| 1 | Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5 Mtr (IDU to ODU), copper power cable upto 5.5 Mtr (IDU to ODU), i/c drain pipe of suitable length and size. R-32/R-410/R-407C Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required |
| 2 | 3.8 TR BEE 5 Star Rating |
| 3 | Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). |
| 4 | 2.0 TR with 5 Star BEE Rating |
| 5 | Providing and fixing of readymade MS fabricated and duly painted, wall bracket type stands for mounting the Split A.C. outdoor unit including grouting on the wall and making good the damages to surface complete with rubber vibration pads on outdoor unit bolts etc. complete as required |
| 6 | Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 7 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 8 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 9 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2mm |
| 10 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2mm |
| 11 | SITC of 5 KVA capacity Automatic Line Voltage stablizer copper bound wall mounted having following specifiation with TDR. :-(a) Input Voltage : 170-275 volt(b) Output Voltage : 230 volts (+ 10%) |
| 12 | Wiring for circuit/ submain wiring along with earth wirewith the following sizes of FRLS/HFFR PVC insulatedcopper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 13 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 14 | Supplying & fixing suitable size Gl box wih modular plate and cover in fronton surface or inrecess including oviding and fixing 25 Amodular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 15 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. |
| 16 | For 4 way, Double door TPN MCBDB |
| 17 | Supply, installation, testing, and commissioning of one 63A, 415V, TPN (Three Pole + Neutral) MCB with \\"C\\" Curve tripping characteristics and a 10kA breaking capacity. The unit shall be housed in a factory-fabricated CRCA Sheet Steel Enclosure (powder-coated). The scope includes fixing the enclosure to the wall (surface or flush), internal wiring connections, earthing of the metal box, and all necessary hardware. etc as required. |
| 18 | Providing and carrying out core cutting in RCC/brick masonry wall for passing refrigerant pipes, drain pipe and control cable of air-conditioning unit up to 4 TR, including filling the core opening with PU foam and making good the surface after installation, complete as required. |
| 19 | Fabricating, Supplying & Fixing wire mesh protection frame work made out of 40 mm x 6 mm thick angle & \\"T\\" strengthened with intermediate members of MS flat iron of size 30 mm x 5 mm thick welded at a distance of 30 cm horizontally & vertically and duly welded with wire mesh of size 75 mm x 25 mm made with 6 SWG wire mash of size 75 mm x 25 mm made with 6 SWG wire on all sides and top i/c providing and fixing of double door gate with double locking arrangement ( Two Nos. sliding bolts and One No go down lock) having 0.5 mtr. long legs of 40 mm x 40 mm x 6 mm thick angle iron, duly grouted in cement concrete foundation ration 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate), up to suitable depth painting with one coat of red oxide & Two coats of synthetic enamel paint of approval colour and shade etc. complete as reqd. |
| 20 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 21 | 100 A, 16 KA,TPMCCB |
| 22 | Supply, installation, testing, and commissioning of one 63A, 440V, TP MCB with \\"C\\" Curve tripping characteristics and a 10kA breaking capacity. The unit shall be fixed in pre existing Sheet Steel Enclosure. The scope includes fixing TP and making the connections as required. |
| 23 | Supplying & laying of following size XLPE insulated and PVC sheathed Aluminium conductor armoured power cable of 1.1 KV grade conf. to IS 7098 (Part-I) on surface with the help on suitable clamp and other accessories etc. as required. |
| 24 | 4x16 sqmm |
| 25 | 4x25 sqmm |
| 26 | Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR) with camera licenses to record for all channels having specifications and features etc as mentioned below : 1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to record per NVR and to provide a live view, storage and simultaneously Multi-channel playback of all IP camera or more and must be ONVIF with minimum support of 384 Mbps incoming Bandwidth. 2) NVR should support video compressions : H.265 or better, H.264, MJPEG. 3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with G.711U/A, G.711u, PCM, G726 audio compressions. 4) Intelligent auto power on when power resumes after power outage. 5) Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID support of RAID 0/1/5/6/10. 6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port 7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0, 2xUSB2.0) 8) Video Output Ports: 2x HDMI and 2 VGA 9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external sensors and output devices like hooter/ Siren etc. 10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated mobile number for power failure, HDD failure, vandalism, tempring, network disconnection and panic 11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing. 12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE, FTP, DDNS, Alarm Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI, SDK and OEM Cloud for remote monitoring without any public IP need. 13) Standards: CE, FCC, RoHS, BIS Certified 14) Power Supply : Should support AC100-240V, 50/60Hz Power supply. 15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing) 16) The VMS application shall support all the features & functionalities of the offered cameras. 17) VMS should consist Licenses for all channels to record Cameras with General, motion detection, intelligent, alarm and POS recording modes. VMS should be provided with Camera Licenses , with no dependency of VMS licenses by binding with the MAC address of the cameras to achieve the functionality. 18) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR footage. 19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote monitoring over the Internet. 20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode 21) It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF 22) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert details. The snapshot function is supported on monitoring and playback page |
| 27 | 23) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any combination of critical, warning, or informational messages or alarm notifications. When an alarm occurs, the email message includes the NVR name, time of alarm and a list of camera that is configured to record upon alarm 24) It should have Web and GUI interface. 25) Built-In Artificial Intelligence: NVR should have built-in AI :- - 2 Channel face detection and recognition, - Minimum 4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection 26) Face Recognition Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum 20,000 Faces or more with Face Detection speed of 12 face images/sec and facility to add Name, gender, birthday, address, credential type, credential No., countries & regions and state to each face image. 27) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses, expressions, face mask, beard, Top color, top type, hat, bag, age, gender and umbrella. 28) ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle body, vehicle model, vehicle logo, calling, seatbelt, vehicle registration location etc vehicle attributes. 29) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan, cybersecurity exception 30) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and email. 31) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection. 32) Smart playback function: Should support smart search for the selected area in the video and smart playback to improve the playback efficiency 33) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics 34) Analytics by NVR: Perimeter protection and face recognation32 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16/25/32(36), 2nd screen: 1/4/8/9/16 |
| 28 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required. |
| 29 | 1 Run of cable Please Enable Macros to View BoQ information |