| 1 | DSR Item No.1.10Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | DSR Item No.1.15Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/Recessed steel/PVC conduit including dismantling as required. |
| 4 | Group C |
| 5 | DSR Item No.1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 6 | 3 x 1.5 sq. mm |
| 7 | 3 x 2.5 sq. mm |
| 8 | 3 x 4 sq. mm. |
| 9 | DSR Item No.1.21Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 20 mm |
| 11 | 25 mm |
| 12 | DSR Item No.1.24Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 13 | 5/6 amps switch |
| 14 | 3 pin 5/6 A socket outlet |
| 15 | DSR Item No.1.25Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 16 | DSR item no. 1.26Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 17 | DSR Item No.1.27Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 18 | 1 or 2 Module (75mmX75mm) |
| 19 | 3 Module (100mmX75mm) |
| 20 | 4 Module (125mmX75mm) |
| 21 | 6 Module (200mmX75mm) |
| 22 | 8 Module (125mmX125mm) |
| 23 | 12 Module (200mmX150mm) |
| 24 | DSR Item No.1.31Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 25 | DSR Item No.1.32Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 26 | DSR item no. 1.33Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 27 | DSR item no. 1.57Supplying & fixing suitable size GI box with modularplate and cover in front on surface or in recessincluding providing and fixing 25 A modular socketoutlet and 25 A modular SP MCB, \\"C\\" curve includingconnections, painting etc. as required. |
| 28 | DSR Item no. 2.2Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 29 | 63/100 A,30KA, FP MCCB |
| 30 | 250 A,36KA, FP MCCB |
| 31 | DSR ITEM No.2.5Supplying and fixing of following ways surface/ recessmounting, vertical type, 415 V, TPN MCB distributionboard of sheet steel, dust protected, duly powderpainted, inclusive of 200 A tinned copper bus bar,common neutral link, earth bar, din bar for mountingMCBs (but without MCBs and incomer) as required.(Note: Vertical type MCB TPDB is normally usedwhere 3 phase outlets are required.) |
| 32 | 8 way (4 + 24), Double door |
| 33 | DSR Item no. 2.10Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 34 | Single pole |
| 35 | Triple pole and neutral |
| 36 | DSR item no. 5.1Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 37 | DSR item no. 5.7Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 38 | DSR item no. 8.7LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt) Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal\ surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output.LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness >0.50 mm) |
| 39 | 40 watt |
| 40 | DSR item no. 8.10LED Batten light (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of LEDsurfacemounted Batten light of following body material and constructionas per IS : 10322 with driver (Replaceable) as per therequirement with Driver efficiency >85%, Operating voltageAC 140-270 Volt, freq 50/60 hz, Operating temp range -5 degto 40 deg centigrade, internal surge protection of 2.5 KV withShort & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI >80 , Flicker free (flicker should be below 5 %), life time(LED,Driver & electrical circuitary), of minimum 50000Burning Hours with , 70% of initial Lumen maintained tilllife ends,CCT 3000°K / 4000°K / 5700°K /6500°K (As perANSI Bin), SDCM(Standard Deviation Color Matching) <3,Maximum power consumption should not more than thespecified rating and Fixture shall be of relevant BIS standardand trade mark certificate ( T.C.). Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing. OEMmust have its own in house NABL lab setup for all testingfacilities for LED fixtures. complete in all respect i/c externalconnections with 1.5 sq mm FRLS/HFFR, PVC insulatedcopper conductor single core cable and earthing etc. as requiredwith Minimum 5 year OEM warranty. System lumen efficacy≥120 <135 lm/Watt output . LM79 & LM80 Test report and alltesting required for LED fixtures as per BIS shall besubmitted. Shape size and CCT shall be as approved byEngineer-in-Charge as per requirement. (Thermalmanagement: heat sink of aluminium housing such that LEDjunction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness >0.50 mm) |
| 41 | 18- 22 watt |
| 42 | DSR item no. 8.15LED Flood Light, powder coated pressure die castaluminium (System lumen efficacy 105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of FloodLight, powder coated pressure die cast aluminium body withbuilt in or separate driver as per the requirement with Driverefficiency >85%, Input voltage: Input voltage: 140-270 VoltAC, freq 50/60 hz, Operating temp range -5 deg to 50 degcentigrade, internal surge protection of 5 KV L,N,E as perIEC61000-4-5, Driver efficiency >85%,THD < 10% as per IEC61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >70, under voltageand over voltage protection,EMI-EMC as per CISPR -15,lenses for beam angle 30 deg-120deg as per the application andthe project requirementdeg., suitable tilt able fitting, life time(LED,Driver & electrical circuitary) of minimum 50000 BurningHours with 70% of initial Lumen maintained till life ends asper LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) ,SDCM(Standard Deviation Color Matching) <5, Maximumpower consumption should not more than the specified ratingand Fixture shall be of relevant BIS standard complete in allrespect i/c external connections with 1.5 sq mmFRLS/HFFR, PVC insulated copper conductor single corecable and earthing etc. as required with Minimum 5 year OEMwarranty. System lumen efficacy 105 <120 lm/Watt output.LM79 & LM80 Test report and all testing required for LEDfixtures as per BIS shall be submitted. Shape size and CCTshall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminium housing suchthat LED junction temperature shall not rise above 90°C). |
| 43 | 100 watt |
| 44 | DSR 9.2 Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 45 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min(Minimum) |
| 46 | Supply & erection of Exhaust Fan (heavy duty motor with copper wound metallic body) following size complete with motor, metallic blades, double ball bearing with minimum power consumption, rigid frame with rubber mounting for silent operation, epoxy powder coating along with metallic louver to be installed in the existing opening including cost of making the hole in existing wall suitable size of above fan making in original shape of wall. The size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. The Exhaust fan should be Havells/Orient and Bajaj make only. |
| 47 | Size 15 inches (380mm) Sweep, 900 RPM Heavy Duty Exhaust Fan (Single Phase) with louver of Havells make (Turbo Force SP)/ Crompton make (EXHD380-6-1)/ Bajaj make (Supreme Plus)/ Orient make (Industrial Heavy Duty)/ Usha make (Turbo HDEF) make only. |
| 48 | Supply and Erection of B.L Holder (ISI marked) of make Anchor Penta/ Havells (Reo)/ Goldmedal/ Lauritz Knudsen only on the existing junction box/ wooden block including making the connection etc as required. The job includes the all labour and petty material charges required to complete the job to the entire satisfaction of E.I.C. of work. |
| 49 | Supply and fixing of G.I box of size 200 mm x 150 mm suitable for accommodate the following accessories along with Modular switch with modular plate and cover for switches in recess / surface etc as required for Computer Point with 4 Nos. 5/6 Amp. Modular type switch and 4 Nos. 3 pin 5/6 Amp. Modular type socket outlet. The job includes the cost of making interconnections with suitable copper wire, painting of box with approved paint and other petty material required to complete the job to the entire satisfaction of Engineer-in-Charge at site. |
| 50 | S/E of M.S. bracket (‘L’ shape) made from 40mmx40mmx 5mm thick angle iron to be installed on existing parapet / wall with the help of suitable size of nuts & bolts etc. for erection of metal halide flood light fitting. The job includes cost of painting of bracket with superior quality of paint and other all petty material etc. as required to complete the job. |
| 51 | Fabrication, Supplying, Installation, Testing and Commissioning of indoor type double door Electric Control Panel of cubical construction conforming to IEC 61439 (Part I & Part II), floor mounted type, fabricated out of 2 mm thick CRCA sheet, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated of approved shade, having suitable capacity TPN Aluminum bus bars, DMC/ SMC bus bar supports, base frame of MS channel 100mm x 50mm x 6mm size, having switchgears and accessories , internal wiring with 2.5 sq.mm PVC insulated single core cable, common copper earth bar of size 25 x 5 mm over the entire width of panel and 2 nos. earth studs, cable entry from the top & bottom, cable gland plates, numbering, labeling etc. complete in all respect, suitable for operation on 415 V, 3 phase, 50 Hz. AC supply with protection class IP 54 as required. The job includes the cost of MCCB, accessories, interconnection with solid connection, carriage and installation of cubical panel at site to the entire satisfaction of Engineer in charge. The outdoor type double door Electric Control Panel should have provision of following switchgear and accessories:- (Note:- (Note: All MCCBs shall be with ROM, Spreader terminals) |
| 52 | INCOMING |
| 53 | 250 Amps. 36KA, four Pole, Thermal magnetic release, MCCB (Ics = Icu at 415 V) with O/L, S/C & built-in earth fault protection :- 1 No. |
| 54 | BUS BAR |
| 55 | TPN Aluminum bus bars (having 100% Neutral) of minimum of 300 Amps. Capacity with heat shrinkable colored sleeves and i/c DMC/SMC bus bar supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec. The current density of aluminum bus shall be 1 Amp/sq. mm.- 1 Set. |
| 56 | OUTGOING |
| 57 | 63/100 Amps. 36 KA, four Pole, Thermal magnetic release, MCCB (Ics = Icu at 415 V) with O/L, S/C & built-in earth fault protection :- 6 Nos. |
| 58 | Supply and laying of PVC insulated PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid direct in pipe/ trench/ DWC/ RCC/Hume. The job include the cost of making connections with suitable size of Al. Lugs / thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer In Charge. The cable should be of Polycab / Havells / Finolex / RR Kabel/ KEI/ RPG/ Universal/ Grandlay make only. |
| 59 | Size 25 Sq.mm 3.5 Core PVC Armored Aluminum Conductor Cable Please Enable Macros to View BoQ information |