| 1 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP 42 ( VDS approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors.(Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 2 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector IP 42 ( VDS approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 3 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required.(Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 4 | Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS approved) approved. (Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 5 | Supply, Installation, Testing & Commissioning of Addressable Monitor Modules ( VDS approved ) for monitoring Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 6 | Supply, Installation, Testing & Commissioning of Addressable Relay Modules (VDS approved) for switching / integration of Lift / AHU etc complete as required. (Approved Make : Siemens/ Honeywell-Esser/ BOSCH) (Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 7 | Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Seimens / Honeywell- Notifier/ Bosch)The new devices should be matched with the existing 2/4/6 loop addressable Fire panel (make-- Seimens) |
| 8 | Through Checking of existing Fire Detection system installed at MCH building under MCHES-II/ PWD by deputing requisite technicians and engineers as per requirement & rectified the all fault. Software commissioning charge in case of any software issue / Device Removing from Detection line / Re-Commissioning. This is including all necessary tools, tackles, ladder etc. & issue of fit certificate. |
| 9 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab/KEI) with necessary arrangement as per G.S. on wall/ceiling. |
| 10 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make,medium quality] on wall, ceiling with saddles and other accessories as required and mending good damages to building works20mm size |
| 11 | S&F of MS box of suitable size of fire panel with locking arrangement with front acrylic door incl. necy. Painting and locking arrangement as per direction of EIC. |
| 12 | Commissioning charges for newly installed devices with the existing per-installed 2/4/6 loop Addressable Fire panel (MK: Siemens ) as per direction of EIC. Making necessary drawing of total installation FD System and submitted to the office as per direction of EIC. |
| 13 | Supply, fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. ( MK: Airmaster/ Systemair/Premire/ Air Enerprise)a) Fire Damper |
| 14 | b) Actuator with controlling unit and detector |
| 15 | NOTE :- 1) The Fire Alarm system shall comply with latest requirements of --(i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 ,(iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand. |
| 16 | TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. |
| 17 | Terms and conditionsThe Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. |
| 18 | Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules |
| 19 | Before taking up the work necessary drawing/layout should be prepared and must be approved from the appropriate authority of PWD according to the prevailing fire safety policy. After commissioning, completion certification should be obtained from same appropriate authority of PWD without which payment should not be released. |
| 20 | [ Rates should be Quotated inclusive of all taxes & duities and L.W.C. @ 1% as applicable ] Please Enable Macros to View BoQ information |