| 1 | MAIN PANEL: Supply and Installation of wall cum floor mounted L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRC sheet with M.S. angle iron frame (main frame with 50 x 50 x 6mm angle and each compartment with 40 x40x 6 mm angle iron). The base of panel should be made with 75 mm x 40mm x 4.4 mm M.S. channel . Each compartment will be providing with hylam board at back side. |
| 2 | Incoming Arrangement :A) 415V, 415A TPN Main Switch unit with HRC Fuse (Open Execution Type) ( Make- L&T)- 1 No. |
| 3 | B) Supplying and fixing 415V, 320A TPN on load front operated Changeover switch open execution type in SS enclosure/ cubical with nuts bolts etc (L&T) |
| 4 | Bus Bar Section :500V, 600 Amp capacity 99.9% -99.5% electrolytic tinned 4 bar copper bus bar having size of flat 4 x (2x 40x5) mm mounted on non- hygroscopic porcelain insulator/hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes ( Red , yellow , blue & black) for phases & neutral identification - 1 Set. |
| 5 | Outgoing Arrangement :a) 415V, 250A TPN Main Switch with 3nos. HRC Fuse (Open Execution Type) ( Make- L&T )- 2 Nos., b) 415V, 160A TPN Main Switch unit with 3 Nos. HRC Fuse (Open Execution Type) ( Make- L&T )- 3 Nos. c)415V, 63A TPN Main Switch unit with 3 Nos. HRC Fuse (Open Execution Type)( Make- L&T )- 2 Nos. d) Do-do-240V 40A DPIsolator Unit-1 No (L&T) |
| 6 | Metering Panel :a) 0 - 500 V Digital Voltmeter ( Make- L&T ) with selector switch ( Kayee)- 1 No. |
| 7 | b) 0 - 300A Digital Ammeter ( Make- L&T ) with selector switch ( Kayee)- 1 No. |
| 8 | c) 230V R.Y.B. LED indicator lamp - ( Make- Approved ) - 3 Nos. d ) 415/5 Amp ratio C.T. ( Make- Kappa ) - 3 Nos. , Slide lock fuse - 3 Nos. |
| 9 | Interconnection :All interconnection between incoming main to busbar are to be made with suitable size electrilytic tinned copper bars or equivalent flexible PVC insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and for metering arrangements are to be made by suitable size of copper with proper socketing of the end of each wire leads . |
| 10 | The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating . |
| 11 | Installation :The complete panel board is to be installed on suitable brick padestal incl. net cement finish as directed by the E.I.C. |
| 12 | EMERGENCY PANEL: Supply and Installation of wall cum floor mounted L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRC sheet with M.S. angle iron frame (main frame with 50 x 50 x 6mm angle and each compartment with 40 x40x 6 mm angle iron). The base of panel should be made with 75 mm x 40mm x 4.4 mm M.S. channel . Each compartment will be providing with hylam board at back side. |
| 13 | Incoming Arrangement :A) 415V, 250A TPN Main Switch unit with HRC Fuse (Open Execution Type) ( Make- L&T )- 1 No. |
| 14 | B) Supplying and fixing 415V, 250A TPN on load front operated Changeover switch open execution type in SS enclosure/ cubical with nuts bolts etc (L&T) |
| 15 | Bus Bar Section :500V, 315 Amp capacity 99.9% -99.5% electrolytic tinned 4 bar copper bus bar having size of flat [4 x50x5mm] mounted on non- hygroscopic porcelain insulator/hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes ( Red , yellow , blue & black) for phases & neutral identification - 1 Set. |
| 16 | Outgoing Arrangement :a) 415V, 160A TPN Main Switch with 3nos. HRC Fuse (Open Execution Type) ( Make- L&T )- 1 No., b) 415V, 100A TPN Main Switch unit with 3 Nos. HRC Fuse (Open Execution Type) ( Make- L&T)- 2 Nos. c)415V, 63A TPN Main Switch unit with 3 Nos. HRC Fuse (Open Execution Type) ( Make- L&T)- 3 Nos. d) 40A DP Isolator-1 (L&T) |
| 17 | Metering Panel :a) 0 - 500 V Digital Voltmeter ( Make- approved ) with selector switch ( L&T)- 1 No. |
| 18 | b) 0 - 300A Digital Ammeter ( Make- approved ) with selector switch ( L&T)- 1 No. |
| 19 | c) 230V R.Y.B. LED indicator lamp - ( Make- Approved ) - 3 Nos. d ) 415/5 Amp ratio C.T. ( Make- Kappa ) - 3 Nos. , Slide lock fuse - 3 Nos. |
| 20 | Interconnection :All interconnection between incoming main to busbar are to be made with suitable size electrilytic tinned copper bars or equivalent flexible PVC insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and for metering arrangements are to be made by suitable size of copper with proper socketing of the end of each wire leads . |
| 21 | The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating . |
| 22 | Installation :The complete panel board is to be installed on suitable brick padestal incl. net cement finish as directed by the E.I.C. |
| 23 | Uninstallation of existing old panels after charging all cable to a temporary hired panel as specified in schedule by proper gland and socket. Hand over of the panel to the custody of Superintendent of Baranagar SGH. |
| 24 | Hiring & Installation charges for the following capacity DG sets.a) 160kVA |
| 25 | Fuel Charges of D.G Set for installation of Main panel and Emergency panel at th Hospital |
| 26 | Providing on hire basis following main switches ,change over switch, Power DB , SPN DB etc on suitable angle iron frame incl. provoding interconnection wiring with socketing earthing attachment etc & dismantling at the function (with PWD approved materials).500V, 320 amp TPNIC switch with re-wirable type [for 3 days] |
| 27 | 500V, 400-600 amp 4 nos bus bar with SS enclosure. [for 3 days] |
| 28 | 500V, 250 amp Changeover switch with re-wirable type [for 3 days] |
| 29 | 500V, 200 amp TPN incoming switch with rewirable type [for 3 days] |
| 30 | 500V, 100 amp TPN incoming switch with rewirable type [for 3 days] |
| 31 | 500V, 63 amp TPN incoming switch with rewirable type [for 3 days] |
| 32 | Supply and Fixing 3x 250/5A CT for Ammeter(Make-Kappa) |
| 33 | Changing of 1ph 0-300A Digital ammeter for LT panel. ( L&T) |
| 34 | Changing of 1ph 0-500V for Digital VoltmeterLT panel. (L&T) |
| 35 | Supply and fixing of Indicator lamp of Panel ( Red, Yellow, Blue) |
| 36 | 4 pt Selector Switch for Ampmeter and Voltmeter (Make-L&T) |
| 37 | Supply and fixing 1/2\\" x 1&1/2\\" copper nut-bolts with copper washer. |
| 38 | Supply and fixing 8mm x 1&1/2\\" MS nut-bolts with washer. |
| 39 | Supply and fixing 10mm X 4\\" MS Pin type Fastner. |
| 40 | Supply and fixing 4 terminal porcelain Stud (500A) on cable alley box. (Make -DMC) |
| 41 | S&F and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry.4Core 120Sqmm |
| 42 | 4Core 95Sqmm |
| 43 | 4Core 50Sqmm |
| 44 | 4Core 35Sqmm |
| 45 | 4Core 16Sqmm |
| 46 | 2Core 6Sqmm |
| 47 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. 4Core 120Sqmm |
| 48 | 4Cx95 Sqmm |
| 49 | 4Cx50 Sqmm |
| 50 | 4Core 35Sqmm |
| 51 | 4Cx16 Sqmm |
| 52 | 2Core 6Sqmm |
| 53 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 50Sqmm |
| 54 | 16Sqmm |
| 55 | 10Sqmm |
| 56 | Supply & laying FR-LSH 50 sq.mm. single core flexible copper wire (Make: Finolex/Polycab /RR) |
| 57 | Supply & laying FR-LSH 16 sq.mm. single core flexible copper wire (Make: Finolex/Polycab /RR) |
| 58 | Supply & laying FR-LSH 10 sq.mm. single core flexible copper wire (Make: Finolex/Polycab /RR) |
| 59 | Supplying and fixing 100 A, 415V, TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (L&T/Siemens/ABB) (For Changing Existing old SFU in Panel) |
| 60 | Supplying and fixing 63A, 415V, TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (L&T/Siemens/ABB) . (For Changing Existing old SFU in Panel) |
| 61 | Supplying and fixing 32A, 415V, TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (L&T/Siemens/ABB) . (For Changing Existing old SFU in Panel) |
| 62 | Supplying and fixing 8-way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, with cable-end box at both ends, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of, spiral link, copper wire and neutral link & provision for earthing attachment . Incoming 125A Four pole MCCB-1no, Outgoing 63A TPMCB-8 no.[Make - Legrand/Siemens/ABB] |
| 63 | S&F 415 V, Horizontal type, TPN MCB DB (6-way) with SS enclosure double-door with IP-42/43 protection, with Four Pole Isolators as incomer and SPMCBs ('C' Curve, 10 KA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS.INCOMING-63 A FP Isolator -1 No.OUTGOING-16-32A SPMCB-18 Nos. [Make - Legrand/Siemens/ABB] |
| 64 | S&F 250V, SPN MCBDB (2+14) way with SS enclosure double-door (Ivory White with IP-42/43 protection with DP Isolators as incomer and SPMCBs ('C' Curve, 10kA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS.INCOMING-40 A DP IsolatorOUTGOING-12 Nos. 6-10A SPMCB [Make - Legrand/Siemens/ABB] |
| 65 | Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991) a) 4 No.415V, 315A Cu- Bar [85mm long] Dimension of Cu. bars-4 x 40x5mm Dimension of Sheet Metal Box 500x150mm |
| 66 | Do-Do- b) 4 No.415 V, 200 A Cu- Bar [85mm long] Dimension of Cu. bars-4 x 20x5mm Dimension of Sheet Metal Box 500x150mm |
| 67 | Supply & Delivery of 4 core 50 sqmm 1.1kV grade XLPE A/Al armoured cable as per GS.(Make- RR/Polycab/Gloster) |
| 68 | 4 Core16 Sqmm |
| 69 | Laying of 4 C 50sqm XLPE a/Al cable at an average depth of 100 mm in floor/pavement/wall etc.after cutting floor/ pavement/ wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish. |
| 70 | Laying of 4 C 16sqm XLPE a/Al cable at an average depth of 100 mm in floor/pavement/wall etc.after cutting floor/ pavement/ wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish. |
| 71 | Laying of one No. cable upto 50 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, includin filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. for 4C x25 sqmm cable. |
| 72 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required a) 50mm |
| 73 | Dismantling of Existing old worn out Wiring in ground floor and first floor as per requirement and handover the dismantled materials in the custody of Superintendent ,Baranagar SGH. |
| 74 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex /Polycab/RR) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [Average run 9 mtr] ( Light Pt-( New Fitting -15 Existing fitting- 20) , fan -Existing-20, New-17 Exhaust Existing-3) |
| 75 | Supply and delivery of Single LED Fitting (20Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories and 1 nos LED Tube[Make: Philips(TMC 502 P 1xT-LED 22W P3241,Essential LEDTube 1200mm 20W865 T8 IND I – 2100lm), Havells, Bajaj, CG, or as per EIC] |
| 76 | Supply and delivery of Twin LED Fitting (20Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories and 2 nos LED Tube [Make: Philips(TMC 502 P 2xT-LED 22W P3241,Essential LEDTube 1200mm 20W865 T8 IND I – 2100lm-2nos),( Havells, CG, or as per EIC] |
| 77 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length, as per GS. |
| 78 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length., as per GS. |
| 79 | Supply & delivery of 1200mm sweep 230V AC Ceiling fan incl. Blades, canopy etc. with 18\\" down rod (14SWG), Fork (10SWG), Heavy type insulator, 3/8th inch bolt with nut, heavy type split pin etc., as directed by EIC with complete accessories. [Make: Orients(Summer cool Brown), Crompton HS+] |
| 80 | Supply & Fixing Socket type fan regulator (Step type) (Anchor) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. Connections etc. |
| 81 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex/RR/Polycab) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as requireda) 2x6sqmm + 1x4sqmm [HTPNDB to SPNDB] |
| 82 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC |
| 83 | Do - Do - Do - 3x1.5sqmm |
| 84 | Finising the end of above PVC insulated & unsheathed copper wire as per GS 2x6sqmm + 1x4sqmm |
| 85 | Do - Do - Do - 2x2.5sqmm + 1x1.5sqmm |
| 86 | Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite / perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 87 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 88 | Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Anchor) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 89 | Earthing with 50 mm dia GI pipe (ISI-M) 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S&F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground, as per GS. |
| 90 | Excavation of soil for installation of Earth Electrode and filling & ramming, for Soft Soil, as per GS. |
| 91 | S&F earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as reqd., as per GS. |
| 92 | Connecting the equipments to earth busbar including S&F 2x8SWG GI (Hot Dip) wire on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as reqd. & mending good damages as per GS. |
| 93 | Supply & Delivery 120 Watt outdoor type LED Street light fitting with IP-66, individual Secondary Optics Peanut Lens and Separate Toughned Glass Diffuser, Potted Driver with 10KV SPD and minimum efficiency > 110 LPW as directed by EIC. (Crompton: TRP-411-120-57-HL2-GL-NSG or equivelent make of Philips/Wipro). |
| 94 | Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. |
| 95 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint |
| 96 | Wiring by 3x 1.5 sqmm single core PVC insulated copper wire through polythene pipe from loop box to fitting as per GS.[Make-Finolex/Polycab/RR] |
| 97 | Supply & Delivery of 2 core 6 sqmm 1.1kV grade XLPE A/Al armoured cable as per GS.(Make- RR/Polycab/Gloster) |
| 98 | Laying of 2 core 6 sqmm cable on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. |
| 99 | Supplying and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry of 2 Core 6 sqmm XLPE/PVC armoured cable. |
| 100 | Finishing the end of 2 Core 6 sqmm XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. |
| 101 | S&F of 240V double door Timer DB [equivalent of 2+10 SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 240V, 25 A DP MCB , 1 no. 240V, 25A, DP Power Contactor, 1 no. Digital time switch-24 hrs with minimum switching of 15 minutes, 1 no. 240V, 25A SP MCB ('C' Curve 10kA) with inner-outer plate & internal wiring by suitable size of Cu wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement as directed by EIC. |
| 102 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Phinolex/Polycab/RR) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.2x4+1x2.5 sq.mm (AC point) |
| 103 | Supply & Delivery of High-wall Split-type Air-Conditioner having following specification:Cooling Capacity-6.5 kW (Minimum)Minimum ISEER 3.8, BEE level 3-Star(min)[1st July22 to 31st December 2025]IS Compliance-IS-1391(Part-1 & Part-11) with all amendmentRefrigerant R410A/R32Compressor-Rotary/ScrollEvaporator & Condenser Coil - CopperOperating outdoor temperature - 48°C and aboveAir Flow: 800 CFM (Minimum)Power supply -230V, 50Hz (±tolerance asper applicable standard), as directed by EIC.The scope of work is also includes supply and fixing of the following:(i) Necessary refrigeration copper line with nitrile rubber insulation and wrapping tape-3 mtr(ii) Necessary 3/4 core copper cable (FRLS type make: Finolex/RR Kable/Polycab) 3mtr and 230V. 25A, 3pin plug top with indicator (North West).[O. General / Mitsubishi Electric /Daikin/Blue Star/Voltas/ Carrier]. |
| 104 | Supply & Delivery of High-wall Split-type Air-Conditioner having following specification:Cooling Capacity-6.5 kW (Minimum)Minimum ISEER 3.8, BEE level 3-Star(min)[1st July22 to 31st December 2025]IS Compliance-IS-1391(Part-1 & Part-11) with all amendmentRefrigerant R410A/R32Compressor-Rotary/ScrollEvaporator & Condenser Coil - CopperOperating outdoor temperature - 48°C and aboveAir Flow: 800 CFM (Minimum)Power supply -230V, 50Hz (±tolerance asper applicable standard), as directed by EIC.The scope of work is also includes supply and fixing of the following:(i) Necessary refrigeration copper line with nitrile rubber insulation and wrapping tape-3 mtr(ii) Necessary 3/4 core copper cable (FRLS type make: Finolex/RR Kable/Polycab) 3mtr and 230V. 25A, 3pin plug top with indicator (North West).[O. General / Mitsubishi Electric /Daikin/Blue Star/Voltas/ Carrier]. |
| 105 | Installation, Testing & Commissioning of Indoor & Outdoor unit of above Hi wall split AC machine after making hole in wall etc as per Direction of EIC including Supply of required Refrigerant, S&F of necessary suitable fixing arrangement for indoor and outdoor unit as recomended by Manufacturer, laying and making connection of refrigeration pipe, power cable, drain pipe ete and mendingn good the damages as per direction of the EIC. |
| 106 | S & F of additional following items for length exceeding 3 mtr. For complete installation and commissioning of above AC machine.(i) Supply & Fixing of extra refrigerant pipe (as requisite dia) with nitrite rubber insulation and wrapping tape (each mtr Refrigerent pipe will include cost of 1 meter liquid pipe line and 1 mtr gas pipe line of required dia and other accessories as required). |
| 107 | S & F of additional following items for length exceeding 3 mtr. For complete installation and commissioning of above AC machine. 2.5 Sq.mm, 3/4 core copper cable(FRLS type- make : Polycab/Finolex) |
| 108 | Supply and Laying Soft Drawn PVC Drain Pipe 19 mm dia with proper supports & brackets as per direction of EIC.(Make- Suprime/Oriplast) |
| 109 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Legrand Myrius/Honeywell MK), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 110 | Supply & Fixing 240 V, 25 A, Modular type starter (North West) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. Please Enable Macros to View BoQ information |