| 1 | Supply & delivery of single 4ft LED tube light fitting incl. 4ft LED tube, 1200 mm, Efficacy>= 100 lm/W, THD<10%, complete with all accessories. (Mas LEDtube 1200mm) [Philips: TMC 501 P 1xT-LED 36W P3241] or equivalent of Havells, Crompton etc. [Approved by EIC] |
| 2 | Supply & delivery of Sweep:- 48\\" (1200mm) AC ceiling fan, 50-70 Watts, Speed:->=350 RPM, Air delivery:->=220 CMM, make: (Orient PSPO NEWBREEZE or SUMMERCOOL / equivalent of EPC or USHA STRIKER PLUS or CROMPTON [Approved by EIC] |
| 3 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand / Havells / Siemens).Single Pole 6-32A MCB [MNDB, MEDB, PDB 1,2, LDB 1,2, EDB 1,2 O/G] |
| 4 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. [Separate 20A Plug Point] |
| 5 | Distributionwiringin1.1KVgrade2x22/0.3(1.5sqmm)single corestranded'FR' PVCinsulated&unsheathedcopperwire (BrandapprovedbyEIC) insuitablesizePVCcasing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVCinsulated&unsheathedcopperwire for ECC, incl. necy. fittingsetc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on ModularGI /PVCswitch boardwithtopcoverplateonwall incl.mendinggooddamagestooriginal finish. [PVCcasing capping and Switch board both on surface]Average run 11 mtr |
| 6 | Supply & Fixing 240 V 6 A Piano key type switch (Make-Anchor/Havells) on existing sheet metal switch board having bakelite/perspex top cover by screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 7 | Supply & Fixing 240 V, 6A plug socket and 5 pin (Make-Anchor/Havells)), without switch & plug top, on existing sheet metal switch board with bakelite/perspex top cover by screws after making housing for plug by cutting bakelite/perspex top cover and making necy. connections with PVC wire and earth continuity wire etc. |
| 8 | 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 9 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 10 | 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC |
| 11 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mmdia x 62 mm long) 60 cm Exhaust fan (24\\") |
| 12 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat ironframe & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x62 mm long) |
| 13 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By TATA-Medium GI pipe [D.G. Body:2, D.G. Neutral: 2, VTPN DB:1, UPS Neutral: 1] |
| 14 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 15 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe |
| 16 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. |
| 17 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages |
| 18 | Add @ 18% GST |
| 19 | Add @ 1% L.CESS Please Enable Macros to View BoQ information |