| 1 | Painting of the electric pole with 2 coats of aluminium paint over red oxide primer complete in all respect. SOR 634 |
| 2 | Supply and laying of 16 sq. mm 2 core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 3 | Supply and laying of 16 sq. mm 4 core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 4 | S/E of 25sq.mm 4core overhead line Aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade on pole with clamps. Nuts, bolts insulator etc. with supporting G.I. wire SWG complete in all respect. (with 03 years guarantee / warranty at site) |
| 5 | Supply and fixing for automatic street light cubical control Junction Box painted with anti-corrosive alkali and acid proof paint consisting of 6 Amps MCB (B - Curve) complete in all respect |
| 6 | S&F of 50 Amp. to 63 Amp. SPMCB (10KA) CAT A |
| 7 | S&F of 80 to 100 Amp 4 pole MCCB (16 KA) Thermal Magnetic release CAT A |
| 8 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 25 A SPN |
| 9 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 40 A SPN |
| 10 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 25 A TPN |
| 11 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 40 A TPN |
| 12 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge. 16 sq. mm |
| 13 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge. 25 sq. mm |
| 14 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/termination with GI thimble etc. as required. |
| 15 | Supply and burrying of 75 mm Dia 1 Mtrs. Long Electrode casted with maintenance free, conductive concrete, non corrosive mixture ( Ultra low Resistive carbon 0.001 ohm/Mtr) in the ratio of 3:1:1 (marconite : cement : water) on M.S. Rod wiih hole (16 mm diameter X3 Mtrs ) will be vertically installed for earthing with 1 Mtr G.I strip (25 mm X 2.5mm) connected with SS nut bolt. The earth electrode will be installed into the 100 mm pit up to 3000 mm depth. noraml soil will be used as backfill material. Make : As approved in U.P.P.W.D & C.P.R.I. Certified. |
| 16 | Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 17 | RCC Pole Clamp, |
| 18 | PCC Pole Clamp, 6 inch & 4 inch |
| 19 | GI Pipe for Street light fixing (Size- 1.00 mtr long & 1.25” Dia) |
| 20 | Supply and Fixing SP of Reflecting Red Colour Strip & Pole Numbering |
| 21 | Supply and installation of GI Pole Cover/Maintanace Door of Existing Pole |
| 22 | Making Connection of Each Street Light by S/L 1.5 Sqmm FRLSH Copper wire Complete as per Direction of Engineer In Charge (MR) MR Please Enable Macros to View BoQ information |