| 1 | Excavation in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter deep and getting out hard and dense soil complete all as specified and directed. |
| 2 | M&L for dry sand filling in cable trenches for protection of cables with two layers(ie. 8mm and 15mm thick) below and above cable and punned down to speicified thickness complete all as specified and as directed.Note: Punned down thickness shall only be measured for payment. |
| 3 | Returning, filling in, including spreading, levelling watering and well ramming in layers n.exc 25cm in Soft/loose soil complete all as specified and directed. |
| 4 | Removing excavated material (soils) distance n.exc 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 5 | Supplying & laying factory made unreinforced Precast concrete cover of class LV, type 1, flat, size 250 mm x 150 mm x40mm for protection for cable all as specified. |
| 6 | Supply and laying of GI tubing light grade for cable protection of size 40 mm dia complete all as specified and directed. |
| 7 | Supply, laying & testing of XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables(heavy duty) with stranded aluminium conductor, 1100 volts, grade cross setional area 50 sq mm, 4 core complete all as specified and as directed. |
| 8 | Material and labour for earthing complete with galvanized earth plate electrode in 60 cm x 60 cmx 6 mm thick buried directly in ground vertically at a depth not less than 2.25 meter below ground level with top edge of earth plate at depth not less than 1.5 mtr below ground level connecting to and including GI wire 4.00 mm dia mm by means of GI bolts, nuts, check nuts and washer light grade, 15 mm dia GI protection pipe and connected to equipment, GI pipe medium grade 20 mm dia for watering and including funnel wire mesh, RCC pit cover and PCC 1:3:6 type C-2 including Rocksalt, charcoal, excavation and earth work disposal of surplus soil shown as plate No 3 of SSR Part - I 2009 and all as specified complete.Note : The unit rate quoted shall deemed to have included for GI protection pipe, GI earth wire up to 7.5 mtr, GI water pipe, wire mesh , funnel , excavation, RCC pit cover complete. |
| 9 | Supply, laying & testing of XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables(heavy duty) with stranded aluminium conductor, 1100 volts, grade cross setional area 10 sq mm, 4 core complete all as specified and as directed. |
| 10 | Material and labour for Industrial plug and socket panel with 32A MCB, 3 phase complete all as specified and as directed. |
| 11 | Supply and fixing 415V 10KA 'B' curve miniature circuit breaker(MCB) of four poles and current carrying capacity TPN 40 to 100 AMP in the DB complete with connection testing and commissioning all as specified and as directed. |
| 12 | Supply and fixing sheet metal enclosure for single door DB made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted TP & N 8 ways, 415volts, ISI marked, 200 Amps bus bar stove enameled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed. Please Enable Macros to View BoQ information |
| 13 | Supply and fixing sheet metal enclosure for single door DB made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted TP & N 8 ways, 415volts, ISI marked, 200 Amps bus bar stove enameled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed. Please Enable Macros to View BoQ information |