| Sl. No. | Item Description |
| 1 | Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 100 x 50 x 5 mm angle and each vertical compartment with 50x50x5 mm MS angle iron). The base of panel should be made with 100mm x 50mm x 5 mm M.S. channel. cable outgoings form panel either should be back side of the panel of arrangement for cable alley is required and sprader terminal or copper falt has been require for outgoing & incoming connection. [Manufacturer/Fabricator having Test Certificates from CPRI]. [An Auto Cad Drawing of the panel has to approved by EIC before making of panel.] [Factory inspection has to be made by the agency before painting] [NS] |
| 2 | INCOMER : 250 Amp FP moulded case circuit breaker of (36KA Ics Value) with Thermal Magnetic release and rotatry handle with ON/OFF/TRIP/R/Y/B indication Lamps, MFM , Trip record mdoule with Communication Facility along with Control SP MCB. (Make- L&T, /Legrand/Seimens/ABB or equivalent make as per approved by EIC)- 1 No. |
| 3 | METERING & INDICATION:-a) Advanced LED Multifunction Meter Digital Type Load Monitor ( Make L&T / Legrand/Siemens or equivalent make as approved by EIC) - 1 No. b) LED single function Meter 1Ph LED Ammeter Cl 0.5( Make- L&T/Legrand/Siemens or equivalent make as approved by EIC) --- 3 nos. c) LED single function Meter 1Ph LED Voltmeter Cl 0.5 ( Make- L&T/Legrand/Siemens or equivalent make as approved by EIC)-- 3 nos.d) 230V R.Y.B. LED indicator lamp-(SIEMENS/L&T/Legrand or equivalent make as approved by EIC) ---- 3 nos.e) 250/5 Amp ratio C.T (Kappa/Pragati/AE or equivalent make as approved by EIC) --- 3 nos.f) S & F 6 Amp SPMCB (Make-SIEMENS/L&T/Legrand or equivalent make as approved by EIC)---6 nos. |
| 4 | g) Indicating LED lamps for On/Off with protective SP MCB's.( Make- L&T/Legrand/Siemens or equivalent make as per approved by EIC)- 1 Seth) S&F Trip Record Module including communication cable of 2 mtr. length.(Make- L&T / Legrand/Siemens or equivalent make as approved by EIC)(i) 3 Phase Energy Meter with RS-485 port( Make- L&T/Legrand/Seimens or equivalent make as per approved by EIC)- 1 Set(j) 3 Phase Energy Meter with RS-485 port( Make- L&T/Legrand/Seimens or equivalent make as per approved by EIC)- 1 Set |
| 5 | BUSBAR:-500V, 400 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar [size of flat 4x 50 mm x 5 mm] mounted on non-hygroscopic FRP/SMC/DMC insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set. |
| 6 | The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications. |
| 7 | OUTGOINGS:-(i) 63A FP MCCB, 25 kA breaking capacity with thermal magnetic release protection. (Make- L&T / Legrand/Seimens /ABB or equivalent make as approved by EIC)- 16 Nos.(ii) Indicating LED lamps for On/Off/trip with protective SP MCB's. (Make- L&T/Legrand/Seimens/Rishabh Instrument or equivalent make as approved by EIC)- 16 Sets |
| 8 | Interconnection :-All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pvc insulated multistranded single core Cu cable as directed by E.I.C and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads. |
| 9 | Earthing :-A separate continuous GI earth busbar of size 50mm x 6mm shall run across the full length of the panel board . All electrical equipment are to be properly earthed with suitable size G.I. wire. |
| 10 | The complete panel board is to be spray painted after required surface treatment by 9 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating with cable alley chember & ventilation facility. |
| 11 | Installation :-The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C.All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC. |
| 12 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS. [Make: Polycab/Havells/RR] |
| 13 | 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC [1(v)/E-9] |
| 14 | Supply & Delivery of XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make:- Polycab/Havells/RR] |
| 15 | 4 Core 16 Sqmm [For AHU Power Supply] |
| 16 | 4 Core 35 Sqmm [ For 2 x 30 KVA UPS Shifting to Grond Floor UPS Room] |
| 17 | 4 Core 120 Sqmm [For AHU Panel power supply] |
| 18 | Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. [2B/F-1] |
| 19 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting. [2C/F1] |
| 20 | Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. [2E/F-1] |
| 21 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire as per GS. |
| 22 | 4 Core 16 sqmm [6(i)/F-3] |
| 23 | 4 Core 120 Sqmm [6(ii)/F-3] |
| 24 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below as per GS. |
| 25 | 4 Core 16 Sqmm [7©/F-4] |
| 26 | 4 Core 35 sq mm [7©/F-4] |
| 27 | 4 Core 120 Sqmm [7©/F-4] |
| 28 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials as per GS. |
| 29 | 4 Core 16 Sqmm [8(b)/F-5] |
| 30 | 4 Core 35 sq mm [8(b)/F-5] |
| 31 | 4 Core 120 Sqmm [8(b)/F-5] |
| 32 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support as per GS. [D-14/34aii] |
| 33 | With 25x25x3mm angle iron support. 300x50x1.25mm (18SWG) |
| 34 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes |
| 35 | 2.5 sq mm |
| 36 | 4 sq mm |
| 37 | 6 sq mm |
| 38 | 10 sq mm |
| 39 | 16 sq mm |
| 40 | False Ceiling Work |
| 41 | Supplying ,fitting & fixing Eco-friendly, Water Resistance and Incombustable Calcium Silicate board/tiles (Density >900 Kg per Cu.M.) of approved design and brand placed in the grid module to form a false ceiling all complete as per drawing & direction of Engineer - in- Charge.(i) 6mm thick square edged Calcium Silicate tiles (size 595mm X 595mm) [Page No. 168 Item No.- E1 of PWD SOR] |
| 42 | Supplying,fitting & fixing in position suspended false ceiling with frame work of aluminium hollow section of size 50mm X 25mm (2.0mm thickness) combined with aluminium corners of size 38mm X 25mm, suspended by aluminium hollow tube section of size 38mm X 25mm having size of 600mm X 600mm ceiling with aluminium composit panels (ACP) - Interior grade of thickness 3.0mm comprising of proctective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent complete in all respect including all incidental charges etc. as per direction of Engineer-in-charge.[NS] |
| 43 | Modular Monoblock Joint Free Ceiling & Corner Panels for O.T [For 2 Nos OT]Supplying, fitting and fixing of joint free Ceiling and Corner Panel made of Modular Monoblock PUF Panels, having Front Side (visible inside of OT) made of Stainless Steel (304) sheet of thickness 0.8 mm and Back Side made of factory powder coated PPGI sheet of thickness 0.50 mm. All Panels should be injected with Poly Urethane Foam (PUF) with a minimum density of 40 Kg/ m3 and should be sealed with Aluminium Extrusion to make the structure rigid. Total thickness of the Ceiling & Corner Panel should be 30 mm. The Corner Panels should be factory fitted with Ducting and Return Grill Cut-outs for easy connection. Each OT must have Cascade Pressure Stabilizer having multi 304-Graded Stainless Steel Blades to control air pressure. The Sheet should be of TATA/ JINDAL/SAIL or equivalent reputed make and Panels should be from JINDAL MECTEC/ JDV / ALTOS or equivalent reputed make. The rate includes cost of all materials, fixtures, labour, installation charges, transportation cost, complete in all respect as per direction, instruction and approval of the Engineer-in-Charge. [NS]This is a specialized walling system designed for high-hygiene environments, most commonly Modular Operation Theatres (OT). |
| 44 | Modular Monoblock Joint Free SS Wall Panels for O.T [For 2 Nos OT]Supplying, fitting and fixing of joint free Wall Panel made of Modular PUF Panels, having Front Side (visible inside of OT) made of Stainless Steel (304) sheet of thickness 0.8 mm and Back Side made of factory powder coated PPGI sheet of thickness 0.50 mm. All Panels should be injected with Poly Urethane Foam (PUF) with a minimum density of 40 Kg/m3 and should be sealed with Aluminium Extrusion to make the structure rigid. Total thickness of the wall Panel should be 50 mm. The Corner Panels should be factory fitted with Ducting and Return Grill Cut-outs for easy connection. Each OT must have Cascade Pressure Stabilizer having multi 304- Graded Stainless Steel Blades to control air pressure. The Sheet should be of TATA/JINDAL/SAIL or equivalent reputed make and Panels should be from JINDAL MECTEC/ JDV / ALTOS or equivalent reputed make. The rate includes cost of all materials, fixtures, labour installation charges, transportation cost, complete in all respect as per direction, instruction and approval of the Engineer-in-charge. [NS]This is a specialized walling system designed for high-hygiene environments, most commonly Modular Operation Theatres (OT). |
| 45 | Lift Work |
| 46 | Supply & fixing of MS stracture inside the existing lift shaft made by 2 nos. ISMB 200 of thichness 5.7 mm having length 8 ft each. 2 Nos. ISMB fixed by welding on a 20mm thick MS plate in each side in a distance of 250mm. The size of the MS sheet will be 3ftx2ft and making 15 nos. 20mm dia hole in each plate. The total febricated stracture fied on the existing lift shaft by 18mm dia 200mm long bullet type fastner. The scope of work also includes scaffolding arrangement inside lift shaft, hiring of man power, painting of stracture and mending the damages as per direction of EIC. [NS] |
| 47 | Excavation of soil for installation of Earth Electrode and filling & ramming.For Morrum Soil [ 1(b)/G-1 ] |
| 48 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe [ 2(a)/G-1 ] [SPD 3+ UPS 2 ] |
| 49 | Extra for providing masonry enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width duly plastered with cement mortar (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe [ 3(a)/G-2 ] |
| 50 | Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. as per GS. [5(d)/G-3] |
| 51 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. |
| 52 | No. 4 SWG [5(a)(i)/G-2 ] |
| 53 | No. 10 SWG [5(a)(iv)/G-2 ] |
| 54 | Supplying and fixing double door SPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.( Make - Legrand/L&T/Seimens ) |
| 55 | 2+6 way [ 13 / D- 9 ] [For Three Phase SPD & 3 Nos. Lift Outgoing] |
| 56 | Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per GS. |
| 57 | 2 way [11/D-9] [For 6 KV UPS Input Output] |
| 58 | 4 way [11/D-9] [For Three Phase SPD] |
| 59 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [ Make -Legrand ] |
| 60 | 6-32 A DP [ 7 / D- 6] [For 6 KV UPS Input Output] |
| 61 | 63A FP [ 7 / D- 6] [For Three Phase SPD] |
| 62 | Supplying & Fixing of Maxi Trunking & Fittings from High Impuct unplasticised polyvinyl chloride UPVC grade as per IS 14927 Part 2 and BS : EN 50085 - 2 -1 ( Precision / AKG make ) on wall / ceiling incl necy. PVC fittings etc. and Product code PT 100100 of 100 mm x 100 mm in size also mending good the damages to original finish as per direction of EIC. [NS] |
| 63 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS. |
| 64 | 4x(10 sqmm) + 2x(6 sqmm) as ECC [ 1(d1) / E- 9 ] [Lift+UPS+SPD] |
| 65 | Supply & Fuxing of 440V, Type-2, 3P+N, SPDs (Surge Protection Devices) for Protection against indirect lightning and switching surges having surge current rating 40 KA incl. making necy. Connection as per direction of EIC. |
| 66 | Dismantling Work of New CCB Building |
| 67 | Lowering of existing single/twing light fittings and removing the existing L-clamp by CO's own manpower & tools as per direction of EIC. |
| 68 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [17/C-2] |
| 69 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS. [Make: Polycab/Havells/RR] |
| 70 | 3x1.5 Sqmm [1(b)/E-9] |
| 71 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works as per GS. |
| 72 | 20mm Size [7(a)/E-16] |
| 73 | Supply & Fixing of 2/3 Way PVC Circular box as per direction of EIC. |
| 74 | Supply & Fixing of 3 Way PVC Ceilling rose on existing circular box as per direction of EIC. |
| 75 | SUB -STAION -WORK |
| 76 | Supply & Deliver of 1.1KV 4 C x 300 sq mm XLPE Armoured Al. cable as directed by EIC. ( Make - Gloster / Polycab / Havells / RR Kabel / PWD Appvd ).( DG AMF Panel to DG ) [ 3 RUN ] |
| 77 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the GI Conduit Pipe pipe as per GS. [Make: Polycab/Havells/RR] |
| 78 | 4 x 400 Sqmm [NS] [DG AMF Panel to Change Over Switch ] |
| 79 | Supplying & fixing of hanger on wall ( T Shape ) for laying of LT cable with proper arrangement appx 15'' long ,apppx 12\\" height with 2 nos x chera angle appx each length 3\\" to 3.5\\" as per appvd drawing and the cable hanger made with MS angle 40 mm x 40 mm x 5 mm incl. painting with 2 coats of RO primer with one coat of appvd. Paint with grouting on wall with cement morter as per requirement at site incl scaffolding arrangement if reqd. as per direction of EIC |
| 80 | Laying of 4 C x 300 sq mm cable through existing cable hanger as per direction of EIC. |
| 81 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below: |
| 82 | 4 Core x 300 sq mm [ 7C/ F-4] |
| 83 | 4 x 400 Sqmm |
| 84 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 85 | 4 Core x 300 sq mm [ 8B/ F-5] |
| 86 | 4 x 400 Sqmm |
| 87 | Supplying and fixing 415V, 800A TPN SFU with sheet steel enclosure on suitable size angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating as per direction of EIC.(Make-L&K/ABB) |
| 88 | Supplying and fixing 415V, 800A TPN on load front operated Changeover switch with Sheet Steel enclosure on sutiable size angle iron frame on wall with nuts bolts etc as per direction of EIC..(Make-L&K/ABB) |
| 89 | Supplying and Drawing 1.1KV single core stranded 'FR'PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC ) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required |
| 90 | 2 x 6 sq mm + 2 x 4 sq mm [1Y/E9] [For 6 KV UPS Input Output] |
| 91 | SITC of 230V, 6 KVA Single phase to single phase true online UPS (Make-numeric by legrand or equivelent model), input voltage range 160-300V AC, output voltage 220/230V +/- 1%, powerfactor 0.99, with isolation transformer and 20 nos. 12 V, 42 AH Battery for providing 60 mins. battery back up incl. S&F of iron rack for battery & interconnection cable as per direction of EIC. |
| 92 | Compound Light/Street Light Arrangement |
| 93 | Supply & delivery of hot dip galvanized (As per IS: 2629/IS 2633/IS 4759 & with its latest amendment) 9 mtrs length decorative octagonal pole made of HT steel(Sheet thickness-3 mm) conforming to grade S355JO/JR of BSEN 10025 along with a welded base plate of required size stud of termination of 4 core 10/16/25/35 sq.mm al (Ar) cable incl S&F 1 no 6 amp SP MCB (c-series) with 4 way stud for each outgoing circuit to the fittings with proper pad locking arrangement for the pole. [Top dia (A/F)-70 mm Bottom dia (A/F)- 175 mm] Base plate size: 275 mm (L)x 275 mm(W) x 16 mm(Thickness). Foundation Bolt-4-M24 x 750 mm(L) x 4 nos 'J' type bolts (Make-Transrail / Valmont/Lysaght/Bajaj) (T.C & G.C must be submitted to EIC before execution) N.B: Specification of poles may be changed as per manufacturer standard, the agency must approve the material from the EIC before execution and should visit the site physically. |
| 94 | Errection of the following decorative octagonal pole by designing & casting RCC(M-16)foundation of suitable size as specified below considaring the safe soil bearing capacity at site as 10 T/sq m incl excavation of earth providing cutting bending and placing in position reinforcement as per drawing & providing pipe for cable entry & exit as per required & providing and fixing of 4 nos foundation bolt (J type) as specification below & as per drawing on ground surface incl back filling cleaning extra earth---up to 9 mtr. [Foundation size-500mm(L)x500mm(W)x1200mm(H), J Bolt size-M24 x 750mm [L].For 9 mtr Octagonal Pole. N.B : Specification of poles may be changed as per manufacturer standard, the agency must approve the foundation design from the EIC before execution and should visit the site physically. |
| 95 | SITC of single dip galvanized steel overhang bracket (Swan Neck Type/As per direction of the EIC) at the top of the pole having 1.5 M length complete with all fixing arrangements as required including painting & S & F pole cap. Single Arm |
| 96 | Supply & Fixing 240V 120W LED street Light having luminious effeciency of 110-120lm/w incl. IP66 protection complete with all accessories as per direction of EIC. (Make: Phillips, Model.- BRP503 LED156 CW R5C PSU S1 V1/ Bajaj/Crompton) [NS] [Analysis Attached] [With 5 years on site warrenty] |
| 97 | S & F 3 phase Single Timer box Made of 16 SWG MS sheet (size approx– 450 X 400 X 175mm) with powder coated synthetic paint incl. hinged type MS door , inter locking system consisting the following materials : 1) S & F 24 Hr. timer (GIC-67DDT0/Legrand) – 1 no.2) S & F 415 Volt 40A 3P contactor [Make: Legrand, Model.- 416139] – 1 no.3) 6 amp auto mannual toggle switch – 1 no. (L&T)4) Indicating lamp B & G (L&T) – 2 nos.5) 415V, 40A, 10KA, Cseries FP MCB(legrand/L&T) on din rail for incoming-1 no6) 100A capacity 4W Brass stud type connector on FRP chair for I/C & 2 nos. O/G- 3 nos All control circuit wiring would be made by 1x1.5 sqmm stranded Cu wire(FRLS) and the I/G & O/G circuit with 1x6sqmm copper wire maintaining colour code incl taping, socketing to complete the work. The box should be fixed on wall with suitable size of flush nut and necy. Connection. [NS] |
| 98 | Supply of XLPE Insulated & Sheathed multi stranded Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make:- Polycab/Havells/RR/Gloster] |
| 99 | 4 Core 10 Sqmm [For Street Light + Glowsign Power] |
| 100 | Laying of one No. cable in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. upto 35 sqmm. [F2/1A] |
| 101 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below as per GS. |
| 102 | 4 Core 10 Sqmm [7©/F-4] |
| 103 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials as per GS. |
| 104 | 4 Core 10 Sqmm [8(b)/F-5] |
| 105 | S&L of 1.1 KV grade 3 X 1.5 Sq mm FR single core multi stranded copper wire for connection from loop box to fittings through 13 mm dia polythene |
| 106 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 40 mm dia [F6/11C] |
| 107 | Excavation of morrum soil for installation of earth electrode and filling & ramming for morrum soil [G1/1B] |
| 108 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level & restoring surface duly rammed (:For Morrum Soil ISI-Medium GI pipe as to GS. [G1/2A] |
| 109 | GLOW SIGN |
| 110 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish as per GS.[Switch Make: Legrand, Model: Myrius/ Schneider Model- Miluz Lara/ Honeywell Model: Orna][Wire Make: Polycab/ Havells/RR] |
| 111 | Average run 9 mtr [1(iv)/E-20] |
| 112 | Supply & Fixing of of LED illuminated sign board fabricated by 20'(L)x4'(H)x4\\"(W) ACP box supported with 50 x 50 x 5 mm M.S. MS angle structure all around with 25mm x25mmx 1.5 mm Al. edge angle for all edges.The front side of the board will be fabricated with hinges and arrangement in such a way so that it can be opened for maintenance purpose, including mechanical locking arrangement .The 3 mm ACP facial (Blue colour) should be provided in all side anf front side of the ACP provided with laser cutting and back portion of the ACP board should be pasted with 2mm thick white Acrylic Sheet of same size as ACP facial as per the direction of EIC.The sign board should be illuminated with 3 module LED strip 7 Suitable size SMPS. Distribution wiring for power supply to LED strip to be done by 3x1.5 Sqmm wire. Back side of the of the board should be covered with 3mm Thick ACP sheet to protect rain water. The matter to be displayed will be finalised by authority and to be given later.This fabricated display structure is to be fixed on the direction on the wall by supply & fixing of suitable size of angle iron frame as per direction of EIC. [Matter has to be approve from the competent authorty in prior] |
| 113 | Supply & Fixing of of LED illuminated sign board fabricated by 3'(L)x2'(H)x3\\"(W) ACP box supported with 25x25x3 mm M.S. MS angle structure all around with 12mm x12mm x 1.2 mm Al. edge angle for all edges. The whole stracture has been painted with 1 coat od primer and two coat of paint.The front side of the board will be fabricated with hinges and arrangement in such a way so that it can be opened for maintenance purpose, including mechanical locking arrangement .The 3 mm ACP facial (Blue colour) should be provided in all side anf front side of the ACP provided with laser cutting and back portion of the ACP board should be pasted with 2mm thick white Acrylic Sheet of same size as ACP facial as per the direction of EIC.The sign board should be illuminated with 3 module LED strip 7 Suitable size SMPS. Distribution wiring for power supply to LED strip to be done by 3x1.5 Sqmm wire. Back side of the of the board should be covered with 3mm Thick ACP sheet to protect rain water. The matter to be displayed will be finalised by authority and to be given later.This fabricated display structure is to be fixed on the direction on the wall by supply & fixing of suitable size of angle iron frame as per direction of EIC. [Matter has be approve from the competent authorty in prior] |
| 114 | SITC of Green Model Cooler cum Purifier ( Intregrated inbuilt with cooler and purifier in a single unit ) 80 ltrs storage capacity. with external diamensions 640 mm x 450 mm x 1350 mm ( ± 10% ) , (W x D x H ) , Operating Power Supply - 230 ± 10 % v AC, 50 Hz, running current in amps (max)-3.2 ± 10 %, Power in watts-625 ± 10 %,Water storage tankc capacity-80 ltr,capacity with comfort level water outlet temperature at 17 deg c-60 lph,refrigent-r134 ( Green Gas ) 22, Compressor make- Emerson,thermal insulation for storage tank- puf,total no. of faucets-02 (1 normal+1 cold), recommendd max water flow rate through the faucets in lpm-1.5,no of stages for filter cum purifier-03,no of purifier circuits-03,purifier fault indication (buzzer),visual control (leds),water flow swith,10 minutes UV auto shut off,storge tank material & body material- front SS 304 & rest pre coated steel,working with -0.4 kg/cc min. water input pressure and 2 kg/cc of max. water input pressure, integrated water cooler cum purifier with end point/last point purification technology, including one year warranty as per condition. make EUREKA FORBES /KENT / UNILEVER. |
| 115 | Supply and Fixing of Inline sediment filter- size 20 inch, suitable for 80 Ltr. Capacity Water Cooler Cum Purifier 60 ltr and above purification capacity/ hour with Made of spun or high quality paper. |
| 116 | Supplying , Deliverying , fabrication of Water Purifier Stands with MS Angle.The Stands is constructed by MS angle iron frame of 4 nos 50 x 50 x 6 mm size approx length (4 Nos 800 mm each ) and hight 4 x 600 mm each (leg) .The complete stands by proper placing and welding by MS angle iron frame with cutting ,welding , grinding and finished by Expert welder with expert technician and painting the Stands by two coats of RO primer after scrapping by emery paper for smooth finish and complete the installation as per direction of EIC. |
| 117 | Supply & Fixing 240 V, 1nos 6A & 1nos 20A plug socket with separate 1nos 6A & 1 nos 20A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240 x 200 x 65 mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 118 | Distribution wiring in 1.1 KV single core stranded 'FRLS' PVC insulated & unsheathed copper wire (Finolex / Havells/ KEI / Gloster /approved by EIC) in suitable size (32/25 /19 mm ) dia 3mm thick Poly. Pipe conceal in wall incl. necy. fittings as required as per G S |
| 119 | 2 x 2.5 sq mm + 1 x 1.5 sq mm (Power plug) |
| 120 | CCB UPS ROOM AC |
| 121 | SITC of 24000 BTU/Hr. & 700 CFM capacity capacity non-inverter type ceilling ceilling suspended ductable Air-conditioner machine fitted suitable for Refrigerant-R410A/R-32 having PCB in metal enclosure with installation kit. The outdoor unit fixed on wall by S&F of bracket and indoor unit fixed on ceilling using sutible size tie rod incl. charging the refregerent as per direction of EIC. (Make: Mitsubishi Electric/Fujitsu-General /Mitshubishi Heavy Industries as approve by the E.I.C.) |
| 122 | Supply & Laying Extra Add-on items- 5/8\\"(for suction) & 1/4\\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation incl. fixing arrangement and wrapping insulation of aerotape complete in all respect for 2/3 TR A.C. Machine. as per direction of E.I.C. |
| 123 | Supply and fixing of PVC insulated stranded copper cable for Working Voltage up to 1100 Volts of following sizes as per direction of EIC. [Make- Polycab/ Havells/RR] |
| 124 | 3 Core 4 sq. mm. |
| 125 | 4 Core 2.5 sq. mm. |
| 126 | S&F of 25mm Dia PVC drain pipe for AC drain pipe on wall, ceiling with saddles and other accessories as required and mending good damages to building works. |
| 127 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. as per GS. [5(a)/E-17] |
| 128 | Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections as per GS. [5(b)/E-17] |
| 129 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. as per GS. [17/E-19] |
| 130 | S&F of 250V dual timer DB (equivalent to 8 way SPNDB in size) with double door sheet steel enclosure, neutral bar, din rail, with lP43 protection comprises with 32A DP MCB(C-curve 10ka) and 1 no 24 hr digital time switch and 2 nos. 25A modular type power contactor complete with internal wiring with suitable size of copper wire includ LED indicator and earthing attachment as per direction of EIC. [NS] [Analysis Attached] |
| 131 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish as per GS.[Switch Make: Legrand, Model: Myrius/ Schneider Model- Miluz Lara/ Honeywell Model: Orna][Wire Make: Polycab/ Havells/RR] |
| 132 | Average run 9 mtr [1(iv)/E-20] |
| 133 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish as per GS.[Switch Make: Legrand, Model: Myrius/ Schneider Model- Miluz Lara/ Honeywell Model: Orna][Wire Make: Polycab/ Havells/RR] |
| 134 | On Board [3(i)/E-20] |
| 135 | Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works as per GS.[Switch Make: Legrand, Model: Myrius/ Schneider Model- Miluz Lara/ Honeywell Model: Orna] |
| 136 | 8 Module [1(c)/E-17] |
| 137 | Supply & Fixing of 1 module blanking Plate as per direction of EIC. |
| 138 | Supply & Fixing 240 V 16 A modular key type switch (Brand approved by EIC) on GI Modular type switch board having top cover plate and making necessary connections as required as per GS. [3(b)/E-17][Switch Make: Legrand, Model: Myrius/ Schneider Model- Miluz Lara/ Honeywell Model: Orna] |
| 139 | Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. as per GS. [4(b)/E-17][Switch Make: Legrand, Model: Myrius/ Schneider Model- Miluz Lara/ Honeywell Model: Orna] |
| 140 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. as per GS. [5(a)/E-17] |
| 141 | Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections as per GS. [5(b)/E-17] |
| 142 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. as per GS. [17/E-19] |
| 143 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS. ( Make - Legrand/Schneider/Seimens ) |
| 144 | 8 Way [14/D-10] |
| 145 | Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per GS. ( Make - Legrand/Schneider/Seimens ) |
| 146 | 4 way [11/D-9] |
| 147 | Supplying and fixing MCCB SS enclosure with IP- 20/30 protection, pwder coated provision for housing Four pole (4P) MCCB, concealed in wall after cutting the wall & mending good the damages to original finish / on flat iron frame incl. painting, connection & provision for earthing attachment as per GS. [12/D-9] ( Make - Legrand/Schneider/Seimens ) |
| 148 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS ( Make - Legrand/Schneider/Seimens ) |
| 149 | 63A FP [6(a)/D-5] |
| 150 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA in existing Vertical DBs including necessary connection as per GS ( Make - Legrand/Schneider/Seimens ) |
| 151 | 160A [10/D-8] |
| 152 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS. ( Make - Legrand/Schneider/Seimens ) |
| 153 | 6-32A SP [7/D-6] |
| 154 | Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991)315 A 415V CU Bar, Size: 4 x 40x5mm (Box Size: 500x500mm) [19(b)/D-13] |
| 155 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS. [Make: Polycab/Havells/RR] |
| 156 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC [1(s)/E-9] |
| 157 | 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC [1(v)/E-9] |
| 158 | 4x35 Sqmm [NS] |
| 159 | Cutting Channel of size (40 mm x 40 mm)/(43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19/25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles as per GS. |
| 160 | 19 mm dia 3 mm thick [ 6(a)/ E- 3 ] |
| 161 | 25 mm dia 3 mm thick [ 7 (a)/ E- 3 ] |
| 162 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works as per GS. |
| 163 | 20mm Size [7(a)/E-16] |
| 164 | 25mm Size [7(b)/E-16] |
| 165 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works |
| 166 | 415 mm x 240 mm x 65 mm [11(g)/E-4] |
| 167 | 200 mm x 150 mm x 65 mm [11(d)/E-4] |
| 168 | Supply & Fixing bakelite / perspex top cover on existing Inspection board by Brass screws as per GS. |
| 169 | 415 mm x 240 mm x 65 mm [13(g)/E-5] |
| 170 | 200 mm x 150 mm x 65 mm [13(d)/E-5] |
| 171 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 172 | 1.5 Sqmm [NS] |
| 173 | 2.5 Sqmm [9(i)/F-5] |
| 174 | 4.0 Sqmm [9(ii)/F-5] |
| 175 | 35 Sqmm [NS] |
| 176 | Supply of XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make:- Polycab/Havells/RR/Gloster] |
| 177 | 4 Core 35 Sqmm [For PDB from LT Panel] |
| 178 | 4 Core 120 Sqmm [For S/Stn LT Panel to UPS Room] [UPS I/P O/G Cable] |
| 179 | 4 Core 185 Sqmm [For S/Stn LT Panel to UPS Room for 2 Nos. 60 KVA UPS] [UPS I/P O/G Cable] |
| 180 | Laying of one cable through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand as per GS. |
| 181 | 4 Core 120 Sqmm [4(a)/F-3] |
| 182 | 4 Core 185 Sqmm [4(b)/F-3] |
| 183 | Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting as per GS. |
| 184 | 4 Core 35 sqmm [2(c)/F-1] |
| 185 | Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting as per GS. |
| 186 | 4 Core 120 Sqmm [2(e)/F-1] |
| 187 | 4 Core 185 Sqmm [NS] |
| 188 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below as per GS. |
| 189 | 4 core 35 sqmm [7(C)/F-4] |
| 190 | 4 core 120 sqmm [7(C)/F-4] |
| 191 | 4 core 185 sqmm [7(C)/F-4] |
| 192 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials as per GS. |
| 193 | 4 core 35 sqmm cable [8(b)/F-5] |
| 194 | 4 core 120 sqmm cable [8(b)/F-5] |
| 195 | 4 core 185 sqmm cable [8(b)/F-5] |
| 196 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required as per GS. |
| 197 | 80 mm Dia |
| 198 | Supplying, fabrication & fixing M.S Angle of 6 mm thick of size (50 mm x 50 mm x 6 mm) and for laying of cable incl. drilling 3 nos holes in side of MS angle including fixing of the angle in wall by 3 nos. bullet type fastner.The entire structure should be painted with 1 coat of primer and 2 coat paint as per direction of EIC. |
| 199 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter as per GS. |
| 200 | 45 cm (18\\") [28(b)/C-4] |
| 201 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long)as per GS |
| 202 | (18\\") [ 33/D-14 ] |
| 203 | Supply of 230V , 50 Hz Heavy Duty Exhaust fans of following diameter complete with all accessories as per direction of EIC. ( Make -EPC Electrical Privet Limited ) |
| 204 | 18\\"( 450mm ) Speed 1420 RPM [NS] [Analysis Attached] |
| 205 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connecte with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length as per GS [17/C-2] |
| 206 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. as per G.S. [16/C-2] |
| 207 | Supplying and delivery of LED Industrial Batten light made of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing with Aluminium end-cap) voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range 0o to 40o C, internal surge protection of 2.5 KV(internal) with Short & Open circuit protection , THD < 10% , P. F.≥0.9, IP20, CRI >80, and minimum 40000 Burning Hours (Life projection shall be calculated as per TM-21 methodology), CCT 5700°K /6500°K, and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, with Minimum 5 year OEM warranty. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. (System lumen efficacy ≥115 lm/Watt) |
| 208 | Single fittings along with S/F of 1 no. 18-20 W LED lamp as per specification |
| 209 | Twin fittings along with S/F of 2 no. 18-20 W LED lamps as per specification |
| 210 | S&F of 10/12W Bulkhead light fittings having polycarbonate body and IP 65 Protection as fixed directly wall or ceiling as per direction of EIC. [Make: Magik, Model.- HWAR012C or equivelent model of Surya/Orient] |
| 211 | S & F240V, 16A, 24 Hr. digital time switch (Make: GIC, Model-67DDT0 of Equivelent model of Legrand) as per direction of EIC. |
| 212 | S&F of 250V Single timer DB (equivalent to 8 way SPNDB in size) with double door sheet steel enclosure, neutral bar, din rail, with lP43 protection comprises with 32A DP MCB(C-curve 10ka) and 1 no 24 hr digital time switch and 1 nos. 25A modular type power contactor complete with internal wiring with suitable size of copper wire includ LED indicator and earthing attachment as per direction of EIC. [NS] [Analysis Attached] |
| 213 | Supplying and fixing 415V, TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. As per GS. |
| 214 | 200A [4(a)/D-3] |
| 215 | 160A [4(a)/D-3] |
| 216 | 63A [4(a)/D-3] |
| 217 | Supplying and fixing 415V, TPN on load front perated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc as per direction of EIC. [Make: L&T, Seimens, Schneider] |
| 218 | 160A [3(a)/D-2] |
| 219 | 250A [3(a)/D-2] |
| 220 | Supplying & fixing earth busbar including Connecting the equipments of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall as per GS [4(a)/G-2 ] |
| 221 | Excavation of soil for installation of Earth Electrode and filling & ramming.For Morrum Soil [ 1(b)/G-1 ] |
| 222 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe [ 2(a)/G-1 ] |
| 223 | Extra for providing masonry enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width duly plastered with cement mortar (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe [ 3(a)/G-2 ] |
| 224 | Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. as per GS. [5(d)/G-3] |
| 225 | Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on thetop of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode as per GS. [7/G-3] |
| 226 | Supplying & fixing earth busbar including Connecting the equipments of Copper 25 mm x 6 mm on wall as per direction of EIC. |
| 227 | SITC OF FIRE DETECTION & ALAMING SYSTEM |
| 228 | Supply, Installation, Testing & Commissioning of Microprocessor controlled. IP Addressable Multi-sensor detector (VDS / UL /ERTL/ LPCB / FM approved) with inbuilt optical smoke Sensors and heat detector sensor with inbuilt short circuit fault Isolator as per NFPA style 7 wiring complete with base (Note Detectors without built-in fault isolator is also acceptable Provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. Thedetector should have 360 degree optical view with single/ multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors as per direction of EIC. (Make Esser by Honeywell because existing system has been done by honeywell) |
| 229 | Supply, Installation,Testing & Commisioning of IP Addressable Manual Call Point ( VDS / UL / ERTL / LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required as per direction of EIC. (Make Esser by Honeywell / Secutron / Securiton/Johnson Control/ Cerberus Pro By Siemens /GST / Miacom) |
| 230 | Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter (sound output of minimum 80 db ) cum strobe (strength of iight 10 cd) complete with inbuilt short circuit fault isolator. (VDS / UL / ERTL / LPCB / FM approved) approved as per direction of EIC. (Make Esser by Honeywell / Secutron / Securiton/Johnson Control/ Cerberus Pro By Siemens /GST / Miacom) |
| 231 | Supply, Installation, Testing & Commissioning of Loop Isolator Modules ( VDS / UL /ERTL/ LPCB / FM approved ) Loop Isolator can isolate the shorted circuit from the whole system to ensure normal operation of other devices and locate the devices in fault. After the short circuit fault is cleared, those devices will be re-introduced into the system with degree of protection IP 30 as per direction of EIC. (Make Esser by Honeywell / Secutron / Securiton/Johnson Control/ Cerberus Pro By Siemens /GST / Miacom) |
| 232 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. as per G.S. [16/C-2] |
| 233 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required as per GS. |
| 234 | 2 x 22/0.3 (1.5 sqmm) [1(a)/E-9] |
| 235 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works as per GS. |
| 236 | 20mm size [7(a)/E-16] |
| 237 | Supply & Delivery of Fire shield brand Modular Automatic Clean Agent HFC-236 type Fire Extingusher made of MS body treated against corrosion fitted with heat sensitive glass bulb sprinkler heads (68 degre C / 79 degre C ) pressure indicator ,arrangement for fixing to the ceiling pressurized with nitrogen gas to 15 Kg / cm sq |
| 238 | 5 Kg capacity suitable for covering 13.25 cu. m (465 cu ft) [PMSSY UPS ] |
| 239 | Cleaning, Refilling, Hydro testing of Existing ABC type fire extinguisher of 4 K.G. capacity with change of damaged spares including removing from site & re-fixing after refilling.( refilling of Existing Extinguishers.) |
| 240 | Cleaning, Refilling, Hydro testing of Existing CO2 fire extinguisher of 4 K.G. capacity with change of damaged spares including removing from site & re-fixing after refilling.( refilling of Existing Extinguishers.) |
| 241 | Supply Delivery and installation of ABC Powder type 04 Kg fire extinguishers (stored pressure) HSN code-84241000 conforming to IS:15683 and complete in all respect as per direction of EIC 04 Kg with ISI marked Mono Ammonium Phosphate base ABC power conforming to IS:14609 and pressurized with nitrogen gas. Suitable for operating between (-)30ºC to (+)55ºC. Fire rating -2A & 55B [CCB] |
| 242 | Supply Delivery and installation of ABC Powder type 09 Kg fire extinguishers (stored pressure) HSN code-84241000 conforming to IS:15683 and complete in all respect as per direction of EIC 09 Kg with ISI marked Mono Ammonium Phosphate base ABC power conforming to IS:14609 and pressurized with nitrogen gas. Suitable for operating between (-)30ºC to (+)55ºC. Fire rating -4A & 144B [CCB] |
| 243 | Supply, Delivery and installation of Co2 type fire extinguishers: HSN code-84241000 4.5 Kg capacity with ISI marked Co2 type fire extinguisher squeeze grip type conforming to IS:15683:2006 madefrom seamless cylinder conforming to IS:7285 dulyapproved by Chief controller of explosive, Nagpur, fitted ISI marked controlled valve conforming to IS:3224, high pressure 1 mtr. long discharge hose and horn complete with initial gas charged with carrying handle and wall mounting bracketoperating between (-)30ºC to (+)55ºC. Fire rating -21 B. |
| 244 | Supply, Delivery and installation of Co2 type fireextinguishers: HSN code-84241000 22.5 Kg. capacity with 5 mtrs long discharge hose and horn mounted on trolly wheels complete in all respect with ISI marked Co2 type fire extinguisher squeeze grip type conforming to IS:15683:2006 made from seamless cylinder conforming to IS:7285 duly approved by Chief controller of explosive, Nagpur, fitted with ISImarked controlled valve conforming to IS:3224, Fire Rating 89B |
| 245 | SITC OF AC MACHINE |
| 246 | SITC of 24000 BTU/Hr. & 700 CFM capacity capacity non-inverter type ceilling ceilling suspended ductable Air-conditioner machine fitted suitable for Refrigerant-R410A/R-32 having PCB in metal enclosure with installation kit. The outdoor unit fixed on wall by S&F of bracket and indoor unit fixed on ceilling using sutible size tie rod incl. charging the refregerent as per direction of EIC. (Make: Mitsubishi Electric/Fujitshu-General /Mitshubishi Heavy Industries as approve by the E.I.C.) |
| 247 | Supply & Laying Extra Add-on items- 5/8\\"(for suction) & 1/4\\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation incl. fixing arrangement and wrapping insulation of aerotape complete in all respect for 2/3 TR A.C. Machine. as per direction of E.I.C. |
| 248 | Supply and fixing of PVC insulated stranded copper cable for Working Voltage up to 1100 Volts of following sizes as per direction of EIC. [Make- Polycab/ Havells/RR] |
| 249 | 3 Core 4 sq. mm. |
| 250 | 4 Core 2.5 sq. mm. |
| 251 | S&F of 25mm Dia PVC drain pipe for AC drain pipe on wall, ceiling with saddles and other accessories as required and mending good damages to building works |
| 252 | ARRANGEMENT FOR HUME PIPE |
| 253 | Constructing Inspection Providing massonery chamber /box type 250 mm thick 1st class brick work (1:4) in all sides over a layer of jhama brick soling and 150 mm thick cement concrete with stone chips (1:3:6) including necessary earth work, fitting and fixing approved type S.W. master trap, constructing masonry invert with cement concrete (1:1.5:3) with stone chips, plastering inside and outside (outside upto 300mm below G.L.) with 20 mm thick cement plastering (1:4) and neat cement punning,including with R.C.C. slab of 100 mm thick with cement concrete (1:1.5:3) withstone chips including necessary reinforcement (upto 1%) and shuttering and necessary corbelling brick work (1:4) with suitable size appx 1200 mm x 1200 mm (inside) chamber and appx 900 mm depth (below the Ground level ) as per requirement at the condition of site , approved make With Pakur variety at the time of construction the Inspection chamber with the arrangement of fixing the Hume on both side wall of the chamber for easy laying of various cables and fill up the chamber with loose sand as per requirement / required and direction of EIC |
| 254 | Supply & Fixing and placing special type RCC concreate slab of size 450 mm x 450 mm x 100 mm thick made with 8 mm dia TMT Rod with sand ,cement & stone chips motter by casting arrangement incl necessary matching & lifting arrangement as per direction of E.I.C |
| 255 | Supply & Laying of 250 mm dia Hume pipe PWD appvd make with appx 25 mm thk reinforced cement concrete pipe NP3/NP2 with with coller etc spigot socket for culverts on first class bedding of granular material in single row including fixing with cement mortar 1:2 to comp the job for laying of Cable as per requirement & direction of EIC |
| 256 | Charges for metal road cutting appx.800 mm width x 300 mm depth incl. refilling and mending the dameges as per direction of E.I.C. |
| 257 | Charges for normal road soil cutting appx. 800 mm width x750 mm depth incl. refilling and mending the dameges as per direction of E.I.C. |
| 258 | Supply & Laying of 42/50 mm dia ISI mark HDPE Pipe with all accessories as required for the entire system with all OEM accessories as per site condition. |
| 259 | Add GST @ 18% on Rs.88,32,151.00 i.e. total amount over item 1 to 156 |
| 260 | Add L.W.Cess @ 1% on Rs.1,04,21,939.18 i.e. total amount over item 1 to 157 Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail