Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of modular OT Wall and corner panels with insulated prefabricated puff Panels. The OT wall shall be constructed using GI puff panels having 0.8 mm thick GI sheets on both sides. These panels should have been produced in a double band laminator, in which two continuously moving belts carrying 120 GSM galvanized steelsheets of |
| 2 | 80 mm thickness are firmly bonded together by sprayed -in insulating foam, which hardens during the process. The core consists of rigid polyurethane foam, which has been injected under high pressure, with a minimum density of 40kg/m3. The thickness of Puff shall be minimum 40 mm. The sheet panel shall be of indigenous reputed make and be provided with manufactures test certificate. The puff panel shall be fixed to the floor with bottom track of 1.5 mm thick steel U channel section having min size of 50mm X 50mm. The bottom shall be fixed in the floor of the OT with 10mm thicknessand min. 60mmlong SS fasteners which shall be fully threaded and power drilled |
| 3 | The Panels of walls and ceilingshall be tied together by suitable SS coving. The individual wall panels of wall and ceiling shall be tied together by suitable SS coving. The individual wall panels shall be welded together bySS. All joints shall be filled with metal filler and shall be sand casted on site till smooth finish is obtained. Wall & panel joints shall not be visible after the final wall coating is applied. The gap between the masonry wall surfaces and the panel of the theatre shall be sufficient for the flush mounting of equipment’s. This gap shall be provided to accommodate the equipment at alatter date and to enable services, pipes conduits etc, to be run within the gap |
| 4 | All wall-mounted equipment shall be flush mounted and sealed in operation theatre. All the sharp edges and corners shall be in radius to avoid bacterialcontamination. The wall panel design shall be such that it enables the installation and supports all equipment’s. Provision of openings required for the installations shall not affect rigidity and strength of the panel. Access boxes shall be fitted to the rear of all wall-mounted equipment to enable maintenance to be carried out from outside the operation theatre. Product should have warranty of at least 10 years. Thework should be executed asper the directions of Engineer–in-Charge. |
| 5 | Supply, installation, testing and commissioning of modular OT Wall and corner panels with insulated prefabricated puff Panels. The OT wall shall be constructed using GI puff panels having 0.8 mm thick GI sheets on both sides. These panels should have been produced in a double band laminator, in which two continuously moving belts carrying 120 GSM galvanized steelsheets of |
| 6 | The thickness of Puff shall be minimum 40 mm. The sheet panel shall be ofindigenous reputed make and be provided with manufactures test certificate. The puff panel shall be fixed to the floor with bottom track of 1.5 mm thick steel U channel section having min size of 50mm X 50mm. The bottom shall be fixed in the floor of the OT with 10mm thicknessand min. 60 mm long SS fasteners which shall be fully threaded and power drilled. The Panels of walls and ceiling shall be tied together by suitable SS coving. The individual panels of wall and ceiling shall be tied together by suitable SScoving. |
| 7 | The individual wall panels shall be welded together bySS. All joints shall be filled with metal filler and shall be sand casted on site till smooth finish is obtained. Wall & panel joints shall not be visible after the final wall coating is applied. The gap between the masonry wall surfaces and the panel of the theatre shall be sufficient for the flush mounting of equipment’s. This gap shall be provided to accommodate the equipment at a latter date and to enable services, pipes conduits etc, to be run within the gap. All wall-mounted equipment shall be flush mounted and sealed in operation theatre |
| 8 | All the sharp edges and corners shall be in radius to avoid bacterial contamination. The wall panel design shall be such that it enables the installation and supports all equipment’s. Provision of openings required for the installations shall not affect rigidity and strength of the panel. Access boxes shall be fitted to the rear of all wall mounted equipment to enable maintenance to be carried out from outside the operation theatre. Product should have warranty of at least 10 years. The work should be executed asper thedirections of Engineer–in-Charge. |
| 9 | Supply, installation, testing and commissioning of modular OT ceiling panels with insulated prefabricated puff Panels. The OT ceiling shall be constructed using GI puff panels having 0.8 mm thick GI sheets on both sides. These panels should have been produced in a double band laminator, in which two continuously moving belts carrying 120 GSM galvanized steel sheets of 0.80 mm thickness are firmly bonded together by sprayed -in insulating foam, which hardens during the process. The core consists of rigid polyurethane foam, which has been injected under high pressure, with a minimum densityof 40kg/m3. |
| 10 | The thickness of Puff shall be minimum 40 mm. The sheet panel shall be ofindigenous reputed make and be provided with manufactures test certificate. The puff panel shall be fixed to the floor with bottom track of 1.5 mm thick steel U channel section having min size of 50mm X 50mm. The bottom shall be fixed in the floor of the OT with 10mm thicknessand min. 60 mm long SS fasteners which shall be fully threaded and power drilled. The Panels of walls and ceiling shall be tied together by suitable SS coving. The individual panels of wall and ceiling shall be tied together by suitable SScoving. |
| 11 | The individual wall panels shall be welded together bySS. All joints shall be filled with metal filler and shall be sand casted on site till smooth finish is obtained. Wall & panel joints shall not be visible after the final wall coating is applied. The gap between the masonry wall surfaces and the panel of the theatre shall be sufficient for the flush mounting of equipment’s. This gap shall be provided to accommodate the equipment at a latter date and to enable services, pipes conduits etc, to be run within the gap. All wall-mounted equipment shall be flush mounted and sealed in operation theatre |
| 12 | All the sharp edges and corners shall be in radius to avoid bacterial contamination. The wall panel design shall be such that it enables the installation and supports all equipment’s. Provision of openings required for the installations shall not affect rigidity and strength of the panel. Access boxes shall be fitted to the rear of all wall mounted equipment to enable maintenance to be carried out from outside the operation theatre. Product should have warranty of at least 10 years. The work should be executed asper thedirections of Engineer–in-Charge. |
| 13 | ALUMINIUM WORK |
| 14 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners tobe paid for separately) : |
| 15 | For fixed portion |
| 16 | Powder coated aluminium (minimum thickness of powder coating 50micron) |
| 17 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittingsshall be paid for separately) |
| 18 | Powder coated aluminium (minimum thickness of powder coating 50 micron |
| 19 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost ofaluminium snap beading shall be paid in basic item): |
| 20 | With float glass panes of 4 mm thickness (weight not less than 10.00 kg/sqm) |
| 21 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screwsetc. complete as per architectural drawings and directions of engineerin-charge. |
| 22 | Pre-laminated particle board with decorative laminationon both sides |
| 23 | EPOXY WORK |
| 24 | Providing Epoxy flooring self leveling type on strong base in desired colour/design as approved by Engineer-in-Charge. Resin for epoxy is to be of floor grade type i/c appropriate hardner and filler material. with 5 yeardefect liability period |
| 25 | 3 mm thick |
| 26 | MISCELLANEOUS WORK |
| 27 | Dismantling plain cement or lime concrete work including stacking serviceable materials in countable stacks within 15M. Lead and disposal ofunserviceable materials with all leads all complete as per direction of E/I. |
| 28 | Dismantling pucca brick or lime work including stacking serviceable materials in countable stacks within 15M. Lead and disposal of unserviceablematerials with all leads all complete as per direction of E/I. |
| 29 | Taking down chaukhats in Windows including stacking serviceable materials within 15M. Lead and disposal of unserviceable materials with all leads all complete ap per direction of E/I. |
| 30 | Dismantling lime terracing upto avg. 115mm depth with chisel and hammer including stacking servieable materials in countable stacks within 15M. Lead and disposal of unserviceable materials with all leads all comlete as per direction of E/I. |
| 31 | Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - All work up to plinth level : |
| 32 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mmnominal size) |
| 33 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 gradedstone aggregate 20 mm nominal size). |
| 34 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 35 | providing Tor steel reinforcement of 8mm dia rods as per approved design and drawing exclusive carriage of M.S. bars to work site, cutting, bending and binding with annealed wire with cost of the wire, removal of rust, placing the rods in position all complete as per building specification and direction of E/I.TMT Fe 500 (only valid for SAIL & TATA STEEL) |
| 36 | Raking out joints in lime or cement mortar and preparing the surface for re-pointing or replastering, including disposal of rubbish to thedumping ground, all complete as per direction of Engineer-in-Charge. |
| 37 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar,ladder, railings, brackets, gates and similar works |
| 38 | Supporting work for load bearing structure |
| 39 | ISMC BOX 150 |
| 40 | Near hematology area (for beam frame) horizantal direction |
| 41 | Near hematology area (for column frame) vertical direction |
| 42 | Hacking of CC flooring including cleaning for surface etc. completeas per direction of the Engineer-in-Charge. |
| 43 | Dismantling tile work in floors and roofs laid in cement mortar includingstacking material within 50 metres lead. |
| 44 | BRICK WORK |
| 45 | providing designation 75 B brickwork in C M ('1 :6 ) in superstructure with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10 mm thick mortar joints, cost of screening materials, raking out joints to 15mm depth, curing. taxes and royalty all complete as per building specification and direction of E/l. |
| 46 | Providing designation 125mm thick reinforced designation 75A brick work in CM (1 : 4) in superstructure with approved quality of clean coarse sand ofF.M. 2 to 2.5 including the cost of screening, carriage of materials, scaffolding, raking out joints to 15 mm depth, curing, taxes and royalty (but excluding the cost of reinforcement ) all complete as per building specifcation and directionof E/I |
| 47 | FINISHING WORK |
| 48 | Providing 6mm thick cement plaster (1:4) in ceiling with clean coarse sand ofF.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per specification and direction of E/I. |
| 49 | EXTERNAL PLASTER |
| 50 | Providing 12mm thick cement plaster (1:6) with clean coarse sand of F.M.1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per specification and direction of E/I. |
| 51 | Dismantling old plaster and pointing in cement or lime and raking out joints to 15mm. Depth, watering and disposal of unserviceable materials with allleads all complete as per diretion of E/I. |
| 52 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 53 | Providing two coats of plastic emulsion paint of approved shade and make over old surface including washing cleaning and preparring the walls, scaffolding, washing of floor and taxes all complete as per buildingspacification and direction of E/I. |
| 54 | FLOORING WORK |
| 55 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only .Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. |
| 56 | 11.41A.2 Glazed vitrified floor tiles polished finish of size |
| 57 | Size of Tile 600 x 600 mm |
| 58 | Providing and fixing granite 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for flooring, kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at alllevels. |
| 59 | Granite of any colour and shade Area of slab over 0.50 SQM |
| 60 | Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. |
| 61 | n flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof Acid and alkaliresistant tile |
| 62 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointingthe joints with white cement and matching pigment etc., complete. |
| 63 | Providing and laying 1st quality Ceramic glazed wall tiles thickness to be specified by the manufacturer) in walls over 12mm cement mortar (1:3) and jointed with grey cement slurry flush pointed with white cement including rubbing polishing and cost of curing, taxes and royalty all complete as perbuilding specification and direction of E/I. |
| 64 | DOOR WORK |
| 65 | Hermetically Sealed Sliding Door System: Fabrication, Supply, installation, testing & commissioning of sliding type Hermetically Sealed door having high density particle board cores/ CFC free Polyurethane, high pressure laminate face on both sides, viewing window 300 x 300mm. Size: 1500 x 2100 mm (W x H) as per direction of EIC.Automatic Doors: Provided with Radar Switch - 2 Nos., Foot Switch - 2 Nos. and Photocell Sensors.Automatic Door (1500 mm x 2100 mm) Approved makes -Metaflex /REBBON / MDD Engineering/ Altos / Dormed/ Meditech |
| 66 | WATERPROOFING WORK |
| 67 | Water proofrng for Old and New Roof Slab :- Providing and laying water prooflng treatment on roof slab by applying two Component, factory a designed ready to use, acrylic modified flexible material applied with brush, roller or spray waterproofi ng coating as per manufacturer specification-With following steps :- |
| 68 | (a)surface preparation :-Provrding and cleaning of concrete surface to remove dust, oil, grease including removal of existing loose paint / coating, and cement laitance by cleaning with compressed air & water jet including all materials, labour, tools complete. Ponding test to be done after plugging all outlets and to be checked from soffit to identify seepage, leakage. On identification of seepage, cement grouting to be done with non shrink expanding admixture of Sika lndia Pvt.Ltd. |
| 69 | / MYK Schomberg / Dr Fixit/Fosroc or equrivallent. Providing and reparing of all corners and joints such as those between the parapet wall and the roof slab etc shall be chamfered with '150mm X '150 mm fillet of mortar (Cement: sand - 1:4) admixed with acrylic polymer of Sika/ Fosroc/MYK Schomberg/Dr Fixit or equivalent Before chamfering a prime coat shall be given with theslurry of acrylic polymer Repairing surface irregularities, damaged concretein base slab, dead cracks if any, with an acrylic polymer modified repair mortar including a coat of bonding agent of the same with cement slurry including all material, labour, tools complete. |
| 70 | (b)1st Coat :- Apply 1st coat of two component acrylic modified, ready to use, flexible cementitious material on surface saturated dry roof and inside wall of Parapet wall upto 600 mm by brush or roller. After 1st coat of application ,45 gsm oI Fibre glass cloth to lay when the first layer is still green. 1st coat should be applied @1.50 kg/Sqmt/coat For the purpose of measurernent tte entire treated surface will be measured.\\" |
| 71 | (c) :2nd Coat:- To apply the 2nd coat of two component acrylic modified,ready to-use, flexible cementitious material right angle to the '1st coat over the glass fibre laid surface. 2nd coat should be applied @0.7 kg/ Sqmt/coat. For the purpose of measurement the entire treated surface will be measured.\\" Alter three days of drying the 2nd coal , the rain water outles to be plugged and ponding test to be done for 48 hours to identify seepage, leakage from soffit and if found necessary rectification lo be done as persatisfation of E/c. |
| 72 | The Watqrproofing Brand:*Sika Topseal 109hi / Fosroc Brushbond RFX/ Dr Fixit Pidiffin 2Kl MYK Aqraiin TG Product Performance - Chemical Base Part A.Acrylic copol;,mer, Part 13 Specially graded cementitious powder -Density1.6 kg/l (mixed density) at +270C Tensile Strength -2 N/mm2 after 28 Days (with Fibre cloth) (According to ASTM D 2370)Pullout Bond Strenth-2 n/mm2 (concrete failure) (According to ISO. |
| 73 | 4624) Slant-Shear Bond Strength -4 N/mm2 (According to FIP 5.15)Elongation at Break -35% without Fibre Cloth and 20% wilh Fibre Cloth (According to ASTM D 2370) |
| 74 | D Protection of treated with pcc :- The treated surface shourd be covered with 25mm/50mm PCC of M-20 grade(1:1.5:3) with proper slope ( 1:120) towards the rain outlets in alternatepanels of 2 mtx2mt keeping 6 mm gap between the panel joint. integral water proofing admixture conforming to lS 2645 @ of 100 ml perbag of of cement to be addedin the screed concrete (paid separately for thts ltems |
| 75 | all corners shall be charfered with 150mm X 150 mm fillet. The rain water outlets shall be just leveled with the screed concrete to ensure smooth discharge of water - the peripheral gaps between pvc pipe outlet and concrete surface should be packed properly with rich concrete and the peripheral mouth to be sealed with moisture insensitive epoxy putty of Sika lndia Pvt.Ltd / IVIYK Schomberg / Dr FixiUFosroc .For the purpose of measurement the entire treated surface will be measured.\\" |
| 76 | (e)Groove of PCC surface should be filled with Polysulphide Sealant (Paid Separately) Brand - Sika lndia Pvt Ltd / MYK Schomberg / Dr Fixit/Fosroc |
| 77 | Covering of treated surface wrth PCC :- Providing 25 mm thick Cement Concrete M20 (1:1.5:3) raintaining slope in alternate 2 mIx 2 mt panels with aaproved quality of stone chips of 20 mm to 6 mm size graded and clcaned sand of F M 2 5 io 3 including screening,shuttering,and mixing cerite nt c0ncrete in mixer with admixture of integral water proofing and placing rn position,strikirrg cLrring,t-a]glgnd royality all complete as per buildirrg specifictionJand direction of E/l.Panels that has been left should be casteci nextday.-lhere should be 6 mm gap between Panels.Brand- Sika *Plastocrate plus,MYK proof WP10, Fosroc- Conplast X421ic , Dr Frx,t Prdiproof LWr |
| 78 | Provrding and filling of Groove between 25 mm PCC Panels with Polyshlphide Sealant (Poring Grade)as per drawings and technical specifications and dii-ection of E in Charge (with 1B% GST).Brand:-Sika- Polysulphide, Fosroc-l-hioflex 600 Dr. Fixit Pidiseal PS(42P),MYK Seal PS orEuivallent |
| 79 | DRAIN WORK |
| 80 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketedpipes.110 mm diameter |
| 81 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382,leaving 10 mm gap for thermal expansion. |
| 82 | Bend 87.5° 110 mm bend |
| 83 | Shoe (Plain) 110 mm Shoe |
| 84 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement: 4 coarse sand) and making good the wall etc. complete. |
| 85 | 110 mm |
| 86 | EQUIPMENT WORK |
| 87 | Revolving Chair With Arm Synchronic tilt mechanism (GODREJ INTERIO ACE FULL BACK CHAIR) (Product id: 5116877-95084053146) |
| 88 | OCEAN LIFE SCIENCE CORPORATION Laboratory Steel Furniture Side bench with rack and table top OCEAN LIFE SCIENCE CORPORATIONR (OLSC-IWB) |
| 89 | BETCO Laboratory Steel Furniture Island bench with table top BETCOR(BETCO-LB-202) |
| 90 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore |
| 91 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighingnot less than 106 gms. |
| 92 | Providing and fixing C.P. brass angle valve for basin mixer and geyserpoints of approved quality conforming to IS:893118.53.1 15mm nominal bore |
| 93 | Providing and fixing PTMT extension nipple for water tank pipe, fittings of approved quality and colour.15 mm nominal bore, weighing not less than32 gms |
| 94 | Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Circularshape 450 mm dia |
| 95 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level whiteP.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings andfixtures complete, including cutting and making |
| 96 | Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern,with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS :2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the wallsand floors wherever required :Single half stall urinal with 5 litre P.V.C. automaticflushing cistern |
| 97 | Providing and fixing wash basin with C.I. brackets,15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the |
| 98 | Providing and fixing PTMT grating of approved quality and colour.125 mm nominal dia with 25 mm waste hole |
| 99 | Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, collar and bush of approved quality and colour.15 mm nominal bore with 45 cmlength |
| 100 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.32 mm dia |
| 101 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clampsat 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 102 | Concealed work, including cutting chases andmaking good the walls etc. |
| 103 | 15 mm nominal dia Pipes |
| 104 | 20 mm nominal dia Pipes |
| 105 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete asper direction of Engineer in Charge. |
| 106 | 25 mm nominal dia Pipes |
| 107 | 32 mm nominal dia Pipes |
| 108 | Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1cement : 5 fine sand : 10 graded stone aggregate 40 mm nominalsize), inside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: With common burnt clay F.P.S. (non modular)bricks of class designation 7.5 |
| 109 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approvedmake conforming to IS:8931. |
| 110 | Polythene water storage tank of ISI mark (eg sintex/sinter/himgiri/gangotri ) with cover & lockingsystem |
| 111 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 112 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making goodthe walls wherever required :510x1040 mm bowl depth 178 mm |
| 113 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS: 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes.110 mm diameter |
| 114 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS: 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes.75 mm diameter |
| 115 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap forthermal expansion. |
| 116 | 75 mm Coupler |
| 117 | 110 mm Coupler |
| 118 | 75mm single pushfit coupler |
| 119 | 110mm single pushfit coupler |
| 120 | 75 mm single tee with door |
| 121 | 110mm single tee with door |
| 122 | 75 mm single tee without door |
| 123 | 110 mm single tee without door |
| 124 | 75mm bend 87.5 |
| 125 | 110mm bend 87.5 |
| 126 | 75mm shoe (plain ) |
| 127 | 110mm shoe (plain ) |
| 128 | ELECTRICAL PANEL AND ACCESSORIES |
| 129 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor control centre fabricated out of 14 gauge CRCA sheet steel. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final approved shade of powder coated paint. 2 Nos. earthling terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Panel should be complete with Isolation push button for every equipment and auto manualselection switches . Make: GWESPL/Eqv |
| 130 | Tanks |
| 131 | Supply, installation. Testing and commissioning of following Tanks InMSEP/HDPE |
| 132 | Flash Mixer |
| 133 | Flocculation tank |
| 134 | Settling Tank |
| 135 | Break Tank |
| 136 | SBR Tank |
| 137 | Intermediate Water Tank |
| 138 | TOTAL AMOUNT For Tanks (B) (In Rs.) |
| 139 | Point wiring in PVC conduit, with modular typeswitch:Wiring for light poinVfan poinUexhaust fan point/call bell point v/ith1.5sq.mm FR PVC insulated copper conductor single core in surface/recessed PVC conduit, with modular sw'itch, modular plate suitable GI box etc as required |
| 140 | Group C |
| 141 | S/F light plug point with modular type accessories :Supplying and fixing suitable GI box with modular plac and cover in front on surface of in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch. corutection, painting etc. as required (For light plugs to be used in non residential buildings) |
| 142 | S/F power plug point with modular type accessories :Supplying and fixing suitable GI box with modular plac and cover in fronton surface of in recess, including providing and fxing 6 pin 15/16 amps modular socket outlet and l5/16 amps modular switch. connection, painting etc. as required (For light plugs to be used in non residential buildings) |
| 143 | Power plug widng in PVC conduit (2 x 4 sq. nun) :-Wiriug for light/power plug with 2 x 4 sq.mm FR PVC insulated copper conductor single core cable in surface/recessed PVC conduit, along with 1 No 4 sq.nrm FR PVC insulated copper conductor single core cable for loopcarthing etc as required. |
| 144 | Power plug widng in PVC conduit (2 x 4 sq. nun) :-Wiriug for light/power plug with 2 x 4 sq.mm FR PVC insulated copper conductor single core cable in surface/recessed PVC conduit, along with 1 No 4 sq.nrm FR PVC insulated copper conductor single core cable for loopcarthing etc as required. |
| 145 | 2x1.5 sq.urm+ 1x 1.5 sq.mm earthwire |
| 146 | 2 x2.5 sq.mm + I x2.5 sq.mm earth wire |
| 147 | 2 x l0 sq.mm+ I x6 sq.mm earthwire |
| 148 | 4 x 6.0 sq.mm +2x6.0sq.mm earthwire |
| 149 | Wirilg in cxisting conduit :-supplying and drawing following sizes of FR PVC insulated copper conductor single core cable in existing surface / recessed steel / PVC conduit including dismantling as required |
| 150 | 2x4 sq mm. |
| 151 | Wiring in cxisting conduit :-supplying and drawing following sizes of FR PVC insulated copper conductor single core cable in existing surface / recessed steel / PVC conduit including dismantling as required |
| 152 | 40 amps |
| 153 | 80/100 amps |
| 154 | S/F S.P. MCB DB :-Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, compiete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) |
| 155 | 8 way, Double door |
| 156 | S/F S.P. MCB DB :-Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, compiete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 157 | 4 way (4 + 12), Dorrble door, Horizontaltype |
| 158 | 6way (4 + 18), Double door, Horizontal type |
| 159 | S/F S.P. MCB :-Supplying and fixing 6 amps to 32 amps rating, 240 volts, 10 kA, \\"C\\" curve,miniature circuit breaker suitable for.inductive load of following poles in the existing MCB DB complete with connections, esting and commissioning etc.as required. |
| 160 | 6/32 amps, Single pole |
| 161 | 40 amps, TPN |
| 162 | 2.12.6 40 amps, DP |
| 163 | 50/63 amps, DP |
| 164 | S/F ceiling rose :-supplying and fxing 2 pin 5 amp. Ceiling rose on the existing junction box/wooen block including connection etc.as required |
| 165 | ITC fluorescent fitting directly on surface :- Installation testing and commissioning of pre wired, fluorescent fitting ./ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly / wall. including connection with 1.5 aq.mm FR PVC insulated . copper conductor single core cable and earthing etc. as required. |
| 166 | ITC fluorescent fitting with down rods:- Installation testing and commissioning of pre wired, fluorescent fitting.compact fluorescent fitting of all types, complete with all accessories and tube etc. including supplyrng and fixing ball and socket arrangement 2 no.down rods of 20mm dia x 1.6 mm thick steel conduit/Gl pipe upto 30 cm length. , painting and wiring the down and connection with 1.5 sq.mm PVC insulated, copper conductor, single core cable and earthing etc. asrequired |
| 167 | ITC ceiling fan:-Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq.mm FR PVC insulated, copper conductor, single core cable etc. as required. |
| 168 | S/F Piaoo type switch/ socket :- Supplying and fxing of following piano type switch / socket on the existing switch box / coverincluding connections etc. as required. |
| 169 | 5/6 amps, one way switch |
| 170 | 3pin 5/6 amps, socket outlet |
| 171 | Electronic step fan regulator, mini |
| 172 | S/F PVC/G.I. boxes :-Supplying and fixing of following sizes of PVC/G.I box on surface/ recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. |
| 173 | 75 mm x 75mm x 50mm deep/ (4\\" x 4\\") |
| 174 | S/F PVC conduit :Supplyingand fixing of following sizes of PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 175 | S/F Batten holder :-supplying and fixing Batten / Angle holder including connection etc as required. |
| 176 | P/F G.I. lightning condutor final :-Providing and fixing of lighting conductor finial , made of 25mm dia 300mm long , G.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. base plate including holes etc. complete as required. |
| 177 | P/f G.I. lightning conductor tape in horizontalProviding and fixing G.I. tape 20mm x 3mm thick on parapet or surface of wall for lightning conductor complete as required.(for Horizontal run ). |
| 178 | P/F G.I. lightning conductor tape in vertical Providing and fxing G.I. tape 20mm x 3rrm thick on parapet or surface of wall for lightning conductor complete as required.(for Vertical run ) |
| 179 | MV cable :- supply of ISI marked aluminium cable conductor XLPE PVC insulated cable as per IS : 7098 armoured, served shealthed 1100V grade with termination and laying of cable make :- finolex, polycab, Havells universal- 50 sqmm X 3.5 Core armoured AL Cable for SEB supply |
| 180 | MV cable upto 120 sqm in ground without sand cover Laying of one number additional PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 185 sq mm but not exceeding 400 sq. mm in the existing RCC/HUME/STONEWAREA4ETALpipe as required. |
| 181 | Supply Installation, testing and commissioning of follwing size ceiling fan 3 Blades confirming to13:374,.2019 including wiring the down rods of standard length (upto 30cm) with l.Ssq.mm. FR PVC insulated, copper wire suitable for 230V 50H2, single phase supply etc. complete as required.make polar/bajaj/havells/philips. |
| 182 | 1400mm (56\\") Ceiling Fan |
| 183 | S.I.T.C of floowing rating surface mounted LED tube light fitting suitable for 230V 50H2, single phase supply etc. complete as required. |
| 184 | 20122W LED Tube light |
| 185 | LED bulb 9W/10W:- supplying and fixing of LED 9W/10W bilb and acessories asrequired make :- Bajaj/havells/ phillips. |
| 186 | S.I.T.C of floowing rating LED Flood lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in existingpole/pipe for supply voltage 1C[.Z70Y AC,50Hz. Luminarie shall beconfirm tolS:,1,0322part-5/section-5 andshall be complete with all neccssary accessories as required |
| 187 | 90/100W LED Flood light |
| 188 | CARRIAGE OF MATERIAL |
| 189 | Carriage of material |
| 190 | Brick lead 8km |
| 191 | Sand lead 12km |
| 192 | Chips lead 22km |
| 193 | Add 18 % GST (in Basic Rate must fill 12) |
| 194 | Add 1% Labour Cess (in Basic Rate must fill 1) Please Enable Macros to View BoQ information |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail