|
| 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing urface/recessed steel/PVC conduit as required.. 3 x1.5 sq.mm |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing urface/recessed steel/PVC conduit as required. 3 x 2.5 sq. mm |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing urface/recessed steel/PVC conduit as required.3 x 4 sq. mm |
| 4 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole (a) Single Pole |
| 5 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) 40 A |
| 6 | Supply and Fixing of 3 mm thick phenolic laminated sheet |
| 7 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, nterconnections, powder painted including earthing etc. as required. (But without MCB /RCCB/Isolator)(a) 6 way, Double Door |
| 8 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temprange -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEMwarranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) 18- 22 watt |
| 9 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.(a) 5/6 A switch |
| 10 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.15/16 A switch |
| 11 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 A socket outlet |
| 12 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.6 pin 15/16 A socket outlet |
| 13 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. (b) 180 mm X 100 mm X 60 mm deep |
| 14 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. 200 mm X 250 mm X 60 mm deep |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in FRLSont on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modularm socket outlet and 15/16 amps modular switch, connection etc. as required |
| 16 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 amp switch |
| 17 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 amp socket out let |
| 18 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amps switch . |
| 19 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin15/16 amp socket outlet |
| 20 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.3 Module (100 mmX75 mm) |
| 21 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.6 Module (200 mmX75 mm) |
| 22 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.8 Module (125 mmX125 mm) |
| 23 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessedconduit as required. 20 mm |
| 24 | Supply of 12\\" (300mm) sweep 1400 rpm exhaust fan heavy duty complete with shutters, blades etc as reqd. |
| 25 | Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |
| 26 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 27 | Supply, Installation, testing and commissioning of cubical type control panel board for single phase & Three Phase submersible pumping set of following rating complete with contactor, relay , MCB ,condenser ,voltmeter, ammeter and indication lamp etc including connections etc as reqd. (b) 1.5 HP (Single Phase) |
| 28 | SITC of single/three phase monoblock pump set complete with all accessories worable on 240/415 volts, 50 Hz ac supply (a) 1 HP (0.75kw) single phase pump set, head from 12-30 metre suction delivery head from 12-30 metre sunction and delivery 25x25 mm. |
| 29 | Repair/rewinding of existing 1 HP monoblock pump set including replacement of parts like gun metal bush/bearing condensor impeller etc to make the pump functional as required. Please Enable Macros to View BoQ information |