| 1 | Wiring for light/ fan/ exhaust fan/ call bell point with 2x1.5 sq. mm PVC insulated copper conductor cable (FR) in PVC conduit (medium gauge) recessed in slab/ wall complete with 6/10 amps modular type switch, cover plate, GI box including necessary connection etc. as required. |
| 2 | Providing and fixing of 3 pin 6/10 amps plug point with modular type 6/10 amps switch and socket including connection with 2 x 1.5 sq. mm PVC insulated Copper conductor cable (FR) on modular concealed switch board with cover plate earthing the 3rd pin etc. as required. |
| 3 | Providing and fixing of 3/6 pin 16/20 amps plug point with modular type 16/20 amps switch and socket including connection with 2 x 2.5 sq. mm PVC insulated Copper conductor cable (FR) on modular concealed switch board with cover plate earthing the 3rd pin etc. as required. |
| 4 | Wiring for Circuit/Sub-main with the following sizes PVC insulated Copper conductor cable (FR) in PVC conduit (medium gauge) recessed in slab/ wall etc. as required. |
| 5 | 2 X 2.5 + 1 X 1.5 sq mm |
| 6 | 2 X 4 + 1 X 1.5 sq mm |
| 7 | 2 X 10 + 1 X 4 sq mm |
| 8 | 4 X 6 + 2 X 2.5 sq mm |
| 9 | 4 X 10 + 2 X 4 sq mm |
| 10 | 4 X 16 + 2 X 6 sq mm |
| 11 | 4 X 35 + 2 X 10 sq mm |
| 12 | Wiring for Circuit/Sub-main wiring with the following sizes of PVC insulated copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required. |
| 13 | 2 X 1.5 sq mm |
| 14 | 2 X 2.5 sq mm |
| 15 | 1 X 10 sq mm |
| 16 | Providing earthing system with maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 2 nos. 25 kg bag, terminal size 32mmx 6mm including accessories with masonry enclosure of CI cover plate size 12\\"x 12\\" having locking arrangement including CC works etc as required. |
| 17 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12\\"x 12\\" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required. |
| 18 | Extra for using salt (12 kg) and charcoal (96kg) for plate earth electrode as required. |
| 19 | Proving and fixing / Drawing 4.06 mm dia (8 SWG) Copper wire on surface or in existing G.I / PVC / Polythene pipe for loop earthing as required. |
| 20 | Supplying and fixing of the following sizes PVC conduit (medium gauge) on surface with all accessories etc. as required. |
| 21 | 19/20 mm dia |
| 22 | Supply and fixing of 25mm x 3mm Copper on walls/ floor of the building for horizontal/ vertical network including necessary spacers and porcelain insulators at regular intervals. |
| 23 | Supplying, Installation of ESE Lightning Arrestor with 05.00 mtrs long GI mast with base plate 250x 250x5 mm, Bakelite Insulator, Mounting Accessories (Stay wire , Pin fasten / Ring Fastener, U clamp etc.), Lighting Counter, Test Link, 03 nos Copper Rod Earthing with 3 bags 25kg earthing compound, 50 mtr long 70 sq. mm single core flexible copper cable etc. as required:- |
| 24 | Supplying and fixing of the following sizes GI (in recess) and plastic (on surface) modular switch boards etc. as required. |
| 25 | 1-2 module GI switch board |
| 26 | Supplying and fixing of the following sizes modular type cover plates for GI/plastic modular switch boards etc. as required. |
| 27 | 1-2 module |
| 28 | Supplying and fixing of the following modular accessories including necessary connection etc. as required. |
| 29 | 4 step fan regulator (1M). |
| 30 | Buzzer call bell (1M) |
| 31 | 3/6 pin 25 amps socket outlet (2M) |
| 32 | 20/25 amps single phase motor starter switch (2M) |
| 33 | Supplying and installation of Bus bar chamber of the following ratings and sizes made of steel sheet enclosure with all accessories including necessary connection etc. as required. |
| 34 | 63 amps 415 volts four strip Copper busbar chamber 4 ways of size (330mmx280mmx100mm) |
| 35 | Supplying and installation of Switch disconnector fuse unit (main switch) of the following ratings with all accessories including necessary connection etc. as required. |
| 36 | 63 amps 415 volts TPN main switch (rewireable) |
| 37 | Supplying and installation of change over switch of following ratings with enclosure including necessary connection etc. as required. |
| 38 | 400 amps FP on load change over switch (Front handle with enclosure)- |
| 39 | Supplying, installation, testing & commissioning of powder coated prewired panel board suitable for 415 volts TP MCCB as incomer & outgoing including busbar & connection as required of the following ratings & sizes. |
| 40 | 4 way TP MCCB outgoing & TP MCCB incomer upto 400 amps |
| 41 | 6 way TP MCCB outgoing & TP MCCB incomer upto 400 amps |
| 42 | Supplying, installation, testing & commissioning of powder coated prewired digital meter module complete with ammeter, voltmeter, phase indicator lamp, control fuses, CTs, in the existing panel board including connection etc. as required. |
| 43 | Supplying, installation, testing & commissioning of powder coated side cable module (1 pair) in the existing panel board including connection etc. as required suitable for the following sizes and ratings. |
| 44 | 4/6 way outgoing and incomer upto 400 amps |
| 45 | Supplying, installation, testing & commissioning of powder coated prewired digital meter module complete with ammeter, voltmeter, phase indicator lamp, control fuses, CTs, in the existing panel board including connection etc. as required. |
| 46 | (2+4) / 6 way SPN MCB DB (double door). |
| 47 | (2+10) / 12 way SPN MCB DB (double door) |
| 48 | 4 way horizontal TPN MCB DB (Double door) |
| 49 | 6 way horizontal TPN MCB DB (Double door) |
| 50 | 8 way horizontal TPN MCB DB (Double door) |
| 51 | Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connection as required. |
| 52 | 6 to 32 amps SP MCB. |
| 53 | 6 to 32 amps DP MCB. |
| 54 | 6 to 32 amps TPN MCB |
| 55 | 40/50/63 amps TPN MCB |
| 56 | Supplying & installation of TP/FP MCCB of following ratings in the existing MCCB enclosure/ panel board including connection etc as required (Ics=100% of Icu with adjustable settings) |
| 57 | 16 to 100 amps TP MCCB, Breaking capacity 16/18KA (Thermal Magnetic) |
| 58 | 160 amps TP MCCB, Breaking capacity 25KA (Thermal Magnetic) |
| 59 | 200 amps TP MCCB, Breaking capacity 36KA (Thermal Magnetic) |
| 60 | 320 amps TP MCCB, Breaking capacity 36KA (Thermal Magnetic) |
| 61 | Supplying & installation of Surge Protection Device (SPD) of following ratings in the existing Panels/MCB DBs including necessay connections etc as required. |
| 62 | Surge Protection Device (SPD, withdrawable) (Type-2) with Imax 70 KA (3P+N). |
| 63 | Supplying & fixing of 1200 mm sweep white color AC ceiling fan capacitor type double ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades, including wiring the down rod with 2x1.5 sqmm PVC insulated Copper conductor cable(FR) (ISI marked, BEE 1 star/minimum service value 4.0 m3/min/W) |
| 64 | Supplying & installation of 400 mm sweep AC wall mounting fan with metal blade including connection etc as required. |
| 65 | Supplying & installation of 600 mm sweep AC wall mounting air circulator including connection etc as required. |
| 66 | Supplying & installation of 300 mm sweep metalic body exhaust fan including connection etc as required. |
| 67 | Supplying & installation of 300 mm sweep 900 rpm metalic body exhaust fan including connection etc as required (ISI marked) |
| 68 | Supplying & installation of shutter for 225/230/300 mm sweep metalic body exhaust fan in the existing hole as required. |
| 69 | Making different sizes of hole in the wall for fixing of exhaust fan including finishing the same with cement plastering and painting etc as required. |
| 70 | Supplying and fixing of following surface/recess mounted LED luminaries in powder coated die cast housing complete with high efficiency polycarbonate diffuser and necessary connection etc. as required (with 50000 burning hours and minimum lumen output of 100 lm/watt) |
| 71 | Surface mounted integrated 10 watt LED batten with polycarbonate diffuser |
| 72 | Surface mounted box type batten suitable for single 18/20 watt integrated LED tube lamp (without lamp) |
| 73 | Surface mounted round/Square shaped 12 watt LED downlight with integral driver and high quality polycarbonate diffuser. |
| 74 | Recessed/Surface mounted 2ft x 2ft decorative 36 watt LED panel light with integral driver and high quality polycarbonate diffuser. |
| 75 | Supplying and fixing of following LED Tubes, retrofit bulbs/lamps for LED luminaries including necessary connection etc. as required. |
| 76 | 12 watt LED retrofit lamp with polycarbonate body and aluminium heatsink |
| 77 | 18/20 watt LED tube with integral driver and polycarbonate diffuser (50000 burning hours and minimum lumen output of 100lm/watt) |
| 78 | Supplying and fixing of following outdoor LED luminaries in powder coated die cast housing complete with heat resistant tempered glass/diffuser including necessary connection etc. as required (50000 burning hours and minimum lumen output of 100 lm/watt). |
| 79 | 60 watt LED street light fixture with integral driver and secondary lens (IP 66). |
| 80 | 50 watt LED flood light fixture with integral driver and secondary lens (IP 66) |
| 81 | Supplying & fixing of G.I. pipe (medium gauge) bracket fabricated at suitable angle for fixing of outdoor light on wall/ RCC base with necessary MS clamp, nut, bolt etc as required. |
| 82 | 40 mm dia. |
| 83 | Supplying & installation of astronomical time switch including necessary connection etc as required. |
| 84 | Supplying & installation of following power contactors including necessary connection etc as required. |
| 85 | 3 pole 18 amps (AC3) power contactors with 1NO+1NC Aux. Contact. |
| 86 | Supplying and laying of the following XLPE insulated PVC sheathed alluminum armoured cable including connection etc as required. |
| 87 | 3.5 core 35 Sq mm. |
| 88 | 3.5 core 240 Sq mm |
| 89 | Supplying and laying of following sizes XLPE insulated PVC sheathed copper conductor Un-armoured cable including necessary connection etc as required |
| 90 | 3 core 2.5 Sq mm |
| 91 | Supplying and fixing of thermoplastic cable junction box with connectors suitable for following sizes cable. |
| 92 | 1.5 sqmm - 4 sqmm Cable. |
| 93 | Excavation of earth for cable trench of 800mm depth & 300mm width in all kinds of soil including back filling of cable trench with the excavated soil with 20cm layer of sand, 3.5 nos bricks per metre for protection including ramming, consolidating to the original shape as per dirrection of Site Engineer. |
| 94 | Drawing of armoured/un-armoured cable with proper saddling etc as required |
| 95 | Supplying, installation, testing and commissioning of following ratings inverter with Square/ sine wave technology, noiseless operation, inbuilt advance PCB programming, microprocessorwith all accessories including necessary connections etc. as required: |
| 96 | 900VA, 12V DC, 1 Ph input/1 Ph output inverter(Sine wave technology):- |
| 97 | Supplying, installation, testing and commissioning of following ratings Valve regulated lead acid(VRLA) battery with all accessories including necessary connections etc. as required:- |
| 98 | 12 V/ 180AH tall tubular/ flat plate Battery:- |
| 99 | Supplying, installation, testing & commissioning of 6kg ABC powder type fire extinguisher, discharge mechanism-squeeze grip type range minimum 2mtr, applicable on class A,B,C, & electrically stated fire, MAP-90,can contrast-mig welded, valve construction forgining & machining, external coating of can epoxy polyester powder coating, sheet metal thickness 1.06mm, conforms to BIS standard |
| 100 | Supplying, installation, testing & commissioning of single side LED Exit sinage with in built battery as per site requirement. |
| 101 | Supplying, installation, testing & commissioning of Double side LED Exit sinage with in built battery as per site requirement . |
| 102 | Supplying and fixing of MS frame made of (25 x 25 x 5)mm MS angle with necessary support by (40 x 6)mm MS flat and 10 mm thick boiled plywood on top, grouted on wall with 4 nos leg(25x25x5mm MS angle 20 cm long) finished with red oxide and 2 coat synthetic enamel paint including necessary cc work, mending the damages & painting etc as required. |
| 103 | Supplying & installation of metalic fan clamp box of standard size with 3mm thick bakelite/plastic cover as required. |
| 104 | Supplying and fixing of the following PVC conduit (medium gauge) with all accessories on slab/recessed on wall etc as required |
| 105 | 19/20 mm dia |
| 106 | 25 mm dia |
| 107 | SITC of UL864 10th Edition UL Listed and FM approved Analog Addressable 2 Loop Fire Alarm control panel.Panel shall be running on full digital protocol with 32 bit Microprocessor.The Panel shall be cpmlete with color touch screen => 6' LCD Display with minimum 160 characters,minimum 800 trouble events including 200 alarm log history events.Each addressable loop shall be capable of taking 250 addresses per loop configuring neither as all detectors or modules or any mix of both.The system shall be polarity insentive .The panel shall support degrade mode operation or shall have redundant CPU and shall have battery back up of 24 hrs in normal condition and 30minutes in Alarm condition. |
| 108 | SITC of UL Listed and FM approved Repeater Panel.The panel shall be able to give location of all fire/fault and isolation conditions of addressable units of main Fire Alarm panel via the address codes and also having remote -system-control capabilities.The panel shall have a color touch screen monochrome LCD display and 10,000 event memory. |
| 109 | Supplying, installation, testing & commissioning of intelligentanalog addressable photothermal detector complete with mounting base complete as required. |
| 110 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 111 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required |
| 112 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 113 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel/PVC conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 114 | Single pair 2-core 1.5 sqmm |
| 115 | Two pair 2-core 1.5 sqmm Please Enable Macros to View BoQ information |