| 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required Group C |
| 2 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 4 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (a) 5/6 amp switch |
| 5 | (b) 3 pin 5/6 amp Socket Outlet |
| 6 | (c) 15/16 amp switch |
| 7 | (d) 6 pin 15/16 amp socket outlet |
| 8 | (e) Bell Push |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm |
| 11 | Wiring for curcuit/ submain wiring alongwith earth wire with the following size FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as reqd. 2X2.5 mm+1X2.5 mm earth wire. |
| 12 | Wiring for curcuit/ submain wiring alongwith earth wire with the following size FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as reqd. 2X6 mm+1X6 mm earth wire. |
| 13 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 14 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole with Neutral |
| 17 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 18 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 19 | Providing and laying earth connection from earth electrode with 6SWG dia GI wire in 15mm dia GI pipe with earth electrode as required. |
| 20 | S&L 25mmX5mm GI strip at 0.5 metre below ground as strip earth electrode,including connection/terminating with GI nut,bolts,spring, washer etc as reqd. (Jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at 50mm) |
| 21 | SITC of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal ( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9,Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS :374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 22 | SITC of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/ 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineerin-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). LED Batten light (System lumen efficacy >135 lm/Watt) 18- 22 watt |
| 23 | SITC of power distribution board made out of 1.6 mm sheet steel, epoxy powder coated , specially designed Al bus bar 400A to 630A with heat shrinkcable colour coated sleeves suitable for accommodating MCCBs/MCBs /Isolators as incoming and outgoing as required (without MCCBs/MCBs/Isolators ) complete with digital meter module, including Voltmeter Ammeter with selector switch, CTs control fuse and indicating lights including connections etc. as required ( Conforms to IS:8623) |
| 24 | P/F 4.5 kg Co2 type fire extinguisher sqeeze type, trolly wheel as well mounting type complete in all respect with isi mark i/c fixing arrangement etc. as reqd. |
| 25 | P/F ABC (Aluminium Phosphate) Power type fire extinguisher of 6 kgs capacity complete in all respect with isi mark i/c fixing arrangements etc as reqd. |
| 26 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as reqd. Upto 450 mm sweep |
| 27 | Supplying and fixing modular blanking plate on the existing modular plate & switches excluding modular plate as reqd. |
| 28 | Supplying and fixing following size GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 4 Module |
| 29 | Supplying and fixing following size GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 8 Module |
| 30 | Supplying and fixing following size GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 12 Module |
| 31 | Supply of 15\\" (380mm) sweep 1400 rpm exhaust fan heavy duty complete with shutter, blade etc as reqd. |
| 32 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 A,36KA,FPMCCB |
| 33 | Supplying and fixing call bell/buzzer suitable for single phase, 230 V complete as reqd. Please Enable Macros to View BoQ information |