| 1 | Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc, complete all as specified and directed. Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and protection cover/Bricks . |
| 2 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed. |
| 3 | Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point, complete all as specified and directed. |
| 4 | Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 120 mm outer diameter and 103.5 mm inner Diameter with IS 16285(part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed. |
| 5 | Supply, laying & testing HT 11 KV cable XLPE insulated, screened PVC bedded galvanised steel strip armoured HT electric power cable (heavy duty) 11000 volts grade with aluminum conductor 11 KV (E) grade, cross sectional area 95 Sqmm 3 core as per IS-7098 suitable for earth system laid in trenches including taking out unserviceable /brunt HT cable of any type /rating, complete all as specified and as directed. |
| 6 | Supply, laying & testing HT 11 KV cable XLPE insulated, screened PVC bedded galvanised steel strip armoured HT electric power cable (heavy duty) 11000 volts grade with aluminum conductor 11 KV (E) grade, cross sectional area 120 Sqmm 3 core as per IS-7098 suitable for earth system laid in trenches including taking out unserviceable /brunt HT cable of any type /rating, complete all as specified and as directed. |
| 7 | Supply, laying & testing HT 11 KV cable XLPE insulated, screened PVC bedded galvanised steel strip armoured HT electric power cable (heavy duty) 11000 volts grade with aluminum conductor11 KV (E) grade, cross sectional area 150 Sqmm 3 core as per IS-7098 suitable for earth system laid in trenches including taking out unserviceable /brunt HT cable of any type /rating, complete all as specified and as direcetd. |
| 8 | Supply, laying & testing HT 11 KV cable XLPE insulated, screened PVC bedded galvanised steel strip armoured HT electric power cable (heavy duty) 11000 volts grade with aluminum conductor11 KV (E) grade, cross sectional area 185 Sqmm 3 core as per IS-7098 suitable for earth system laid in trenches including taking out unserviceable /brunt HT cable of any type /rating, complete all as specified and as direcetd. |
| 9 | Disconnecting and taking out old Unserviceable HT joint and Supply & fixing , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for End joint (Outdoor termination), heat shrinkable type complete with all jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size upto 95 Sq mm complete all as specified and directed. |
| 10 | Disconnecting and taking out old Unserviceable HT joint and Supply & fixing , jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for End joint (Outdoor termination), heat shrinkable type complete with all jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size upto 120 to 185 Sq mm complete all as specified and directed. |
| 11 | Disconnecting and taking out old unserviceable HT joint and Supply & fixing only, jointing and testing cable jointing kit of 11 KV (Earthed) grade cable for straight through, cold shrinkable type complete with all jointing material and accessories suitable for 50 to 185 Sqmm 3 core XLPE armoured aluminium conductor cable of any sizes and type including excavation, returning and filling upto 10 mtrs, complete all as specified and directed. |
| 12 | Material and labour for testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 11 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed.Notes : (i) All T&P and other accessories required for checking and finding of fault in cable shall be provided by the Contractor (ii) Charges/rent of the fault locating mobile machine, operator, engineer, electricians etc shall be deemed to included rate quoted by Contractor. (iii) Checking and finding fault upto 03 places of same route of the cable will be considered as one Job. |
| 13 | Supply and fixing in replacement including commissioning & testing of HT lightening arrestor expulsion type complete with all fitting transmission class, discharge capacity 65 Kilo Amps current rating 10 KA suitable for 11000 Volts & making necessary connections complete including taking down of existing lightening arrestor, complete all as specified and directed. |
| 14 | Supply and fixing in replacement including commissioning & testing of drop out fuse unit suitable for 11000 volt mounted on MS channel complete with post insulator polymer type fuse barrel (fibre glass tube) etc for 3 phase, including taking down of existing drop out fuse unit, complete all as specified and directed. |
| 15 | Supply and fixing in replacement including commissioning & testing of 11 KV Air break gang operated triple pole switch for current rating upto 200 amps, mechanically operated mounted on polymer insulator and steel frame outdoor type suitable for vertical installation single brake provided with locking arrangement, consisting of MS channel , HT post type insulator, copper complete including taking down of existing unserviceable air break switch, complete all as specified and as directed. |
| 16 | S & F in repair HT cable route indicator made out of 45 X 45 X 6 mm MS angle of length 60 cm and bolted with round CI plate of suitable size indicating HT cable 11000 V complete including excavation & grouting by PCC 0.3x0.3x0.3 mtr, complete all as specified and directed. |
| 17 | Supplying and fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for , HT 25x20 cm, complete all as specified and as directed. |
| 18 | Supply and fix in repair Cross arms, bracings, supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and applying two coat of aluminium paint over a coat of red oxide, complete all as specified and as directed. |
| 19 | Supply and fix in repair 11000 volt, Pin type, polymer type, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nuts,150 mm height, 150 mm dia for 11000 volts grade complete all as specified and as directed. |
| 20 | Supply and fix in repair 11000 volt Disc type, polymer insulator 145 mm high and 255 mm dia ball and socket type white / brown \\"two in one series\\" assembly for tension with clamps for conductor suitable for 11000 volt working pressure, complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 21 | Supply and fix in repair 11000 volt Disc type, polymer insulator 145 mm high and 255 mm dia ball and socket type white / brown \\"two in one series\\" assembly for tension with clamps for conductor suitable for 11000 volt working pressure, complete all as specified and as directed. Please Enable Macros to View BoQ information |