| 1 | A CABLE AND CABLE LAYING :Supplying and delivery of following size Armoured cablesXLPE/PVC insulated are designed for 1.1 kV StrandedAluminium conductor, high tensile galvanized steel wire/striparmour for mechanical protection, and PVC/FR PVC outersheathing power cable of following size.(IS 7098 Part - 1/2011 with Up To Date Amendments.)i) 4Core 185 Sqmm.[S.S Panel to J.M Building N.E-LT-Panel] |
| 2 | ii).4 core 70 sq mm.[L.T Panel/Feeder Box to E.VTPN-DB] |
| 3 | iii).4 core 25 sq mm.[VTPN DB TO TPNDB] |
| 4 | Laying of cable on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting.i). above 3½ core 50 sqmm and upto 3½ core 90 sqmm. |
| 5 | ii). upto 3/4 core 25 sqmm. |
| 6 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.i). Above 35 sqmm to 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc. |
| 7 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.With 25x25x3mm angle iron support.i). 300x50x1.25mm (18SWG) |
| 8 | Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.i). 300x50x1.25mm (18SWG) |
| 9 | Supply & Fixing of perforated GI cable tray tee with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.i). 300x50x1.25mm (18SWG) |
| 10 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire.i). From 70sqmm to 150sqmm |
| 11 | ii). Up to 50 sqmm |
| 12 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.i). 8 SWG. |
| 13 | Supply & Fixing & Fabrication MS angle iron support structure for building outer wall of 50x50x6mm & 40x 40x 6mm channel as vertcal member from the wall & 25x6 mm flat as horizontal base structure fabrication ,welding (450 mm clear from wall) by making hole into the wall by grouting & making good the the damages as original finish with necessary double coat of enamel painting with after applying primer . |
| 14 | Laying of 35 Sqmm to 300Sq mm A/Al cable through the above structure by binding with suitable size of GI wire. |
| 15 | Laying only Cable through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core.i). above 50 sqmm but not exceeding 400sqmm |
| 16 | ii). upto 50 sqmm. |
| 17 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required.i). 125 mm dia. |
| 18 | ii). 80 mm dia. |
| 19 | Laying of one No. cable in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.i). above 35 sqmm and upto 185 sqmm. |
| 20 | ii). upto 35 sqmm |
| 21 | B CABLE & WIRE END FINISHINGFinishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials.i).For 4 core 185 sq mm. |
| 22 | ii). For 4 core 70 sq mm. |
| 23 | iii). For 4 core 25 sq mm. |
| 24 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :i).For 4 core 185 sq mm. |
| 25 | ii). For 4 core 70 sq mm. |
| 26 | iii). For 4 core 25 sq mm. |
| 27 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes.................i).1.5 sq mm. [For Computer board & Power Point] |
| 28 | ii).2.5 sq mm. |
| 29 | iii).4.0 sq mm. |
| 30 | iv).6.0 sq mm. |
| 31 | C LINE PROTECTIVE DEVICEs WITH ALLIED DISTRIBUTION BOARDs Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-43 protection, concealed in wall after cutting the wall & mending good the damages to original finish & necy. wall matching putty & paint as required or total establishment on angle iron frame on wall incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.#[Make : Legrand /Siemens/Schneider Make]#i).8Way, Upto 160A Enclosure... |
| 32 | Supplying and fixing double door Horizontal-TPN-MCB DB with IP-43 protection, concealed in wall after cutting the wall & mending good the damages to original finish & necy. wall matching putty & paint as required or total establishment on angle iron frame on wall incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.#[Make : Legrand /Siemens/Schneider Make]#i).6 Way Enclosure... |
| 33 | Supplying and fixing double door SPN-MCB DB with IP-43 protection, concealed in wall after cutting the wall & mending good the damages to original finish & necy. wall matching paint as required or total establishment on angle iron frame on wall incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. #[Make : Legrand /Siemens/Schneider Make]#i).2+8 way Enclosure... |
| 34 | ii).2+16 way Enclosure... |
| 35 | Supplying and fixing 240/415V, following rating MCCBs & MCBs (Legrand Make) of Breaking capacity 10kA for MCBs & 35kA for MCCBs & \\"C\\"characteristics on existing din rail for newly installed DBs and necessary connection as required. #[Make : Legrand /Siemens/Schneider Make]#i).40A DP MCB Isolator. |
| 36 | ii).63A FP MCB Isolator. |
| 37 | iii).6-32A(10kA) SPMCBs. |
| 38 | iv).40A/63A (10kA) TP MCBs. |
| 39 | iv). 125A (35kA) FP MCCBs. |
| 40 | Cutting Channel of size (40mm x 40mm) & (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 25 mm & 19mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles........i).[19 mm dia and 3 mm thick polythene pipe with 1x14 SWG GI earth continuity wire]. |
| 41 | ii).[25 mm dia and 3 mm thick polythene pipe with 1x14 SWG GI earth continuity wire]. |
| 42 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex/Havells/RR/Poly-Cab) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required........... i).3 x 22/0.3 (1.5 sqmm). |
| 43 | ii).2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC. |
| 44 | ii).2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) as ECC. |
| 45 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm/32mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.i). 2x22/0.3(1.5sqmm)+1x22/0.3(1.5sqmm) ECC. |
| 46 | ii). 2x36/0.3(2.5sqmm)+1x22/0.3(1.5sqmm)ECC. |
| 47 | iii). 2x84/0.3(6sqmm)+1x 56/0.3(4sqmm) ECC. |
| 48 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish.i).[Average run 8 mtr]. |
| 49 | ii).[Average run 10 mtr]. |
| 50 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed]i).[Average run 8 mtr]. |
| 51 | ii).[Average run 10 mtr]. |
| 52 | iii).[Average run 12 mtr]. |
| 53 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make)[for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed]i).[Average run 9 mtr]. |
| 54 | ii).[Average run 10 mtr]. |
| 55 | ii).[Average run 12 mtr]. |
| 56 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6A 3 pin Modular type plug socket & switch (Brand approved by EIC) on 4 Module GI switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works.i). On Board. |
| 57 | Supply & Fixing 240 V, 3 nos. 6 A, 3 pin Modular type plug socket with 3 nos. 6A Modular type switch (Brand approved by EIC) & 1 nos. 16 A, 3 pin Modular type plug socket with 1 nos. 16A Modular type switch, without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works incl. making necy. connections as required. |
| 58 | Supply & Fixing 240 V, 2 nos. 6 A, 3 pin Modular type plug socket with 2 nos. 6A Modular type switch (Brand approved by EIC), without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall for housing the board after cutting the brick wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 59 | Supply & Fixing 240 V, 2 nos. 16 A, 3 pin Modular type plug socket with 2 nos. 16A Modular type switch (Brand approved by EIC), without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall for housing the board after cutting the brick wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 60 | Supplying and delivery of LED Industrial Batten light made of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing with Aluminium end-cap) voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range 0o to 40o C, internal surge protection of 2.5 KV(internal) with Short & Open circuit protection , THD < 10% , P.F.≥0.9, IP20, CRI >80, and minimum 40000 Burning Hours (Life projection shall be calculated as per TM-21 methodology), CCT 5700°K /6500°K, and Fixture shall be of relevant BIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, with Minimum 5 year OEM warranty. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted.(System lumen efficacy ≥115 lm/Watt)i)Single fittings along with S/F of 1 no. 18-20 W LED lamp as per specification |
| 61 | ii). Twin fittings along with S/F of 2 no. 18-20 W LED lamps as perspecification |
| 62 | supply and delivery of 1No. 4', 20W LED Tube]. [Philips: Master Led Tube 1200mm 18W-865 T8 IND -2100 lumen/ Crompton Asto Pro TCS-726/ Eqv Bajaj Model] for above tube frame fittings. (For Future Maintenance) |
| 63 | Fixing only single /twin LED tube light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener & flexible cord. |
| 64 | Fixing only LED tube light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports incl. S&F E.I conduit, ball socket/socket type ceiling plate and connecting the length of PVC insulated wire and necy enamel painting etc. as required by 2x24/0.20 mm (1.5sqmm) flexible copper wire of 1.10 mt. length. |
| 65 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 66 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) 2'x2' with powder-coated pressure Die-cast Aluminium/CRCA sheet body with high-transmission opal PMMA/ polycarbonate/ prismatic diffuser having uniform light distribution and construction as per IS : 10322. The driver rated output wattage should be 10% to 15% higher than lamp rating and efficiency Driver >80%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range 00 to 400 C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , PF ≥0.9, IP20, CRI >80, life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K/ 5700°K / 6000°K / 6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect and LED Chips of SMD Low to mid-power, as per requirement (LM-80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.. i)50 - 60 Watt |
| 67 | ii). 50 - 60 Watt |
| 68 | Supplying & Fixing 240 V AC/DC superior type Multitune ( min 10 nos. tune) Call Bell (Anchor) with selector switch for single/Multi Tunes mode, Battery operated on HW board incl. S&F HW board. |
| 69 | Supplying & Fixing bulk head light fitting (Havells/Phillips/Surya make) with die cast aluminium housing & frosted glass on wall/ceiling incl. S&F 12 watts LED lamp complete set. |
| 70 | S/F 12 watt Inverter LED Lamp (B22 base CDL) In the existing Holders. (Philips /Havells make) . |
| 71 | Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mmx 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991). |
| 72 | Supply & delivery of 230 V, 50 Hz, single phase, 52 watts, 48\\" (1200 mm) Sweep, speed 320 rpm (minimum), A.C. Ceiling Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod (14 SWG & higher thickness), 2 nos. canopies, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 210 cu.m/min (minimum), without Regulator including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required |
| 73 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. |
| 74 | Extra for supplying additional wire and down rod & painting the rod exceeding 30 cm by 2x1.5 sqmm flexible copper wire. |
| 75 | Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc..[For New & Existing Fan] |
| 76 | Supply & delivery of 230 V, 50 Hz, single phase, 40 watts , 9\\" (230 mm) Sweep, speed 1350 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 650 cmh (minimum) including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 77 | Supply & delivery of 230 V, 50 Hz, single phase, 80 watts, 12\\" (300 mm) Sweep, speed 1400 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 1710 cmh (minimum) including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance morethan 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 78 | Fixing only AC Exhaust Fan for Toilet use of 230mm/ 300mm sweep after making hole in wall and making good the damages and smooth cement finish etc. as practicable as possible and providing necessary length of PVC insulated wire and making necy. connection with flexible cord.i). 9\\"(inch),230mm. |
| 79 | ii). 12\\"(inch),300mm. |
| 80 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long).i).For 9\\"(inch),230mm Ex-Fan. |
| 81 | ii).For 12\\"(inch),300mm Ex-Fan. |
| 82 | Supply & Delivery of 230 V, 50 Hz, single phase, 85 watts, 18\\" (450mm), speed 1325 rpm (minimum), Bracket Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body with metal back cover. Power Factor not less than 0.9 and minimum air delivery 110 cu.m/min (minimum), including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulationresistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 83 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts &washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length. |
| 84 | Supply & Delivery of 230 V, 50 Hz, single phase, 85 watts, 18\\" (450mm),speed 1325 rpm (minimum), Air-Circulator adjustable Pedestal Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body with metal back cover. Power Factor not less than 0.9 and minimum air delivery 110 cu.m/min (minimum) includingcapacitor with safety pin, nutbolts,washers,temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR,PVC insulated copper conductor single core cable and earthing etc. as required. |
| 85 | Excavation of soil for installation of Earth Electrode and filling & ramming.i). For Morrum Soil. |
| 86 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:i). By ISI-Medium GI pipe |
| 87 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 88 | Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. |
| 89 | Dismenteling the existing distribution boxes,wiring, Concealed switch board, Concealed type JB,Panel related all acessories light fixtures and fittings etc. and mending good the damages to the original finish by neat cement concrete mixture & neccy. plaster cover with 1.5mm thick wall putty as existing wall matching as required. Please Enable Macros to View BoQ information |