dust, salt, medium grade GI watering pipe of 20mm dia with funnel and wire mesh and light grade GI protection pipe of 15mm bore from top edge of earth plate upto main distribution board complete all to as shown in eletctrical plate No 3 of MES SSR 2009 (Part-I) connected main switch board all as specified and testing on completion.NOTE : Item of Earthing includes cost of 7.5m long galvanised iron earth wire of size 4mm dia and protection pipe of 15mm bore GI light grade shall be measured and paid seperaterly. |
| 74 | Supply, installation, commissioning and testing LT distribution panel, outdoor cubical type, floor mounted, factory made, CPRI approved, fabricated out of 2 mm thick mild steel sheet mounted on frame of mild steel angle iron 40mm X 40 mm X 6mm, 45cms above the ground level duly supported with mild steel angel iron 50 mm X 50mm X6mm thick in PCC foundation in PCC (1:2:4), type B-I, using 20mm graded crushed stone aggregate. LT Main distribution board shall be totally enclosed weather proof and vermin proof with front and rear opening with IP-54 protection as per IS-8623 duly powder coated for 433 volts, 3 phase, 4 wire having TPN copper bus bars of 100 Amps rating duly drilled holes for connections, RYB insulated with different color code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete all as specified and directed by Engr-in charge comprissing of following :- (a) MCCB 100 Amps 4 pole, 35 KA-01 No (Incoming) (b) MCB, SPN, 32 Amps-08 Nos (for out going) (c) RYB neon indicating lamp -01 Set (d) Voltmeter digital type with inbuilt selector switch 0 to 500 volts-01 No 415 Volts, 50 Hz flush mounted square pattern. (e) Ammeter digital type with inbuilt selector switch- 60A-01 Nos, flush mounted square pattern and set of three CTs of suitable rating with all the outgoing feeders. |
| 75 | Supply, installation, commissioning and testing LT distribution panel, indoor cubical type, floor mounted, factory made, CRCA approved, fabricated out of 1.6mm thick mild steel sheet mounted on frame of mild steel angle iron 40mm X 40mm X 6mm. 45cms above the ground level duly supported with mild steel angle iron 50 mm X 50mm X6mm thick in PCC foundation in PCC (1:2:4), type B-I, using 20 mm graded crushed stone aggregate. LT Main distribution board shall be totally enclosed weather proof and vermin proof with front and rear opening with IP-43 protection as per IS-8623 duly powder coated for 433 volts, 3 phase, 4 wire having TPN copper bus bars of 200 Amps rating duly drilled holes for connections, RYB insulated with different color code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete all as specified and directed by Engr-in charge comprissing of following :-(a) On load change over switch 4 pole 400 Amps, 415 Volt-02 Nos (incoming).(b) MCCB, 3 pole, 200 Amp, 415 Volt breaking capacity 35 KA-04 Nos (Out going).(c) MCCB, 3 pole, 200 Amp, 415 Volt breaking capacity 35 KA-04 Nos .(d) Voltmeter digital type with inbuilt selector switch 0 to 500 volts-01 No 415 Volts, 50 Hz flush mounted square pattern.(e) Ammeter digital type with inbuilt selector switch 0 to 200 volts-01 flush mounted square pattern and set of three CTs of suitable rating with all the outgoing feeders.Note for Ser No Item No 11.03 & 11.04 :- Unit rates quoted by the contractor are inclusive of PCC foundation, excavation and necessarry form work etc. |
| 76 | Street light fitting HPSV 70 watts, single piece, cast aluminium housing (IP-65) with POT optics reflector including sodium vapour lamp 70 watts complete with all accessories such as electronics ignitor/capacitor, heavy duty ballast, cast aluminium gear control gear box, toughened heat resistant glass cover pre wired including provision of GI bracket of 40 mm bore light grade pipe made to shape of over all length of 1.5 mtr for street light fitting with two set MS clamp of size 40x6mm with nuts, bolts and washers and 4 sqmm PVC isulated and sheathed multi strand fire proof coper electric cable 1100 Volt grade for electric connection to street light fitting complete all as specified and directed by Engr-in-Charge. Make : Crompton Greaves, Cat Part No SSG21071H/WI with lamp type 70WHPSV(T) or equivalent in Bajaj or Philips. |
| 77 | Junction box of size 30cm x 25cm on the pole or wall fabricated out of MS sheet of 3mm thick on angle iron (50x50x6mm) frame complete with openable shutters in front and rear having proper locking arrangement and bolted, spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer including copper bus bar (02 Nos) of size 25X3 mm of suitable length mounted on suitable insulator including one No of MCB SPN 32 Amps complete all as specified and directed. |
| 78 | Supply, laying, jointing and testing XLPE insulated screened, PVC badded galvanised steel strip armoured electric power heavy duty electric cable with aluminum stranded conductor 1100 volts, laid in trenches/through pipe/wall/pole under road complete all as specified and directed of following sizes (a) 300 Sqmm 3.5 Core. |
| 79 | (b) 95 Sqmm 3.5 Core. |
| 80 | (c) 70 Sqmm 3.5 Core. |
| 81 | (d) 50 Sqmm 3.5 Core. |
| 82 | (e) 35 Sqmm 3.5 Core. |
| 83 | (f) 25 Sqmm 3.5 Core. |
| 84 | (g) 16 Sqmm 4 Core. |
| 85 | Sub Total |
| 86 | External Water SupplySCHEDULE 'A' PART-IX Section-ISch ‘A’ Part-IX Sec-I is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall inserted their rates in green field under Col 6 |
| 87 | External Water SupplySCHEDULE 'A' PART-IX Section-II SCHEDULE 'A' PART-IX Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 88 | Supply, install, testing and commissioning monoblock pump set suitable for operation at 440V, 50HZ, 3 phase with suitable suction and delivery, capable of delivering 6 LPS at 30 meter head of capacity not less than 5 HP. |
| 89 | Supply and fix gun metal foot valve with synthetic rubber 'O' ring screwed female and BSP tested 300 PSD, HYD of size 50mm dia. Make : Sant/Bir |
| 90 | Material and labour for Valve Pit chamber of size 900x900x1500mm (internal dimensions), stone masonry construction including all necessary excavation and eath work in any type of soil, returning, filling in, disposal of surplus spoil to a distance not exceeding 50m and depositing where directed, PCC in foundation of the mix ( 1:4:8), type D-2 (using 40mm graded crushed stone aggregate), stone masonry in cement mortar (1:4) rending, 12 mm thick in cement mortar (1:4) internally, finished even and fair and pointing flush externally as the work proceeds in the same mortar. Mild steel angle iron 50x50x6mm frame. MS sheet cover 3mm thick with handle and locking arangement, painting all the exposed MS work with two coats of synthetic enamel paint of the tint as approved by the GE over a coat of red oxide primer and painting all the MS embedded in PCC with two coats of black bituminous paint suitable for 50mm dia, complete all as specified and shown on drawing. |
| 91 | Sub Total |
| 92 | Refrigeration and AC WorksSCHEDULE 'A' PART-XSCHEDULE 'A' PART-X is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 93 | Supply and install refrigerator frost free, electric driven (single phase) 230 Volt AC, 4 Star BEE rating of capacity 265 ltrs single door in metalic colour complete with PVC stand of suitable size.Make : LG/Samsung/Godrej/Whirlpool. |
| 94 | Supply and install refrigerator frost free, electric driven (single phase) 230 Volt AC, 4 Star BEE rating of capacity 180 ltrs single door in metalic colour complete with PVC stand of suitable size.Make : LG/Samsung/Godrej/Whirlpool. |
| 95 | Supply and install deepfreezer hard top 320 ltrs capacity having single door. Make :Bluestar/Voltas/ Godrej. |
| 96 | Supply and install automatic voltage stablizer suitable for input variation between 170 to 250 volts and output stablised at 230 V, 50 Hz AC supply of capacity 1 KVA with accuracy (±) 2.5% including time delay arrangement. |
| 97 | Supply and install automatic voltage stablizer suitable for input variation between 170 to 250 volts and output stablised at 230 V, 50 Hz AC supply of capacity 3 KVA with accuracy (±) 2.5% including time delay arrangement. |
| 98 | Sub Total |
| 99 | Mechnical Laundry SCHEDULE 'A' PART-XISCHEDULE 'A' PART-XI is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 100 | Supply , installation , testing and commmissioning of Mechanical laundry of make supershine Model No SFL/35/E having loading capacity of 35 Kg (dry weight) or equivalent of thermax, stefab or V.J. engineers complete all as specified & driceted. (a) Slucing Machine electrically heated, having loading capacity of 35 kgs(b) Hydro Extractor having loading capacity of 15 Kgs with SS Basket. (c) Drying tumbler, electrically heated having loading capcaity of 30 Kgs.(d) Dry cleaning machine.(e) Flat Bed press, electrically heated having size 750x1500 mm.(f) sponged ironing table with automatic electric hand iron.(g) Drylinen trolley cage type stainless steel trolleys for storing and transporting dry linen trolley of size : Lenght 100 cm beadth 75 cm & height 85 cm -01 NO.(h) drylinen trolley cage type stainless steel trolleys for storing and transporting dry linen size of trolley : Length 150 cm Beadth 75 cm & height 85 cm -01 No.(i) Air compressor 1 HP-01 No. |
| 101 | Supply , installation ,commmissioning and testing LT distribution panel , indoor cubical type, floor mounted. factory made CPRI approved , fabricated out of 1.6 mm thick mild steel sheet mounted on frame of mild steel angle iron 40 mm x 40 mm x 6 mm , 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mmx 6 mm thick in PCC foundation in PCC in PCC (1:2:4) type B1, using 20 mm graded crushed stone aggregate .LT main distribtion board shall be totally enclosed weather proof and vermin proof with front and rear opening with IP-43 protection as per IS-8623 duly powder coated for 433volt , 3 phase , 4 wire having TPN copper bus bars of 100 Amps rating dully drilled holes for connections, RYB insulated with differnent color code and sleeved insulators complete or prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete all as specified and directed by Engr- in- charge comprissing of following:-(a) MCCB 100 Amp, 4 pole, 35 KA-01 (incoming).(b) MCB SPN 32 Amps-08 Nos (for outgoing). (c) RYB neon indicating lamp-01 set.(d) Voltmeter digital type with inbilt selector switch 0-500 V-01 Nos , 415 v , 50 Hz flush mounted square patten .(e) Ammeter digital type with inbuilt selector switch 0-60A-06 Nos. Flush mounted square patten and set of three CTs of suitable rating with all the outgoing feeders. |
| 102 | Earthing complete with galvanised steel earth plate electrode 600mmx600mm thickness not less than 6 mm buried directly in ground ( earth pit not less than 2.25 mtr deep below normal ground level ) with top edge of plate not less than 1.5 mtr below normal ground level. connected to and including Galvanised earth wire of size 4 mm dia by means of nutand bolts , check nuts and washers of galvanised including PCC pit of 1:2:4 type B-1 cover reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal dust , salt medium grade GI watering pipe of 20 mm dia with funnel and wire mesh and light grade GI protection pipe of 15 mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate No 5 of MES SSR 2009 ( Part-I) connected main switch board all as specified and testing on complete.Note:- Item of earthing including cost of 7.5 m long galvanised earth wire of size 4 mm dia and protection pipe of 15 mm bore GI light grade . Any variation in leng thshall be measured and paid separately . |
| 103 | Sub Total |
| 104 | Fire Fighting EquipmentSCHEDULE 'A' PART-XIISCHEDULE 'A' PART-XII is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 105 | Supply only fire beater with wooden handle of length 3 mtr all as specified and directed. |
| 106 | Supply only fire hook with wooden handle of length 3 mtr all as specified and directed. |
| 107 | Supply only portable fire extinguisher dry powder store pressure with ABC powder ISI marked, conforming to IS-13849-1993 .of capacity 5 Kg Make: Ceasefire, Bharti fire or equivalent |
| 108 | Supply only portable fire extinguisher dry powder store pressure with ABC powder ISI marked, conforming to IS-13849-1993of capacity 2 Kg Make: Ceasefire, Bharti fire or equivalent |
| 109 | Supply only portable fire extinguisher dry powder store pressure with ABC powder ISI marked, conforming to IS-13849-1993of capacity 1 Kg Make: Ceasefire, Bharti fire or equivalent |
| 110 | Supply only higher capacity dry powder type (gas cartridge 300 grm ) with ABC powder fire extinguisher trolley mounted of capacity 25 Kg . ISI marked IS 10658-1999. Make: Ceasefire, Bharti fire or equivalent |
| 111 | Supply only fire bucket of mild steel sheet heavy duly of capacity 10 Litres |
| 112 | Sub Total |
| 113 | Oil Fired IncineratorSCHEDULE 'A' PART-XIIISCHEDULE 'A' PART-XIII is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 114 | Supply installation , testing and commissioning of fully automatic ( with automatic waste loading arrangements through belt converyor or other methodlogy as per manufacture provision but as per CPCB norms ) oil fired incinerator having burning capacity 10 Kg/Hr of reasonably mixed boi-medical waste with primary and secondary chambers having achievable temprature of 800± 50 ̊C for chamber suitable to meet the latest central pollution control borad emmision norms of approved make comprising of the following :-(a) One mild steel rubber lined chimeny of 30 mtr from ground level having top dia 350 mm and bottom dia not less than 1000 mm with inner layer of 3 mm thick rubber lining complete with ladder , inspection platform , aviation lamp lightining arrestor and earthing . The thickness of MS sheet of cylinderical wall of top 20 mtr of chimney portion shall be 6 mm thick and bottom 10 mtr conical portion of chimney shall be 8 mm thick MS sheet . The external surface of chimeny shall be painted with 2 coat of heatresistance aluminium paint. The chimeny shall be be fixed perfectly vertical with the help of necessary base plate MS bolts over as RCC foundation . The design of RCC foundation shall be approved by GE prior to execution.(b) One fuel oil serivce tank of capacity 500 ltrs made out of mild steel plate with all necessary connection.(c) Mild steel refractory lined duct made out of 3 mm thick mild steel plate with flange , bends of suitable length to connect secondary chamber to venturi scrubber.(d) Mild steel rubber lined duct made out 3 mm thick MS sheet to interconnect droplet sepration to ID fan. (e) Emergency duct/chimney mounted on duct connecting secondary chamber and venturi scrubber to facilate cooling and dilution of hot gasses before entering into ventun scrubber.(f) Venturi scrubber of stainless steel with suitable structure.(g) Droplet seprator of mild steel internally rubber lined with necessary nozzles. |
| 115 | (h) Recirculation tank intergral with droplet separator dia in mild steel rubber lined construction.(j) Make up water tank of HDPE of approx capacity 500 ltrs mounted on roof. (k) Mild steel duct made out of 5 mm thick plate to interconnect ID fan to chimney.(l) Fuel pipe line and valve complete with flanged etc . to interconnect oil service tank to burners.(m) Monoblock type recirculation pump , electric driven of stainless stell with motor. (n) Ms water pipelinesand valves within incinerator room from makeup water tank to venturi scrubber and stainless steel pipe line from recirculation to venturi scrubber. (o) Caustic solition tank attached to droplet separtor and recirculation tank made out of MS plate 6 mm thick. (p) Combution air fan (FD fan) of centrifugal type direct driven of mild steel construction with motor . (q) Induced draft centrifugal fan belt driven of mild steel rubber lined casing and stainless steel impller.(r) Skid mounted electrical control panel vermin proof having IP 52 protection made out of 2 mm CRCA sheet and powder coated in light grey shed provided with 3 Nos of indicator controller ( one each for primary and secondary chamber and one at outlet of venturi scrubber ) 01 No temprature indicator for showing temp in venturi scrubber, 2 Nos sequence controller (one each for the burner ) 2 Nos iginition transformer (one for each burner).(s) Complete painting of the unit with two or more coat as direction of Engg- in - charge. Note :- Rate should include cost of foundation required for erection of plant and chimney as per manufacture directions and with design as a approved by GE.Make of Oil fired incenerator :- Alfa Therm , Thermax , HAAT incenerator. |
| 116 | Sub Total |
| 117 | LiftSCHEDULE 'A' PART-XIVSCHEDULE 'A' PART-XIV is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 118 | Supply , installation , testing and commmissioning of lift electrically operated microprocessor controlled complete with power driven automatic stainless steel sliding doors and stainless steel car enclosure of size 1000x2400 mm , suitable for hospital stretcher ( 15 passanger/ 1020 Kg) at a speed of 0.5 M/sec to serve upto 1st floors including automatic rescue device complete all as specified & driceted. Make : OTIS, Thyseen KMPP Kone or Bharat Bijilee. |
| 119 | Sub Total |
| 120 | MISC ITEMS SCHEDULE 'A' PART-XVSCHEDULE 'A' PART-XV is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 121 | Supply installation testing and commissioning of electric chimney with stainless steel body and designer hood suitable for operation at 220 V , 52 Hz single phase AC electric supply with air flow 1000 cum / hr model No C100037 of Gemini or equivalent of faber / Kutchina. |
| 122 | Supply install automatic hand drier suitable for operation at 230V, 50 Hz AC single phase with stainless steel body and nozzle . Make :- Euronics model No EH 065 or equivalent of orchid make. |
| 123 | Supply and install peddestal fans suitable for operation at 230 Volts AC, 50 Hz single phase 600 mm sweep, oscillating type. Make : Crompton Greaves, Usha, Bajaj and Khaitan. |
| 124 | Supply and install rechargeable emergency light with two filament tubes suitable for operation at 230 V, 50 hz single phase AC Make : Bajaj Cat Part No ELX-10 + based on GMNC Technology or equivelent of Philips |
| 125 | supply and install water purifier, with reverse osmosis system of capacity 25 ltr/ hour including 40 Ltr hyadrulic storage tank model RWT- ROS -0045 make of Renuka or equivalent of Eureka Forbes/ Kent |
| 126 | Supply and install automatic soap dispenser of capacity 1200 ml of Make Euromics model No Es 08 A or equivalent of Orchid. |
| 127 | Sub Total |
| 128 | SECURITY WALL AND FENCINGSCHEDULE 'A' PART-XVI Sch ‘A’ Part-XVI is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall inserted their rates in green field under Col 6 |
| 129 | LIGHTENING PROTECTIONSCHEDULE 'A' PART-XVII SEC-ISch ‘A’ Part-XVII Sec-I is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall inserted their rates in green field under Col 6 |
| 130 | LIGHTENING PROTECTIONSCHEDULE 'A' PART-XVII SEC-IISCHEDULE 'A' PART-XVII Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 131 | Avitation obstruction light suitable for 2x 100 w GLS lamp complete with earthing and cable. |
| 132 | Earthing complete with galvanised steel earth plate electrode 600mmx600mm thickness not less than 6 mm buried directly in ground ( earth pit not less than 2.25 mtr deep below normal ground level ) with top edge of plate not less than 1.5 mtr below normal ground level. connected to and incl using Galvanised iron strip 32 mm x 6 mm size by means of nuts and check nuts and bolts, check nuts and washers of galvanised including PCC pit excavation and earth work in any type of soil, charcoal dust , salt alternator layers medium grade GI watering pipe of 20 mm dia with funnel and wire mesh and light grade GI protection pipe of 40 mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate as per SSR 2009 ( Part-I) connected main switch board all as specified and testing on completion.Note:- Item of earthing including cost of 7.5 m long galvanised iron earth eath strip 32x 6 mm size and protection pipe of 40 mm bore GI light grade . Any variation in length shall be measured and paid separately |
| 133 | Sub Total |
| 134 | CENTRAL HEATING SYSTEMSCHEDULE 'A' PART-XVIII SEC-ISch ‘A’ Part-XVIII Sec-I is prepriced by MES and prepriced rates indicated under Col 5 signifies this fact only. Bidders shall inserted their rates in green field under Col 6 |
| 135 | CENTRAL HEATING SYSTEMSCHEDULE 'A' PART-XVIII SEC-II SCHEDULE 'A' PART-XVIII Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 136 | OIL FIRED BOILER. Only installation, Testing & commissioning of oil fire glycol based Hot Water Generator using HSD oil complete with complete with combustion chamber and equipment automatic monoblock burner assembly tubes control panel with sequence controller, photo cell for flame failure, HT transfer electrodes, blower asembly, electric panel mounting frame, pressure gauges at inlet and outlet suitable for operation of 50 Hz, 3 phase 415 Volts AC supply. Hot Water inlet temp = 65˚C & Hot water outlet temp = 75˚C.(a) Capacity : 4,00,000 K Cal/Hr at MSL |
| 137 | (b) Capacity : 2,50,000 K Cal/Hr at MSL |
| 138 | (c) Capacity : 50,000 K Cal/Hr at MSLNote for srl item no. 24.01 to 24.03.The item has been paid to previous contractor as material lying at site, presently the same is inserted in Sch of credit to be given for fixing.The rates to be quoted are for making the boiler fully functional & serviceable in all respect which may include replacement of unserviceable/worn-out parts, replenishment of oil, supply and fixing of any damaged or missing component/item etc. to make the boiler fully functional to the entire satisfaction of the Engr-in-Charge. |
| 139 | Supply, installation, testing & commissioning monoblock centrifugal pump driven by suitable capacity electric motor for ethylene glycol of following capacity complete with accessories and including cement concrete foundation.(a) 790 LPM and 25 mtr head. |
| 140 | (b) 550 LPM and 25 mtr head. |
| 141 | (c) 100 LPM and 25 mtr head. |
| 142 | GLYCOL MAKE UP CENTRIFUGAL PUMPS : Supply, installation, testing & commissioning mono block centrifugal pump WITH Bronze impeller, driven by suitable capacity electric motor for glycol fluid make up and mixing complete with accessories including cement concrete foundaton suitable for a flow rate of 5 LPM and 5 mtr head. |
| 143 | FLUE GAS CHIMNEY :-Supply and installation of MS flue gaschimney made out of 3mm thick MS sheet minimum 1.2 m above the highest point of the plant room and including connection from boiler to main chimney fabricated from 3mm MS sheet. The item shall be complete with the mounting/fixing arrangement. The generators shall be connected to a independent chimney. The portion of the chimney inside the building shall be insulated with fiber glass insulation wool of 24 kg/cum. The item shall be complete with mounting arrangement. |
| 144 | EXPANSION TANK :- Supply and installation of ovehead expansion tank of size 500 ltrs PVC tank complete covered with 13mm closed cell, electrometic insulation complete with removable lid, in/out/drain/overflow systerm mounting arrangement and complete connection. |
| 145 | EXPANSION TANK :- Supply and installation of overhead expansion tank of size 1500 ltrs PVC tank complete covered with 13mm closed cell, electrometic insulation complete with removable lid, in/out/drain/overflow system mounting arrangement and complete connection. |
| 146 | GLYCOL FLUID TANK500 Ltrs capacity HDPE Tank and complete with removable lid, in/out/drain/overflow system, mounting arrangement and complete connection. |
| 147 | GLYCOL FLUID TANK1000 Ltrs capacity HDPE Tank and complete with removable lid, in/out/drain/overflow system, mounting arrangement and complete connection. |
| 148 | BULK OIL STORAGE TANKSupply, installation, testing connecting with the system and commissioning of Horizontal Cylinderical oil storage tank made out of mild steel Design temperature 30 deg C and design pressure atmosphere static head liquid. Storage Cap (Nominal) : 10 KLGross capacity (Not Exceeding : 10.2 KL)Sheel thickness : 4 mmEnd Plate thickness : 5mmTank shall be complete with manhole, lifting lugs, earthing lugs, vent pipe dipstrick inlet out let connection. |
| 149 | DAY OUL STORAGE TANK :Supply, installation, testing and commissioning of HSD Day service Tank rectangular MS construction with capacity of 990 ltrs complete with inlet, outlet, drain. Tank will be made out of 3mm MS sheet and will be provided with supports made out of minimum 50mm NB class 'B' pipe to keep tank base at minimum (1000 mm) above finshed floor lever. |
| 150 | TRANSFER GEAR OIL PUMPS K'OIL (SELF PRIMING) :Supply, installation, testing and commissioning of Rotary gear transfer pumps for capacity of 15 LPM 10 Mtr head for HSD complete with base frame foundation bolts, coupling and coupling guard and TEFC . Flame Proof motor (1 HP), and other accessories required for commissioning. |
| 151 | HSD OIL PIPING : Supply, installation, testing and commissioning of MS pipe including bends, reduces, flanges, nut, bolts etc complete in all respects of following size :- (a) 40 mm dia pipe. |
| 152 | (b) 25 mm dia pipe. |
| 153 | (c) Ball valves of size 25mm |
| 154 | (d) Non Return valves of size 25mm |
| 155 | (e) Y-Oil Strainer 25mm |
| 156 | (f) Ball valves of size 40mm |
| 157 | HOT GLYCOL FLUID PIPING :Supplying and laying, connecting, fixing and testing of MS ERW 'C' class piping complete with fittings, duly insulated with closed cell elastomeric insulation 30 to 40 kg/m 3 density covered with shrink wrap polythene sheet for the following sizes of Hot Glycol fluid pipes ( The pipes exposed to atmosphere or burried under ground will be insulated with 18mm thick insulation and along the walls inside the building with below mention thick insulation).(a) 200mm dia pipe with 16mm thick insulation. |
| 158 | (b) 150mm dia pipe with 16mm thick insulation. |
| 159 | (c) 125mm dia pipe with 16mm thick insulation. |
| 160 | (d) 100mm dia pipe with 16mm thick insulation. |
| 161 | (e) 80mm dia pipe with 16mm thick insulation. |
| 162 | (f) 65mm dia pipe with 16mm thick insulation. |
| 163 | (g) 50mm dia pipe with 16mm thick insulation. |
| 164 | (h) 40mm dia pipe with 13mm thick insulation. |
| 165 | (j) 32mm dia pipe with 13mm thick insulation. |
| 166 | Supplying and laying, connecting, fixing and testing of 3 layer poly Propylene random copolymer pipes or composite pipes confirming to PN 16 complete with fittings, duly insulated with 13mm thick closedcell elastomeric insulation 30 to 40 kg/M 3 density for the following sizes of Hot Glycol fluid pipes (a) 40mm Dia OD pipe. |
| 167 | (b) 32mm Dia OD pipe. |
| 168 | (c) 25 mm Dia OD pipe. |
| 169 | (d) 20 mm Dia OD pipe. |
| 170 | (e) Butterfly Valves 100mm |
| 171 | (f) Dual Plate non return Valves 100mm dia |
| 172 | (g) Balancing Valves 65 mm dia |
| 173 | (h) Butter fly valves 65 mm dia |
| 174 | (j) Ball valves 25 mm dia |
| 175 | (k) Y strainer 100mm dia |
| 176 | (l) Balancing valves 100 mm Dia |
| 177 | (m) Balancing valves 80 mm Dia |
| 178 | (n) Inlet/Outlet valves of appropriate size for FCUs |
| 179 | (o) Pressure guages with cocks and syphon |
| 180 | (p) water flow switches |
| 181 | (q) Air purgers valves of appropriate size |
| 182 | (r) 12 mm OD polyurethane pipe |
| 183 | GLYCOL CHARGE : Supply and first fill for makeup requirement for the first year of operation of glycol concentrate along with the necessary additives and inhibitor in cognition and supplied in barrels. The mixture freezing temperature should be (-25C). |
| 184 | FAN COIL UNITS :Supply, installation, testing and commissioning of decorative wall mounted type fan coil un0ts complete with grills EBS casting, 3 speed motors thermostate, wall mounting brackets inlet outlet mainfold of following capacity :- (a) 3000 kca/hr. |
| 185 | (b) 4500 kca/hr. |
| 186 | (c) 6000 Kcal/hr |
| 187 | Supply,installation , commissinoing and testing LT distribution panel indoor cubical type floor mounted , factort made CRCA approved, fabricated out of 1.6 mm thick mild steel sheet mounted on frame of mild steel angle iron 40 mmx 40 mm x6 mm , 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mm x6 mm thick in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded crushed stone aggregate LT main distribution board shall be totally enclosed weather proof and vermin proof with front and rear opening with IP-43 protection as per IS-8623 duly powder coated for 433 volts , 3 Phase , 4 wire having TPN copper bus bars of 200 amps rating duty drilled holes for connections RYB insulated with different colour code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete all as specified and directed by Engr-in- Charge comprissing of following :Incomer:- MCCB 200 A , TP, 25 KA, 415 V -1 No Phase indicating light & control fuses -1 Set Digital (0-500V) range voltmeter with selector switch -1 set Digital (0-100A) range ammeter with C.T.S of 200/5 ration and selector switch Outgoing:- 63A, TPN MCB complete with automatic DOL starter with overload , Push Button with indication lights, (0-60 A range Anp meter with CT ( for glycol circulation pumps) -04 set, 0-20 A, TPN MCB complete with DOLstarter , overload , push button indication light ( For Oil Transfer pump)-02 sets ,0-2 Amps , DP MCB ( For Glycol transfer pump)-2 Nos, 32 A SPN MCB for Hot Glycol Generator -4 Nos |
| 188 | Supply,installation , commissinoing and testing LT distribution panel indoor cubical type floor mounted , factory made CRCA approved, fabricated out of 1.6 mm thick mild steel sheet mounted on frame of mild steel angle iron 40 mmx 40 mm x6 mm , 45 cms above the ground level duly supported with mild steel angle iron 50 mm x 50 mm x6 mm thick in PCC foundation in PCC (1:2:4) type B-I using 20 mm graded crushed stone aggregate LT main distribution board shall be totally enclosed weather proof and vermin proof with front and rear opening with IP-43 protection as per IS-8623 duly powder coated for 433 volts , 3 Phase , 4 wire having TPN copper bus bars of 200 amps rating duly drilled holes for connections RYB insulated with different colour code and sleeved insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete all as specified and directed by Engr-in- Charge comprissing of following :Incomer:- MCCB 200 A , TP, 25 KA, 415 V -1 No Phase indicating light & control fuses -1 Set Digital (0-500V) range voltmeter with selector switch -1 set Digital (0-100A) range ammeter with C.T.S of 200/5 ratio and selector switch & selector switch Outgoing:- 63A, TPN MCB complete with automatic DOL starter with overload , Push Button with indication lights, (0-60 A range Amp meter with CT ( for glycol circulation pumps) -04 set, 0-20 A, TPN MCB complete with DOLstarter , overload , push button indication light ( For Oil Transfer pump)-02 sets, 0-2 Amps , DP MCB ( For Glycol transfer pump)-2 Nos , 32 A SPN MCB for Hot Glycol Generator -4 Nos |
| 189 | CABLES TRAYS: Fabricating and installing following size of perforated M.S Cable trays inculding horizontal and vertical bends , reducers , tees , cross members and other accessories as requried and duly suspended from the ceilling with M.S suspenders and including painting ( For cabling work in plant room ) 150 mm width x 50 mm depth |
| 190 | CABLES : Supplying of folowing sizes of insulated PVC sheathed copper conductor armored multistranded cables of 1.1 KV grade confirming to IS-1554(a) 3x6 Sqmm |
| 191 | (b) 3x4 Sqmm |
| 192 | (c) 2x4 Sqmm |
| 193 | (d) 25 X3.50 Sqmm |
| 194 | (e) 6x1.5 Sqmm |
| 195 | ELECTRICAL ACCESSORIES:- Providing and fixing 6 SWG dia G.I wire on surface of in recess for loop earthing interconnecting main panel and other electrical equipment |
| 196 | Providing '' No Smoking'' and ''Flammable'' sign borad as per requirement of petroleum Rules and CCOE Nagpur) |
| 197 | Sub Main wiring using two single core PVC insulated cable with flame retardant FRLS copper multistarnded conductor of size 4 sqmm and including provision of one run of 2.5 sqmm stranded copper conductor as earth wire drawn into PVC conduit ( two run of cable of 4 sqmm and one run of 2.5 sqmm earth wire shall be together measured as one RM for payment purpose) |
| 198 | Earthing complete with galvanised steel earth plate electrode 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting to galvanised iron earth lead 32x6 mm of size by means of bolt nuts check nuts and washer of GI and 32x 6 mm earth lead protected by provision of GI light grade pipe 40 mm bore incl concrete pit pcc (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick cover of RCC (1:2:4) and reinforeced with XPM (wieght not less tha 4 Kg/Sqm) and frame of angle iron 25x 25x 6 mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape GI medium grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate common salt and charcoal filling , test point made out of 75x50x6 mm phosphorous bronze with fixing arrangement funnel wire mesh and eath work in hard/dense soil returning filing in and removal of surplus soil to a distance not exceeding 50 mtr all as per electrical plate as per new SSR 2009 as pecified and testing on complete.Note: Item of earthing including cost of 7.5 m long galvanised iron earth strip 32x 6 mm size and protection pipe of 40 mm bore GI tubing light grade , Variation shall be measured and paid separately. |
| 199 | AIR HANDLING UNITS :- Providing,fixing,testing and commissioning of horizontal double skin air handling unit complete with fan,fan motor drive,common, 8 row deep all finned copper tube heating/cooling coil,pre microwave,hepa filter ,canvas, connection ,3 way mixing valve with modulating motor and thermostat,isolating,balancing valve stainer fresh air damper complete with all as per specification. 3000 CFM 150mm static pressure. |
| 200 | DUCTING :- Providing ,fixing ,testing and commisioning aluminium sheet metal ducting complete with supports damper etc specfication drawing . (a) 0.63mm (20 gauge) |
| 201 | (b) 0.80mm (22 gauge) |
| 202 | INSULATION Supply,installation,testing and commisioning of 12mm thick nitirile insulation on ducts complete all as specified and shown on drawings. |
| 203 | GRILLS Providing,fixing,testing and commisionning aluminium powder coated supply and return air grills,diffuser all as specified and shown on drawings. (a) Aluminium supply air grills with damper |
| 204 | (b) Aluminium supply air grills without damper |
| 205 | FRESH AIR DAMPER Providing ,fixing,testing and commisioning of extuder aluminium fresh air damper with grills,louvers and bird screen all as specified and shown on drawings. |
| 206 | FIRE DAMPERS Providing ,fixing,testing and commisioning of damper of GI construction in supply air duct and return opening all as specified and shown on drawings. |
| 207 | HUMIDIFIER Providing ,fixing,testing and commisioning of auto miser type humidifier complete with control and humidistat |
| 208 | EXHAUST FANS Providing ,fixing,testing and commisioning of 450mm sweep 1400 RPM exhaust fan complete with dimmer. |
| 209 | Sub Total |
| 210 | EXCAVATION AND EARTH WORK FOR SCH 'A' PART-II TO PART-XVIII SITE CEARANCESCHEDULE 'A' PART XIXLump sum price worked out by the Contractor for “EXCAVATION AND EARTH WORK ” as listed in Schedule ‘A’ Part- XIX |
| 211 | DEMOLITION/DISMATLING OF BUILDINGSSCHEDULE 'A' PART XXLump sum price worked out by the Contractor for “DEMOLITION/DISMATLING OF BUILDINGS” as listed in Schedule ‘A’ Part- XX |
| 212 | DEFECTIVE WORKSSCHEDULE 'A' PART XXI SEC-ILump sum price worked out by the Contractor for “DEFECTIVE WORKS” as listed in Schedule ‘A’ Part- XXI SEC-I |
| 213 | DEFECTIVE WORKSSCHEDULE 'A' PART XXI SEC-IISCHEDULE 'A' PART-XXI Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under column-6. |
| 214 | S&F for suspended false ceiling system using chicago metalic (E Grid) exposed suspended system, grid section size 610mm x 610 mm, comprising of GI powder coated Main Runner of diamensions 39mm x 24mm x 0.8 mm thick (Thickness comprising of GI/0.4 + PPPCGS/0.3mm & weight of runner 1.35 Kg for 3600 mm length), Cross Tee of dimensions 29mm x 24mm x 0.8mm thick and wall angle 22.2mm x 22.2mm x 0.65mm thick (Thickness comprising of GI/0.4 + PPPCGS /0.3 mm & weight of Tee of 0.195 kg for 600mm length) and wall angle of diamensions 22.2mm x 22.2mm x 3050 mm x 0.65mm thick (Thickness comprissing of GI/0.35 + PPPCGS/0.3mm & weight of angle 0.70Kg for 3050mm length) with grid system duly suspended with 4mm dia GI wire hangers fixed with steel-through fasterner from purlin of the roof complete all as specified and directd |
| 215 | Sub Total |
| 216 | Schedule Of CreditSCHEDULE 'A' PART-XXII Sec-ISCHEDULE 'A' PART-XXII Sec-I Schedule of Credit (Rs 4969071.75) |
| 217 | Schedule Of CreditSCHEDULE 'A' PART-XXII Sec-IISCHEDULE 'A' PART-XXII Sec-I Schedule of Credit (Old serviceable contractors store sold for incorporating in the works (Rs 6048241.00) |
| 218 | Schedule Of CreditSCHEDULE 'A' PART-XXII Sec-IIISCHEDULE 'A' PART-XXII Sec-I Schedule of Credit (Old serviceable/unserviceable plant/equipment to be incoporated in the works and to be given as free for fixing. |
| 219 | Schedule Of CreditSCHEDULE 'A' PART-XXII Sec-IVSCHEDULE 'A' PART-XXII Sec-I Schedule of Credit (Old Contractors T&P to be sold) Please Enable Macros to View BoQ information |