| 1 | Demolition of cement concrete in ground floor and paving not exceeding 15cm thickness below or above ground level complete all as specified and as directed. |
| 2 | M&L cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundations filling and mass concrete complete all as specified and as directed. |
| 3 | M&L cement concrete 1:2:4 type B-2 using 40mm graded stone aggregate as in walls or retaining walls, any thickness, size or shape including pilasters, buttresses columns, pillars, boundary pillars and posts including caps and bases complete all as specified and as directed. |
| 4 | Taking down chowkats or frames with shutters (without taking of shutters from the frames) exceeding 1.5 Sqm but not exceeding 4 Sqm each complete all as specified and as directed. |
| 5 | S&F 1.25 mm thick Steel rolling shutters, with out ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indicated, complete: but gear operated type with bevel gear box and crank handle complete all as specified and as directed. |
| 6 | S&F Pressed steel frames of size 105mm x 60 mm for door with one or more rebates including supply and fixing 125 mm size MS hinges, lock strike plate, etc.complete all as specified and as directed. |
| 7 | S&F 30mm thick flush shutter , solid core construction with block board core and plywood face panels, both faces are covered with decorative face veneer with lipping/ frame to match complete all as specified and as directed. |
| 8 | Dismantling Asbestos cement (corrugated, semicorrugated , etc) sheets n roof coverings. complete all as specified and as directed. |
| 9 | S&F Pre-painted galvaLume aluminium zinc coating GI based corrugated steel sheet 0.5mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall,fixed with self tapping screws complete all as specified and as directed. |
| 10 | S&F pre painted galvalume aluminium zinc coating GI based plain steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering /cladding to wall fixed with self tapping screws complete all as specified and as directed. |
| 11 | M&L roof trusses framed), trussed, rail and fastening and bracket framing (Beam, Tee, angle, tubler Section) of FE-410(Gde-E250) quality - B, including distance pieces complete all as specified and as directed. |
| 12 | Demolition of brickwork or stone boulder masonry, built in cement mortar including all quoins, arches, pillars, etc., but excluding ashlar facings, dressed stone work and precast concrete articles complete all as specified and as directed.. |
| 13 | M&L Brickwork with subclass \\"B\\" bricks, straight or curved on plan exceeding 6m mean radius built in cement mortar 1:6 complete all as specified and as directed. |
| 14 | Taking down cement plaster on brick or stone walls, etc, incl raking out joints, hacking for key, scrubbing down with water, etc & prepare to receive new plaster complete all as specified and directed |
| 15 | M&L for 15mm thick rendering in cement mortar 1:6 on brick work or concrete surfaces, surface finished even and fair complete all as specified and as directed. |
| 16 | M&L for 15mm thick rendering in cement mortar 1:4 on brick work or concrete surface including supply and mixing with water proofing compound @ 3% by weight of cement, surfaces finished even and fair complete all as specified and as directed. |
| 17 | M&L applying two coats of oil bound distemper over one coat of primer including preperation of newly plastered surfaces of wall complete all as specified and as directed. |
| 18 | M&L applying two coats of cement base paint over a coat of primer including preperation of newly plastered surfaces of wall complete all as specified and as directed. |
| 19 | M&L applying two coat of white wash on ceiling including complete removal of existing treatment of ceiling complete all as specified and as directed.. |
| 20 | M&L applying two coats of oil bound distemper over one coat of primer including complete rremoval of existing treatment on wall surface complete all as specified and as directed. |
| 21 | M&L applying two coats of of cement base paint on wall surfaces including complete removal of existing treatment on walls surface complete all as specified and as directed. |
| 22 | M&L applying two coat of synthetic enamel paint over a coat of red oxide primer including preparation of new steel surface of any description exceeding 10cm width or girth complete all as specified and as directed. |
| 23 | Excavation in trenches , not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc and getting out in soft/loose soil complete all as specified and as directed. |
| 24 | Returning, filling in, including spreading levelling watering and well ramming in layers not exceeding 25 cm as in soft/loose soil complete all as specified and as directed. |
| 25 | Removing excavated soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. |
| 26 | M&L for natural river sand as cushioning of cables including spreading and punning down complete all as specified and as directed.Note : Punned thickness shall be measured for payment purpose |
| 27 | Supply , laying, jointing and testing in replacement of underground HT cable XLPE insulated ,screened PVC bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 95 Sqmm 3 Core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and as directed. |
| 28 | Supply, laying, jointing & testing in replacement of underground LT cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sqmm 3.5 core laid in trenches /ducts/ along poles/ through pipe under road etc complete all as specified and as directed. |
| 29 | Supply and fix cable jointing kit for 11 KV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 95 sqmm all as specified and as directed. |
| 30 | Supply and fix cable jointing kit for 11 KV grade cable for out door termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 95 Sqmm all as specified and as directed. |
| 31 | Supply and laying un-reinforced precast concrete cable cover class HVP type 2 with peak size 450 mm x 180 mm x 40 mm complete all as specified and as directed. |
| 32 | M&L 80 mm bore galvanised iron pipe, light grade with all fittings, laid in trenches,under roads, drain paths, fixed to poles/walls with mild steel clamps, bolts, nuts and washers complete all as specified and as directed. |
| 33 | M&L100 mm bore galvanised iron pipe, light grade with all fittings, laid in trenches,under roads, drain paths, fixed to poles/walls with mild steel clamps, bolts, nuts and washers complete all as specified and as directed. |
| 34 | Supply and laying sub class 'B' bricks old size designation 75 as in cable protection complete all as specified and directed. |
| 35 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine of dia 150mm complete all as specified and as directed. |
| 36 | Supply, installation, testing and commissioning of transformer suitable for 315 KVA (Level-3) step down floor mounted outdoor type 11/.433 kVA, 3 phase, 50 Hz AC, IS: 1180-2014 ISI marked, double wound core type copper wound, oil immersed, air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connected on LV side in accordance with vector symbol Dyn-11 (vector group 4) with neutral brought out on LV side with for earthing and having tapping on HV side for constant out put so as to alter/vary secondary voltage by (Tapping range + 5 % to - 10% in equal step of 2.5 % ) changed by means of manualy operated \\" off load\\" taps changing gear. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-I and IS-2026. The limit of temprature rise after continuous full load run as specified in IS-2026 shall be suitably adjusted to suite the maximum ambient temprature of 55 degree centigrade as prevalent at Bamrauli.The transformer shall be complete with the following fittings and accessories :- (a) Oil conservator tank with fillings holes and cap filter type drain valve and oil level gauge(b) Silicagel breather with connecting pipe, first fill of dehydrating agent.(c) Explosion relief mounted on tank with double diaphram and equalizer pipe connected to conservator air tank (pressure release valve)(d) Air release valve plug |
| 37 | (e) One cable box on LV side (Secondary) consisting of 04 Nos porcelain bushing with nuts, washers & bushing rods with 01 cable gland suitable for reception of taking out suitable size cable, including gland joint.(f) Explosive vent (g) 01 No 100 mm dia thermometer vapour pressure type having range 0-120 degree centigrade with max temp indicator and resetting device incl max reading pointer washer etc. (h) Thermometer pocket on tank cover(j) 04 Nos plain solid CI detachable rollers(k) Two nos Earthing terminals marking plate.(l) Rating plate and terminal marking plate. (m) Extra bushing for neutral outside the cable box brought out on LV side.(n) First filling of oil conforming to IS and tested upto 60 KV dielectric strenght.(o) Lifting lugs(p) Oil drain valve with plug(q) One cable box on HV side (Primary) consisting of 01 cable gland suitable for reception of taking in HT cable including gland joints. |
| 38 | (w) Extra bushing for neutral out side the LV side(x) PCC plateform shall be provided as per drg No CEAF/TD/EM/03, complete all as specified including XPM welded mesh fencing and doors including 75 x 40 mm channel.Note:- (i) Anything missed above but is required for efficient functioning of transformer is deemed to be included in the unit rate quoted under this item(ii) Full load testing shall be done at site. The artificial load shall be arranged by contractor. (iii) Transformer shall be tested in manufacturer's workshop by the rep of Accepting officer before dispatch. |
| 39 | Supply, installation, testing and commissioning of transformer suitable for 200 KVA (Level-3) step down floor mounted outdoor type 11/.433 kVA, 3 phase, 50 Hz AC, IS: 1180-2014 ISI marked, double wound core type copper wound, oil immersed, air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connected on LV side in accordance with vector symbol Dyn-11 (vector group 4) with neutral brought out on LV side with for earthing and having tapping on HV side for constant out put so as to alter/vary secondary voltage by (Tapping range + 5 % to - 10% in equal step of 2.5 % ) changed by means of manualy operated \\" off load\\" taps changing gear. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-I and IS-2026. The limit of temprature rise after continuous full load run as specified in IS-2026 shall be suitably adjusted to suite the maximum ambient temprature of 55 degree centigrade as prevalent at Bamrauli.The transformer shall be complete with the following fittings and accessories :- (a) Oil conservator tank with fillings holes and cap filter type drain valve and oil level gauge(b) Silicagel breather with connecting pipe, first fill of dehydrating agent.(c) Explosion relief mounted on tank with double diaphram and equalizer pipe connected to conservator air tank (pressure release valve)(d) Air release valve plug |
| 40 | (e) One cable box on LV side (Secondary) consisting of 04 Nos porcelain bushing with nuts, washers & bushing rods with 01 cable gland suitable for reception of taking out suitable size cable, including gland joint.(f) Explosive vent (g) 01 No 100 mm dia thermometer vapour pressure type having range 0-120 degree centigrade with max temp indicator and resetting device incl max reading pointer washer etc. (h) Thermometer pocket on tank cover(j) 04 Nos plain solid CI detachable rollers(k) Two nos Earthing terminals marking plate.(l) Rating plate and terminal marking plate. (m) Extra bushing for neutral outside the cable box brought out on LV side.(n) First filling of oil conforming to IS and tested upto 60 KV dielectric strenght.(o) Lifting lugs(p) Oil drain valve with plug |
| 41 | (q) One cable box on HV side (Primary) consisting of 01 cable gland suitable for reception of taking in HT cable including gland joints.(r ) Hand hole of sufficient size to assess interior of tank(s) Dehydrating breather with first filling of Dehydrating agent(t) Two earthing of terminal on tank body to facilitate fixing of 32x6mm GI strip.(u) Rating plate with terminal marking plate(v) Inspection cover(w) Extra bushing for neutral out side the LV side(x) PCC plateform shall be provided as per drg No CEAF/TD/EM/03, complete all as specified including XPM welded mesh fencing and doors including 75 x 40 mm channel.Note:- (i) Anything missed above but is required for efficient functioning of transformer is deemed to be included in the unit rate quoted under this item(ii) Full load testing shall be done at site. (iii) Transformer shall be tested in manufacturer's workshop by the rep of Accepting officer before dispatch. |
| 42 | Supply, installation, testing and commissioning of transformer suitable for 160 KVA (Level-3) step down floor mounted outdoor type 11/.433 KVA, 3 phase, 50 Hz AC, IS: 1180-2014 ISI marked, double wound core type copper wound, oil immersed, air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connected on LV side in accordance with vector symbol Dyn-11 (vector group 4) with neutral brought out on LV side with for earthing and having tapping on HV side for constant out put so as to alter/vary secondary voltage by (Tapping range + 5 % to - 10% in equal step of 2.5 % ) changed by means of manualy operated \\" off load\\" taps changing gear. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-I and IS-2026. The limit of temprature rise after continuous full load run as specified in IS-2026 shall be suitably adjusted to suite the maximum ambient temprature of 55 degree centigrade as prevalent at Bamrauli.The transformer shall be complete with the following fittings and accessories :- (a) Oil conservator tank with fillings holes and cap filter type drain valve and oil level gauge(b) Silicagel breather with connecting pipe, first fill of dehydrating agent.(c) Explosion relief mounted on tank with double diaphram and equalizer pipe connected to conservator air tank (pressure release valve)(d) Air release valve plug |
| 43 | (e) One cable box on LV side (Secondary) consisting of 04 Nos porcelain bushing with nuts, washers & bushing rods with 01 cable gland suitable for reception of taking out suitable size cable, including gland joint.(f) Explosive vent (g) 01 No 100 mm dia thermometer vapour pressure type having range 0-120 degree centigrade with max temp indicator and resetting device incl max reading pointer washer etc. (h) Thermometer pocket on tank cover(j) 04 Nos plain solid CI detachable rollers(k) Two nos Earthing terminals marking plate.(l) Rating plate and terminal marking plate. (m) Extra bushing for neutral outside the cable box brought out on LV side.(n) First filling of oil conforming to IS and tested upto 60 KV dielectric strenght.(o) Lifting lugs(p) Oil drain valve with plug(q) One cable box on HV side (Primary) consisting of 01 cable gland suitable for reception of taking in HT cable including gland joints.(r ) Hand hole of sufficient size to assess interior of tank(s) Dehydrating breather with first filling of Dehydrating agent(t) Two earthing of terminal on tank body to facilitate fixing of 32x6mm GI strip.(u) Rating plate with terminal marking plate(v) Inspection cover. |
| 44 | (w) Extra bushing for neutral out side the LV side(x) PCC plateform shall be provided as per drg No CEAF/TD/EM/03, complete all as specified including XPM welded mesh fencing and doors including 75 x 40 mm channel.Note:- (i) Anything missed above but is required for efficient functioning of transformer is deemed to be included in the unit rate quoted under this item(ii) Full load testing shall be done at site. The artificial load shall be arranged by contractor. (iii) Transformer shall be tested in manufacturer's workshop by the rep of Accepting officer before dispatch. |
| 45 | Dismantling of existing transformer , servo voltage stablizer and VCB including transportation from the existing location to MES store yard of GE(AF) Bamrauli complete all as specified and as directed |
| 46 | Supply, installation, testing and commissioning of HT 11 KV 3 phase 50 HZ cycles indoor type totally enclosed metal clad switch gear complete with Vacuum circuit breaker having rupturing capacity upto 350 MVA and of rating upto 630 Amps, overload, earth fault and short circuit protection, required battery bank / power pack with charging arrangement complete all as specified and directed with specifications mentioned in IS /IEC 62271-201 including latest ammendment / addition. The panel shall have the facility of all the protection system including provision of digital type Ampere meter, Voltmeter, Push buttons, MCBs of required rating, LED indicator Lamps and load manager having with all instantaneous & integrated electrical parameters with old refreshed parameters backup and communication facility with inbuilt selector switch and CTs of appropriate ratio with percentage load bar graph (Model EM 6400) equivalent-01 No. The panel shall also provided with space heater, self powered, IDMT numerical relay, overcurrent and earth fault with high adjustable setting, short curcit fault relay for complete protection of HT 11 KV 3 phase feeder. Relay type REF 601 ( 50, 51, 50N, 51N). The VCB shall have the standard of single element high speed tripping relay with hand reset flag, flush mounting type with 4NO+3NC type PQ8NCH2J, trip circuit supervision relay, hand reset flag flush mounting type 1 NO+1NC+2CO type TCs, AC/DC fail relay PN8CH2JS of ABB of equivalent in Schneider/Simenes/CG. All panel wiring shall be of 1100 Volts grade single core standard copper conductor with PVC insulation, vermin rodent proof of size 1.5/2.5 Sqmm auxilary load supply shall be 24V DC. |
| 47 | The VCB shall have the standard of IEC 62271-100, 400Amps, 11 KV, 50Hz with short circuit current rating 25 KA for 3 secs. The breaking capacity of VCB shall design for 25 KA and making capacity of 62.5 KA peak with maximum temperature rise over ambient shall be within limits as per IEC 2271-100. The contact resistance of main pole<60 micro-ohms, dry-1minute power frequency with stand between line terminal and ground object-28KV rms, between terminals with breaker contact open 25kv rms 1.2/50 micro second full wave impulse between line terminals and grounded object. The spring charging motor shall have 230V AC and charging time required for motor 15 sec (Max). The ground clearance of VCB shall be as per manufacturers GA drawing. The panel shall be designed for floor mounting, free standing, simplex type control and realy panel in sheet enclosure with powder coated paint after suitable pretreatment with IP4X protection. Please Enable Macros to View BoQ information |
| 48 | The VCB shall have the standard of IEC 62271-100, 400Amps, 11 KV, 50Hz with short circuit current rating 25 KA for 3 secs. The breaking capacity of VCB shall design for 25 KA and making capacity of 62.5 KA peak with maximum temperature rise over ambient shall be within limits as per IEC 2271-100. The contact resistance of main pole<60 micro-ohms, dry-1minute power frequency with stand between line terminal and ground object-28KV rms, between terminals with breaker contact open 25kv rms 1.2/50 micro second full wave impulse between line terminals and grounded object. The spring charging motor shall have 230V AC and charging time required for motor 15 sec (Max). The ground clearance of VCB shall be as per manufacturers GA drawing. The panel shall be designed for floor mounting, free standing, simplex type control and realy panel in sheet enclosure with powder coated paint after suitable pretreatment with IP4X protection. Please Enable Macros to View BoQ information |