| 1 | A-SUPPLY PART |
| 2 | 33 KV LINE BAY (INCLUDING ALL CIVIL WORKS) |
| 3 | SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY (INCLUDING ALL CIVIL WORKS) |
| 4 | 33 KV VCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
| 5 | 33 KV Isolator without earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) |
| 6 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
| 7 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
| 8 | 33 KV C&R panel along with O/C, E/F relays (IEC 61850),MIMIC diagram , voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
| 9 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
| 10 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
| 11 | STEEL STRUCTURES |
| 12 | Pipe Nominal bore 200, 5.9 mm thick |
| 13 | Galvanised steel structures |
| 14 | Galvanized nuts and bolts |
| 15 | CONTROL CABLES |
| 16 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
| 17 | 8 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 18 | 2 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 19 | Lugs & Ferrules etc. |
| 20 | CONDUCTOR AND HARDWARE |
| 21 | ACSR Conductor Panther |
| 22 | T-Clamp |
| 23 | Single Tension fitting |
| 24 | Polymer Composit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load 70 KN |
| 25 | Earth Wire 7/4 sqmm |
| 26 | G.I Flat 50*6 mm |
| 27 | 33/11 KV, 6.30 MVA Power Transformer |
| 28 | 33/11KV ONAN,Copper wound,outdoor type,6.30 MVA Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections ans spare 3 Barrells transformer oil |
| 29 | 10 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 30 | 6 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 31 | 2 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 32 | Lugs & Ferrules etc. |
| 33 | Single Bus system 11 KV (Transformer Bay Scheme) INDOOR Switchgear |
| 34 | 11 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector Smart meter-5A,DLMS Compliant with RS-485 Port 1 Incoming & 4 outgoings |
| 35 | 11KV Gapless Surge Arrestor,9KV,10KA LA With polymer Housing Station Type |
| 36 | 11KV (UE) XLPE Power Cable 3 core armoured |
| 37 | II. 400 mm square three core |
| 38 | II. 120 mm square three core |
| 39 | 11KV Heat shrink termination Cable Kits (Indoor) 400 mm square (3-core) |
| 40 | 11KV Heat shrink termination Cable Kits (Outdoor)400 mm square (3-core) |
| 41 | 11KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core) |
| 42 | 11KV Heat shrink termination Cable Kits (Outdoor) 120 mm square (one spare)(3-core) |
| 43 | 11 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch |
| 44 | 11KV Go Set AB switch 3 phase, 3 pole, 400 Amps. |
| 45 | 100 KVA, 11/.433 KV, Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound. |
| 46 | St Poles 9 mtrs long |
| 47 | Galvanised iron of sorts |
| 48 | 120 mm2 PVC 4 core cable,Armoured FRLS |
| 49 | MCCB 200 Amp |
| 50 | Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole |
| 51 | Earthing of 100 KVA Sub Station As per Standard |
| 52 | Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long |
| 53 | COMMON MISCELLANEOUS EQUIPMENTS |
| 54 | a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand |
| 55 | b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply. |
| 56 | Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supply with 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories |
| 57 | Distribution panel (415 V, AC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories. |
| 58 | Development of land (a per available at site ) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain. Including Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates) |
| 59 | 33 KV LINE |
| 60 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
| 61 | GI Channel X-arm including clamps and braces |
| 62 | 100 mm² ACSRDog Conductor |
| 63 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 64 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 65 | Galvinized Nuts and Bolts. |
| 66 | Danger Plates with Clamps |
| 67 | Anti-Climbing Device with Clamps |
| 68 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 69 | Red Oxide |
| 70 | Aluminium Paint |
| 71 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
| 72 | Stone Pad (300 mm x 300 mm x 75 mm) |
| 73 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 74 | SAFETY ITEMS |
| 75 | Rubber Mat 1m*2m (19mm thick) |
| 76 | Fire Extinguisher CO2 type of 4.5 Kg capacity for control room |
| 77 | 3-Sand Bucket Fire Extinguisher |
| 78 | Helmet with LED torch |
| 79 | Rubber Gloves for 33 KV Level |
| 80 | Rubber Gloves for 11 KV Level |
| 81 | Safety Belt |
| 82 | Safety Shoes |
| 83 | Earthing rod (set of 3 rods) |
| 84 | Rain coats |
| 85 | B- ERECTION PART |
| 86 | 33 KV LINE BAY (INCLUDING ALL CIVIL WORKS) |
| 87 | SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY (INCLUDING ALL CIVIL WORKS) |
| 88 | 33 KV VCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
| 89 | 33 KV Isolator without earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) |
| 90 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
| 91 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
| 92 | 33 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
| 93 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
| 94 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
| 95 | STEEL STRUCTURES |
| 96 | Pipe Nominal bore 200, 5.9 mm thick |
| 97 | Galvanised steel structures |
| 98 | Galvanized nuts and bolts |
| 99 | CONTROL CABLES |
| 100 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
| 101 | 8 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 102 | 2 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 103 | Lugs & Ferrules etc. |
| 104 | CONDUCTOR AND HARDWARE |
| 105 | ACSR Conductor Panther |
| 106 | T-Clamp |
| 107 | Single Tension fitting |
| 108 | Polymer Composit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load 70 KN |
| 109 | Earth Wire 7/4 sqmm |
| 110 | G.I Flat 50*6 mm |
| 111 | 33/11 KV, 6.30 MVA Power Transformer |
| 112 | 33/11KV ONAN,Copper wound,outdoor type,6.30 MVA Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections ans spare 3 Barrells transformer oil |
| 113 | 10 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 114 | 6 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 115 | 2 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 116 | Lugs & Ferrules etc. |
| 117 | Single Bus system 11 KV (Transformer Bay Scheme) INDOOR Switchgear |
| 118 | 11 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector Smart meter-5A,DLMS Compliant with RS-485 Port 1 Incoming & 4 outgoings |
| 119 | 11KV Gapless Surge Arrestor,9KV,10KA LA With polymer Housing Station Type |
| 120 | 11KV (UE) XLPE Power Cable 3 core armoured |
| 121 | II. 400 mm square three core |
| 122 | II. 120 mm square three core |
| 123 | 11KV Heat shrink termination Cable Kits (Indoor) 400 mm square (3-core) |
| 124 | 11KV Heat shrink termination Cable Kits (Outdoor)400 mm square (3-core) |
| 125 | 11KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core) |
| 126 | 11KV Heat shrink termination Cable Kits (Outdoor) 120 mm square (one spare)(3-core) |
| 127 | 11 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch |
| 128 | 11KV Go Set AB switch 3 phase, 3 pole, 400 Amps. |
| 129 | 100 KVA, 11/.433 KV, Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound. |
| 130 | St Poles 9 mtrs long |
| 131 | Galvanised iron of sorts |
| 132 | 120 mm2 PVC 4 core cable,Armoured FRLS |
| 133 | MCCB 200 Amp |
| 134 | Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole |
| 135 | Earthing of 100 KVA Sub Station As per Standard |
| 136 | Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long |
| 137 | COMMON MISCELLANEOUS EQUIPMENTS |
| 138 | a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand |
| 139 | b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply. |
| 140 | Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supply with 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories |
| 141 | Distribution panel (415 V, AC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories. |
| 142 | Development of land (a per available at site ) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain. Including Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates) |
| 143 | 33 KV LINE |
| 144 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
| 145 | GI Channel X-arm including clamps and braces |
| 146 | 100 mm² ACSRDog Conductor |
| 147 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 148 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 149 | Galvinized Nuts and Bolts. |
| 150 | Danger Plates with Clamps |
| 151 | Anti-Climbing Device with Clamps |
| 152 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 153 | Red Oxide |
| 154 | Aluminium Paint |
| 155 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
| 156 | Stone Pad (300 mm x 300 mm x 75 mm) |
| 157 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete Please Enable Macros to View BoQ information |