| 1 | Sub-Head No. I (Wiring) |
| 2 | Wiring for light point / Fan point / Exhaust Fan point / Call bell point with 1.5 mm2 FR PVC insutated copper conductor single core cable in PVC casing & capping with modular type switch, modular plate suitable size, G.I-box and earthing the point with 1.5 mm2 FR PVC insulated copper conductor single core cable etc. as reqd. |
| 3 | 2. Group B -- Light Pt. - 90 |
| 4 | 2. Group B - Fan Pt. - 26 |
| 5 | 2. Group B - Wall Fan Pt. - 4 |
| 6 | 2. Group B - Exhaust fan Pt. - 4 |
| 7 | Total |
| 8 | Wiring for light point / Power Plug point with 2 x 4 mm2 FR PVC insutated copper conductor single core cable in PVC casing & capping along with 1 no. 4 mm2 FR PVC insulated copper conductor single core cable for loop earthing etc. as reqd. |
| 9 | Wiring for circuit / Sub - main wiring along with wire with ( the following size of ) PVC insulated copper conductor single core cable in PVC cassing & capping etc. as reqd. |
| 10 | 1. 2 x 1.5 mm2 + 1 x 1.5 mm2 earth wire |
| 11 | 2. 2 x 2.5 mm2 + 1 x 2.5 mm2 earth wire |
| 12 | 4. 2 x 6 mm2 + 1 x 6 mm2 earth wire |
| 13 | 5. 2 x 10 mm2 + 1 x 10 mm2 earth wire |
| 14 | 25 mm2 ISI marked PVC insulated PVC sheathed Al. Conductor S/Core cable |
| 15 | Sub-Head No. II ( Fitting and accessories) |
| 16 | Providing and Fixings ( following capacity TP & N ) dis-connector fuse switch unit inside the existing cubical panel board with ISI marks HRC fuses including drilling holes in the cubical panel board, making connection as reqd. |
| 17 | 3. 100 amp TP & N |
| 18 | S/F Bus bar chamber with 4 strips bus bar of length 300 mm suitable for 100 amp capacity complete with all accessories i/c connection, earthing the body etc. as reqd. |
| 19 | S/F ( following way), single / double pole and neutral, sheet steel MCB distribution board, 240 V on surface / recessed complete with tinned copper bus bar neutral bus bar, earth bar, din bar, detachable gland plate, interconnection, phosphatized and powder painted including earthing etc. as reqd. ( but without MCB / RCCB / Isolator) |
| 20 | 3. 8 way single door |
| 21 | 4. 12 way single door |
| 22 | Supplying and fixing 5 amp to 32 amp rating 230 V 'B' series MCB for lighting and other load of (following poles) in the existing MCB DB complete with connection, testing and commissioning etc. as reqd. |
| 23 | 1. Single Pole |
| 24 | S/F ( following rating) four pole 240 V isolator in the existing MCB DB complete with connection, testing and commissioning as reqd. |
| 25 | 2. 63 amp |
| 26 | Modular base & cover plate for 4 module |
| 27 | Modular base & cover plate for 6 module |
| 28 | Modular base & cover plate for 8 module |
| 29 | Supply & Fixing ( following Modular type switch / socket) on the existing modular plate and switch box i/c connection but excluding modular plate etc. as reqd. |
| 30 | 1. 5 / 6 amps switch |
| 31 | 4. 3 pin 5 / 6 amps socket |
| 32 | S/F suitable size G.I box with modular plate and cover in front on surface or in recess i/c P/F 3 pin 5/6 amp modular socket outlet and 5/6 amp modular switch, connection painting etc. as reqd. ( for light plug to use in non - residential building ) |
| 33 | S/F suitable size G.I box with modular plate and cover in front on surface or in recess i/c P/F 6 pin 15/16 amp modular socket outlet and 15/16 amp modular switch, connection painting etc. as reqd. ( for light plug to use in non - residential building ) |
| 34 | S/F 56 \\" sweep (1400 mm) A.C ceiling fan complete with down rod, canopy, 3 (three ) blades but without regulator etc. as reqd. ( Make Bajaj / Usha or similar ) |
| 35 | Supplying & Fixing stepped type electronic Fan Regulator on the existing modular plate switch box i/c connection but excluding modular plate etc. as reqd. |
| 36 | S/F 400 mm dia wall mounting fan complete with all accessories etc. as reqd. |
| 37 | S/F 305 mm sweep exhaust fan complete with all accessories i/c connection etc. as reqd. |
| 38 | S/F Lumiline surface and wall mounted LED batten with policarbonate housing & intregrated electronic driver ( LUMILINE BS 20W LED 830 SPCWH) |
| 39 | S/F 2 ton capacity split ype Air conditioner, (Dimond, 3 star, 5G 30, G-SC 24 FD 3 WJH) complete with Indo voltage stabilizer, Automatic 4 KVA ( 140-280 for 2 ton) |
| 40 | S/F 3 pin 5 amp ceiling rose on the existing junction box / wooden block i/c connection etc. as reqd. |
| 41 | S/F Brass Batten / Angle holder i/c connection etc. as reqd. |
| 42 | Square box 12mm to 32 mm |
| 43 | Earthing with copper plate 600 mm x 600 mm x 6 mm thick i/c accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) as reqd. |
| 44 | Extra for using salt and charcoal for G.I or copper plate earth electrode as reqd. |
| 45 | P/F 25 mm x 5 mm copper strip in 40 mm dia G.I pipe from earth electrode as reqd. |
| 46 | P/F 4 mm dia copper wire on surface or in recessed for loop earthing as reqd. Please Enable Macros to View BoQ information |