| 1 | Wiring for lighting points/fan points/exhaust fan points/call bell points with 2x1.5 sq mm FRLS/HFFR PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit, with 240V 6A modular switch ,modular plate, suitable GI box and earthing the point with 1.5 sq mm FRLS PVC insulated copper conductor single core cable, etc. as required. (Havells/ Polycab/ Anchor/ SSK/KEI/RR/ eq. make to be approved by EIC) including the cost of conduit. |
| 2 | Supply, Installation, Testing and Commissioning of 12W Watt/+ LED Bulb incl. cost of base block/ base plate holder, minimum 100lm/w, average life 50000 hours, Operating temperature -10°C to +45°C Complete Job .Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro/ eq. make to be approved by EIC |
| 3 | Supply, installation, testing and commissioning of 1200 mm (48”) BEE Star rated energy-efficient ceiling fan, complete with 3 Nos. aluminum blades, downrod, canopy, capacitor, safety pin, nuts, bolts and washers, suitable for 230 V, 50 Hz AC supply. The fan shall have air delivery not less than 220 m³/min, rated speed (RPM) between 340–380 (as per manufacturer’s specification), power consumption not exceeding 50 watts, service value ≥ 6.0, noise level ≤ 60 dB, insulation class ‘B’ and insulation resistance > 2 MΩ. Fan shall be of approved make such as Usha / Havells / Crompton / Orient or equivalent, including installation, online RPM verification, testing, commissioning and handing over to the Engineer-in-Charge, with minimum 2-year manufacturer warranty. |
| 4 | Supplying and fixing ISI-marked 6 A, 250 V modular step-type electronic fan regulator (2 Module), conforming to IS:3854 or latest IS standards, mounted on suitable modular plate with GI flush box, including wiring connections, testing and commissioning, of approved make such as Anchor Roma / Legrand / Schneider / Havells/ eq. make to be approved by EIC, complete as per direction of the Engineer-in-Charge. |
| 5 | Supply, Installation, Testing and Comm. Of 200/250mm sweep exhaust fan Shutter type of havell /Bajaj/ Crompton/equivalent make as directed by engineer incharge,Air Flow capacity >850cmph, 35-50Watts,Noise level 44db, 1200 rpm,water resistant, including making of space in wall/ window as per site requirement and necessary connections.The job includes replacement warranty of fixture if damaged/burn out what so ever reason for a period of two years reckoned from the date of sucessful commissioning / handing over of site to the intending department.(To be got approved before installation from EIC) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch connections etc. as required.( Anchor roma plus/Legrand Mylinc /SSK/Schneider Zencelo /Crabtree athena / eq. make to be approved by EIC). |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 No. 3 pin 5/6 A modular socket outlet and 5/6 A modular switch connections etc. as required.( Anchor roma plus/Legrand Mylinc /SSK/Schneider Zencelo /Crabtree athena / eq. make to be approved by EIC). |
| 8 | Wiring for AC/Power plug points (15/16A heating points) with 2x4 sq mm FRLS/HFFR PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit along with 1x4 sq. mm FRLS PVC insulated copper conductor single core cable for earthing, etc. as required.(Havells/ Polycab/ Anchor/ SSK/KEI/RR) including the cost of conduit. |
| 9 | Wiring for 5-10A socket out lets for computer with 2X2.5 sq. mm FRLS/HFFR PVC insulated copper conductor (Havells/ Polycab/ Anchor/ SSK/KEI/RR/ eq. make to be approved by EIC) as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit, alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for earthing etc. as required including the cost of conduit. |
| 10 | Supplying and fixing of indicators on existing modular plate and switch box , incl. connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent). |
| 11 | Supplying and fixing modular blanking plate on the existing modular plate switch box excluding modular plate as recquired. |
| 12 | Supply and fixing of 6 way (4+18), Double door surface/ recess mounting, Horizontal type,three pole and neutral, sheet steel, MCB distribution board ,415V, dust protected, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, excluding cost of MCBs and Incomer. (Havells/Legrand/SSK/Schnider/ABB/ eq. make to be approved by EIC) |
| 13 | Supply, installation, testing and commissloning of 5-32A single pole rating 240/415V, 10 KA \\"C\\" curve MCB of Legrand/ Havells/ L&T/ABB suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 14 | Supply, installation, testing and commissioning of 40A-32A DP rating 240/415V,10 KA \\"C\\" curve MCB of Legrand/ Havells/L&T/ABB/ eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 15 | Supply, installation, testing and commissioning of 63A DP rating 240/415V,10 KA \\"C\\" curve MCB of Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 16 | Supply, installation, testing and commissioning of 100A DP rating 240/415V,10 KA \\"C\\" curve MCB of Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC suitable for inductive load inside PVC enclosure outside MCB distribution board complete with necessary connections. |
| 17 | Supply, installation, testing and commissioning of 100A 4Pole Connector inside PVC enclosure of Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC complete with necessary connections. |
| 18 | Wiring for Circuit/Sub mains along with earth wire in FRLS/HFFR PVC insulated 660/1100 volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, including the cost of conduit. (Havells/ Polycab/ Finolex/ Anchor/KEI/RR/ eq. make to be approved by EIC). |
| 19 | 2x10 sq mm |
| 20 | 2x 2.5 sq mm + 1x 2.5 sq mm Lighting circuit |
| 21 | Supply, laying, connecting and commissioning of 10 sq mm 2 core XLPE/ PVCInsulated and steel armored 1.1 KV grade Aluminum LT cable from Main Panel to Sub Panel at F.Floor, incl. cost of required al. thimbles duly crimped. (Over head/ under ground). (Havells/Polycab/KEI/ eq. make to be approved by EIC) Please Enable Macros to View BoQ information |