| Sl. No. | Item Description |
| 1 | =B2& \\" BoQ\\" BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CHIEF ENGINEER (R&D) SECUNDERABAD Name of Work: ADDITION / ALTERATION OF BLDG No. 0905 OF RCI, HYDERABAD Contract No: CERD/SEC/TOKEN/60 OF 2025-2026 Bidder Name : PRICE SCHEDULE(This BoQ template must not be modified / replaced by the bidder and the same should be uploaded after filling the relevant columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # SlNo. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency Rate in Figures to be entered by the Bidder Rs. Ps. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e. DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit, if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes Total Amount Total Amount in Words |
| 2 | Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out all kind of soil and disposal of excavated earth upto 50 m and lift upto 1.5 m, complete all as specified and directed. |
| 3 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30 cm measured at a height of 1 m above ground level and removal of rubbish upto a distance of 50 m outside the periphery of the area cleared complete all as specified and directed. |
| 4 | Earth work in excavation by mechanical means (hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out Ordinary rock and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, complete all as specified and directed. |
| 5 | Earth work in excavation by mechanical means (hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out Hard rock (Blasting prohibited area) and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, complete all as specified and directed. |
| 6 | Removing excavated material (all kind of soil) upto 1.00 km and depositing where directed at a level not exceeding 1.50 m above the stating point complete all as specified and directed. |
| 7 | Removing excavated rock upto 1.00 Km and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 8 | Earth work in excavation by mechanical means (hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) all kinds of soil including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, complete all as specified and directed. |
| 9 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc., in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5 m complete all as specified and directed. |
| 10 | Removing excavated soil material upto 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 11 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - all work upto plinth level : 1:4:8 (1 cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) complete all as specified and directed. |
| 12 | S&F, centering and shuttering including strutting, propping etc., and removal of form for foundations, footings, bases of columns etc., for mass concrete complete all as specified and directed. |
| 13 | S&F, centering and shuttering including strutting, propping etc., and removal of form for columns, pillars, piers, abutments, posts and struts, etc., complete all as specified and directed. |
| 14 | S&F, centering and shuttering including strutting, propping etc., and removal of form for lintels, beams, plinth beams, girders, bressumers and cantilevers etc., for mass concrete complete all as specified and directed. |
| 15 | S&F, centering and shuttering including strutting, propping etc., and removal of form for suspended floors, roofs, landings, balconies and access platform complete all as specified and directed. |
| 16 | Providing and laying in position ready mixed or site batched design mix cement concrete of M25 grade with minimum cement content of 330 kg/cum for reinforced cement concrete work as in foundation upto plinth level using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland / Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of |
| 17 | laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the Engineer-in-Charge complete all as specified and directed. |
| 18 | Providing and laying in position ready mixed or site batched design mix cement concrete of M25 grade with minimum cement content of 330 kg/cum for reinforced cement concrete work plinth level to level V using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland / Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of |
| 19 | laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the Engineer-in-Charge complete all as specified and directed. |
| 20 | S&F, TMT steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level of grade Fe-500D or more complete all as specified and directed. |
| 21 | S&F, TMT steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level complete all as specified and directed. |
| 22 | Providing and laying in position cement concrete 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) excluding the cost of centering and shuttering - all work upto plinth level stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc., 40 mm thick with 20 mm nominal size stone aggregate complete all as specified and directed. |
| 23 | M&L for brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level upto floor V level in cement mortar 1:4 (1 cement : 4 coarse sand) complete all as specified and directed. |
| 24 | M&L for 15 mm cement plaster on the single or half brick internal wall of mix 1:6 (1 cement : 6 fine sand) finished even and smooth complete all as specified and directed. |
| 25 | M&L for 20 mm cement plaster on the single or half brick external wall of mix 1:4 (1 cement : 4 fine sand) finished even and smooth complete all as specified and directed. |
| 26 | Distempering two coats on new work with 1st quality acrylic distemper on internal wall, having VOC (Volatile Organic Compound) content less than 50 grams/litre of approved brand and manufacture of required shade and colour including one coat of cement primer complete as per manufacturer's specification complete all as specified and directed. |
| 27 | M&L for finishing external walls with 100% premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS-15489:2004, alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives. New work (two coats applied @ 1.43 litre/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm complete all as specified and directed. |
| 28 | S&F, rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - Part-1 and M.S. top cover 80 x 1.25 mm M.S. laths with 1.25 mm thick top cover for rolling shutters complete all as specified and directed. |
| 29 | Providing and fixing ball bearing for rolling shutters complete all as specified and directed. |
| 30 | M&L for making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75 mm thick bed of hard core 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing and finishing the top smooth complete all as specified and directed. |
| 31 | M&L for hard core broken stone boulders to gauge not exceeding 63 mm complete all as specified and directed. |
| 32 | M&L for kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1:4 (1 cement : 4 coarse sand), 25 mm thick complete all as specified and directed. |
| 33 | M&L for preparation of concrete surfaces by brushing, cleaning and washing all the undulations, cracks, pores cleaned and sealed with PU sealant or crack seal properly and apply 1st coat of PU Magnum @ 750 gram/Sqm over a coat of epoxy primer @ 200 ml/sqm and laying 30-40 GSM Geotextile with 50mm side and end lap on the layers and apply 2nd coat of PU Magnum over geotextile @ 750 gram/Sqm complete all as specified and directed.Note: The above item shall be executed by authorised manufacturer / authorised applicator after taking prior approval from GE. |
| 34 | S&F, Providing and fixing factory made uPVC white color sliding window two track made of extruded profiles with wall thickness of 2.3mm (+ 0.2 mm). Window profile with hollow section with multi chamber, Frame (60 mm x 62 mm). sash (42 mm x 67 mm). Sliding Interlock (One vertical length in each shutters) (45.5 mm x 28 mm). Glazing bead (24.5 mm x 16 mm) will be mitered cut and fusion welded at all corners, including drilling of holes for fixing hardware and drainage of water etc., making arrangement for fixing of hardware. |
| 35 | EPDM gasket 1.2 + 0.2 mm thick galvanized steel frame (30 mm x 21.5 mm), Sash (30 mm x 18 mm), profile to be inserted in required profile, frame will be fixed to the wall with 8 mm x 100 mm long fasteners. Hardware [Touch lock of zinc alloyed (white powder coated), steel roller system including 5 mm thick glazing with selected quality glass, aluminum track on bottom rail for two track sliding frame, wool pine for sliding sash and interlock.]. Area not exceeding 2.00 sqm. |
| 36 | Note: The unit rate quoted by contractor excludes cost of glass and includes all other connected accessories. Net opening will be measured for payment purpose. |
| 37 | Providing and laying in steel work grills welded in built up sections / framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required in stringers, treads, landings etc., of stair cases, including use of chequered plate wherever required, complete all as specified and directed. |
| 38 | M&L for finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications painting steel work with Deluxe Multi surface paint to give an even shade. Two coats applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture complete all as specified and directed. |
| 39 | Supply only liquid integral water proofing compound complete all as specified and directed. |
| 40 | Providing and placing in position suitable PVC water stops conforming to IS:12200 for construction / expansion joints between two RCC members and fixed to the reinforce Serrated with central bulb (225 mm wide, 8-11 mm thick) complete all as specified and directed. |
| 41 | Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead complete all as specified and directed. |
| 42 | Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead complete all as specified and directed. |
| 43 | Providing and laying Double charge vitrified tile polished finish of size 600 x 600 mm in floor (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622 of approved brand & manufacturer in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) jointing with grey cement slurry @ 3.3 kg/sqm including grouting the joints with white cement and matching pigments. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily complete all as specified and directed. |
| 44 | Providing and laying Ceramic glazed floor tiles of size 300 x 300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS:15622 of approved make in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/sq.m including pointing the joints with white cement and matching pigments etc., complete all as specified and directed. |
| 45 | Providing and laying Vitrified tiles of sizes 600 x 600mm (thickness to be specified by manufacturer) with water absorption less than 0.08% and conforming to IS-15622 of approved make in all colours & shade in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/sqm including grouting the joint with white cement & matching pigments etc., complete all as specified and directed. |
| 46 | Providing and fixing 1st quality ceramic glazed tiles conforming to IS:15622 (thickness to be specified by the manufacturer) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm including pointing in white cement mixed with pigment of matching shade complete all as specified and directed. |
| 47 | Dismantling precast concrete or stone slabs of thickness upto 40 mm in walls, partition walls, shelves etc., including stacking within 50 metres lead complete all as specified and directed. |
| 48 | Providing and fixing 18 mm thick granite stone slab colour black, Cherry / Ruby red gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window cills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels complete all as specified and directed. |
| 49 | Providing edge moulding to 18 mm thick granite stone counters, vanities etc., including machine polishing to edge to give high gloss finish complete all as specified and directed. |
| 50 | Demolishing brick work in cement mortar manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead complete all as specified and directed. |
| 51 | M&L for Brick work with common burnt clay machine moulded perforated bricks of class designation 12.5 conforming to IS:2222 in superstructure above plinth level upto floor five level in cement mortar 1:6 (1 cement : 6 coarse sand) with F.P.S. (non modular) brick complete all as specified and as directed. |
| 52 | M&L for Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level upto floor V level in cement mortar 1:4 (1 cement : 4 coarse sand) complete all as specified and directed. |
| 53 | Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead complete all as specified and directed. |
| 54 | M&L for rendering 10 mm thick in CM 1:6 on fair faces of brick walls and surface finished even and fair without using extra cement complete all as specified and directed. |
| 55 | M&L for rendering 6 mm thick in CM 1:3 on fair faces of concrete surfaces on ceiling, finished even and smooth without using extra cement complete all as specified and directed. |
| 56 | M&L for rendering 18 mm thick in two layers with 6mm thick in cement mortar 1:6 as setting coat over 12mm thick cement mortar 1:5 on fair faces of brick work or concrete surfaces, finished even and smooth without using extra cement using water proofing compound (in top layer), as per manufactures instructions, complete all as specified and directed.Note: Water proofing compound shall be measured and paid separately under supply only rates. |
| 57 | Supply only integral water proofing compound complete all as specified and directed. |
| 58 | M&L for PCC 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) upto 25%) type B1 using 20mm graded stone aggregate as in kerbs, copings, bed plates, bases of tank padding concrete etc., including necessary formwork, weathering, slightly rounded or chamfered angles and throating complete all as specified and directed. |
| 59 | Dismantling aluminium / Gypsum partitions, doors, windows fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead complete all as specified and directed. |
| 60 | Providing & fixing false ceiling at all heights with GRG (Glass Fibre Reinforced Gypsum) false ceiling tiles of Size 595 x 595 mm of approved texture, design and patterns having moisture content less than 2%, humidity resistance of 99%, NRC 0.50 to 0.75 as per IS 8225:1987, Non combustible as per BS 476 (Part 4) - 1970 and light reflectance of 85% (minimum) to be laid in true horizontal level suspended on interlocking metal T-Grid of hot dipped galvanised iron section of 0.33mm thick |
| 61 | (galvanized @ 120 grams per sqm including both sides) comprising of main-T runners of size 15 x 32 mm of length 3000 mm, cross - T of size 15 x 32 mm of length 1200 mm and secondary intermediate cross-T of size 15 x 32 mm of length 600 mm to form grid module of size 600 x 600 mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 50 mm long, 8 mm outer diameter M-6 dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 85 x 25 x 2 mm. |
| 62 | Galvanised iron perimeter wall angle of size 24 x 24 x 0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40 mm long dry wall wood screws. The work shall be carried out as per specifications and as per directions of the Engineer-in-Charge with semi perforated 12 mm thick micro tegular edged GRG false ceiling tiles. |
| 63 | Providing and fixing, fixed type powder coated aluminium work (minimum thickness of powder coating 50 micron) for doors, windows, ventilators and partitions with extruded built up standard tubular sections / appropriate Z sections and other sections of approved make conforming to IS:733 & IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions i.e. at top, bottom and sides with required EPDM rubber / |
| 64 | neoprene gasket etc. aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws all complete as per the directions of Engineer-in-Charge. Note: Glazing and paneling to be paid for separately. |
| 65 | Providing and fixing powder coated aluminium work (minimum thickness of powder coating 50 micron) for shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required including all fittings complete all as specified and directed. |
| 66 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design / pattern with approved standard section and fixed to the existing window frame with C.P. brass / stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-Charge. (Only weight of grill to be measured for payment). |
| 67 | Providing and fixing 12 mm thick pre-laminated particle board with decorative lamination on both sides, flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc., complete as per directions of Engineer-in-Charge. |
| 68 | Providing and fixing glazing with coloured tinted float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) in aluminium door, window, ventilator shutters and partitions etc., with EPDM rubber / neoprene gasket etc., complete as per the directions of Engineer-in-Charge. |
| 69 | Providing and fixing fly proof wire gauze stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides to windows, clerestory windows & doors with M.S. flat 15 x 3 mm and nuts & bolts complete all as specified and directed. |
| 70 | Providing and fixing double action hydraulic floor spring with stainless steel cover plate minimum 1.25 mm thickness of approved brand and manufacture conforming to IS:6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kgs for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc., complete as per the direction of Engineer-in-Charge. |
| 71 | Providing and fixing brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good complete all as specified and directed. |
| 72 | Dismantling doors, windows and clerestory windows (steel or wood) shutter of area 3 sq. metres and below including chowkhats, architrave, holdfasts etc., complete and stacking within 50 metres lead complete all as specified and directed. |
| 73 | Taking outdoors, windows and clerestory window shutters (steel or wood) of area 3 sq. metres and below including stacking within 50 metres lead complete all as specified and directed. |
| 74 | Providing and fixing pressed steel door frames of size 105 x 60mm conforming to IS:4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, fixing with adjustable lugs with split end tail to each jamb, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50 x 25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-Charge. |
| 75 | Providing and fixing factory made P.V.C. door frame of size 50 x 47 mm with a wall thickness of 5 mm, made out of extruded 5 mm rigid PVC foam sheet, mitred at corners and joined with 02 Nos of 150 mm long brackets of 15 x 15 mm M.S. square tube, the vertical door frame profiles to be reinforced with 19 x 19 mm M.S. square tube of 19 gauge, EPDM rubber gasket weather seal to be provided through out the frame. The door frame to be fixed to the wall using M.S. screws of 65/100 mm size, complete as per manufacturer’s specification and direction of Engineer-in-Charge. |
| 76 | Providing and fixing 35 mm thick factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder / rice husk / wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite / borer proof, water / moisture proof and |
| 77 | fire retardant and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-in- Charge. |
| 78 | Providing and fixing factory made panel 30 mm thick plain PVC door shutters consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19 mm x 19 mm for styles and 15 x 15 mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make & manufacture. M.S. frame covered with 5 mm thick heat moulded PVC 'C' channel of size 30 mm thickness, 70 mm width out of which 50 |
| 79 | mm shall be flat and 20 mm shall be tapered in 45 degree angle on both side forming styles and 5 mm thick, 95 mm wide PVC sheet out of which 75mm shall be flat and 20 mm shall be tapered in 45 degree on the inner side to form top and bottom rail and 115 mm wide PVC sheet out of which 75 mm shall be flat and 20 mm shall be tapered on both sides to form lock rail. Top, bottom and lock rails shall be provided both side of the panel 10 mm (5 mm x 2 mm) thick, 20 mm wide cross PVC sheet be provided as gap insert for top rail & bottom rail, paneling of 5 mm thick both side PVC sheet to be fitted in the M.S. frame welded / sealed to the styles & rails with 7 mm (5 mm + 2 mm) thick x |
| 80 | 15 mm wide PVC sheet beading on inner side and joined together with solvent cement adhesive. An additional 5 mm thick PVC strip of 20 mm width is to be stuck on the interior side of the 'C' channel using PVC solvent adhesive etc., complete as per direction of Engineer-in-Charge manufacturer's specification. |
| 81 | M&L for PCC 1:3:6 type C0 filling in the back portion of door frames complete all as specified and directed. |
| 82 | Taking down old steel shutters including making good to the wall surfaces exceeding 1 sq. m and not exceeding 2 sqm complete all as specified and directed. |
| 83 | Supplying and fixing mechanical operation rolling shutters of approved make, made of 80 x 1.25 mm M.S. laths with 1.25 mm thick top cover, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS:4454 - Part 1 for rolling shutters complete all as specified and directed. |
| 84 | Supplying and fixing 12mm thick toughened glass door at entrance with steel handles on both sides along complete fittings complete all as specified and directed. |
| 85 | Providing and fixing ISI marked aluminium butt hinges of size 100 x 75 x 4 mm anodised (anodic coating not less than grade AC 10 as per IS:1868) transparent or dyed to required colour or shade with necessary screws etc., complete all as specified and directed. |
| 86 | Providing and fixing aluminium sliding door bolts of size 250 x 16 mm, ISI marked anodised (anodic coating not less than grade AC 10 as per IS:1868), transparent or dyed to required colour or shade with nuts and screws etc., complete all as specified and directed. |
| 87 | Providing and fixing aluminium tower bolts of size 200 x 10mm, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS:1868) transparent or dyed to required colour or shade with necessary screws etc., complete all as specified and directed. |
| 88 | Providing and fixing aluminium handles of size 125 mm, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS:1868) transparent or dyed to required colour or shade with necessary screws etc., complete all as specified and directed. |
| 89 | Providing and fixing aluminium hanging floor door stopper with twin rubber stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS:1868) transparent or dyed to required colour and shade with necessary screws etc., complete all as specified and directed. |
| 90 | Dismantling G.I. pipes of 15 mm to 40 mm dia bore including excavation and refilling trenches after taking out the pipes, manually / by mechanical means including stacking of pipes within 50 metres lead complete all as specified and directed. |
| 91 | Providing and fixing 15 mm dia G.I. pipes complete with G.I. fittings and clamps, including making good the walls etc., concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good to the walls complete all as specified and directed. |
| 92 | Providing and fixing 20 mm dia G.I. pipes complete with G.I. fittings and clamps, including making good the walls etc., concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good to the walls complete all as specified and directed. |
| 93 | Providing and fixing 25 mm G.I. pipes complete with G.I. fittings in existing trenching and refilling etc., complete all as specified and directed. |
| 94 | Dismantling C.I. or asbestos rain water pipe of 100 mm dia pipe with fittings and clamps including stacking the material within 50 metres lead complete all as specified and directed. |
| 95 | Providing and fixing single socketed pipes 110 mm diameter on wall face unplasticised rigid PVC rain water pipes conforming to IS:13592 type 'A', including jointing with seal ring conforming to IS:5382, leaving 10 mm gap for thermal expansion complete all as specified and directed. |
| 96 | Providing and fixing on wall face unplasticised - PVC moulded 110 mm bend for unplasticised rigid PVC rain water pipes conforming to IS:13592 type 'A', including jointing with seal ring conforming to IS:5382, leaving 10 mm gap for thermal expansion complete all as specified and directed. |
| 97 | S&F, Stack clamps for 110 mm dia pipes of any description of 50 mm by 5 mm flat iron and 16 mm dia round iron stays, including bolts and nuts and securing ends of stays to walls or roof complete all as specified and directed. |
| 98 | Providing and fixing soil, waste and vent pipes of 100 mm dia centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS:3989 complete all as specified and directed. |
| 99 | Providing and fixing soil, waste and vent pipes of 75 mm dia centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS:3989 complete all as specified and directed. |
| 100 | Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 (1 cement : 2 fine sand) in S.C.I. / C.I. pipes of 100 mm dia complete all as specified and directed. |
| 101 | Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 (1 cement : 2 fine sand) in S.C.I. / C.I. pipes of 75 mm dia complete all as specified and directed. |
| 102 | Providing and fixing M.S. holder-bat clamps of size 100 mm dia pipe of approved design to sand cast iron / cast iron (spun) pipe embedded in and including cement concrete blocks 10 x 10 x 10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc., complete all as specified and directed. |
| 103 | Providing and fixing M.S. holder-bat clamps of size 75 mm dia pipe of approved design to sand cast iron / cast iron (spun) pipe embedded in and including cement concrete blocks 10 x 10 x 10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc., complete all as specified and directed. |
| 104 | Providing and fixing plain bend of required degree 100 mm dia sand cast iron S&S as per IS:3989 complete all as specified and directed. |
| 105 | Providing and fixing plain bend of required degree 75 mm dia sand cast iron S&S as per IS:3989 complete all as specified and directed. |
| 106 | Providing and fixing 100 mm inlet and outlet sand cast iron S&S as per IS:3989 floor / nahani traps of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors complete all as specified and directed. |
| 107 | Providing and fixing square-mouth S.W. gully trap class SP-1 of size 100 x 100 mm size P type complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x 300 mm size (inside) the weight of cover to be not less than 4.50 kgs and frame to be not less than 2.70 kgs as per standard design complete all as specified and directed. |
| 108 | Disconnecting damaged overhead / terrace PVC water storage tank of any size from water supply line and removing from the terrace including shifting at ground level complete all as specified and directed. |
| 109 | S&F, rotational moulded polyethylene triple layer water storage tanks (cylindrical, vertical with closed top) hoisted and fixed in position 1000 ltr capacity complete all as specified and directed. |
| 110 | Providing and fixing stainless steel A ISI:304 (18/8) kitchen sink with drain board 510 x 1040 mm bowl depth 250 mm as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required complete all as specified and directed. |
| 111 | S&F in repair 15mm dia Brass CP wall mixer 3-in-1 system for mixing hot & cold water and also shower screwed down for iron pipe in Bathrooms fixed complete all as specified and directed. |
| 112 | Providing and fixing C.P. brass long nose bib cock 15 mm dia of approved quality conforming to IS standards and weighing not less than 810 gms complete all as specified and directed. |
| 113 | Providing and fixing C.P. brass stop cock (concealed) 15 mm dia nominal bore of standard design and of approved make conforming to IS:8931 complete all as specified and directed. |
| 114 | Providing and fixing 20 mm dia gun metal gate valve with C.I. wheel of approved quality (screwed end) complete all as specified and directed. |
| 115 | Providing and fixing 25 mm dia gun metal gate valve with C.I. wheel of approved quality (screwed end) complete all as specified and directed. |
| 116 | S&F in repair ball brass valves 20 mm dia high pressure with polythene float and flynut screwed for iron pipe or brass ferrule complete all as specified and directed. |
| 117 | Providing and fixing white vitreous china flat back single half stall urinal of size 580 x 380 x 350 mm with white 5 litres PVC automatic flushing cistern with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS:2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required complete all as specified and directed. |
| 118 | Providing and fixing white vitreous china pedestal type water closet (European type) with ISI marked white solid plastic with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required complete all as specified and directed. |
| 119 | Providing and fixing 10 litres white P.V.C. low level flushing cistern with manually controlled device (handle lever) conforming to IS:7231, with all fittings and fixtures complete all as specified and directed. |
| 120 | Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to European type W.C. of quality and make as approved by Engineer-in-Charge. |
| 121 | S&F, CP brass toilet roll paper holder with flap of approved quality complete all as specified and directed. |
| 122 | Providing and fixing White Vitreous China Wash basin size 550 x 400mm with C.I. brackets with a pair of 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require completed all as specified and directed. |
| 123 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete all as specified and directed. |
| 124 | Providing and fixing uplasticised PVC connection 15 mm nominal dia pipe with brass unions of 45 cm length complete all as specified and directed. |
| 125 | S&F, soap dish fixed with and including chromium plated brass screws and wooden / plastic cleats complete all as specified and directed. |
| 126 | S&F in repair CP brass tubular towel rail, 20 mm dia, D type, 60 cm long fixed with and including chromium plated brass screws and wooden / plastic cleats complete all as specified and directed. |
| 127 | Taking down existing roof treatment of any description including cement plaster on concrete surface of roof slab including cleaning by picking sweeping and washing down with water to remove dust complete all as specified and directed. |
| 128 | M&L for 10mm thick cement plaster in CM 1:4 (after applying cement slurry @ 3 Kg/Sqm over the existing roof slab) and surface finished even and smooth complete all as specified and directed. |
| 129 | M&L for preparation of concrete surfaces by brushing, cleaning and washing all the undulations, cracks, pores cleaned and sealed with PU sealant or crack seal properly and apply 1st coat of PU Magnum @ 750 gram/Sqm over a coat of epoxy primer @ 200 ml/sqm and laying 30-40 GSM Geotextile with 50 mm side and end lap on the layers and apply 2nd coat of PU Magnum over geotextile @ 750 gram/Sqm complete all as specified and directed.Note: The above item shall be executed by authorised manufacturer / authorised applicator after taking prior approval from Engineer-in-Charge. |
| 130 | Cutting grooves in brick wall, 75 mm wide and 65 mm deep and shaping horizontal faces of grooves with cement mortar in CM 1:3 and making good in CM 1:3 after inserting membrane in to the groove complete all as specified and directed. |
| 131 | Reinforced cement concrete work in beams, suspended floors, roofs having slope upto 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level upto floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) complete all as specified and directed. |
| 132 | M&L for mild steel TMT bars 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping etc., binding with MS wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed. |
| 133 | M&L for formwork to edges of concrete flats, breaks in floors, openings in concrete walls, floors & roofs and sides of RCC/PCC bands in walls, horizontal or sloping and similar work all exceeding 20 cm wide complete all as specified and directed. |
| 134 | M&L for two coats of Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre of required shade and colour over one coat of water thinnable cement primer over one coat of putty of approved brand and manufacture on new wall surface complete as per manufacturer's specification all as specified and directed. |
| 135 | M&L for preparation of newly plastered surfaces of ceiling and applying three coats of white wash complete all as specified and directed. |
| 136 | M&L for finishing new walls with 02 coats of 100% premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS-15489:2004, alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives applied @ 1.43 litre/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm over one coat of putty complete as per manufacturer's specification all as specified and directed. |
| 137 | M&L for preparation of new wooden surface over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified and directed. |
| 138 | M&L for preparation of new surfaces of steel and iron / steel surfaces and applying two coats of first quality synthetic enamel paint over a coat of primer complete all as specified and directed. |
| 139 | M&L for removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc., complete on old wall surfaces and applying 02 coats of Distempering with 1st quality acrylic distemper (Ready mix) having VOC content less than 50 grams/litre of approved brand and manufacture to give an even shade over applying one coat of water thinnable cement primer over a coat of putty of approved brand and manufacture complete as per manufacturer's specification all as specified and directed. |
| 140 | M&L for preparation of old plastered surfaces of ceiling and applying two coats of white wash complete all as specified and directed. |
| 141 | M&L for removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc., complete on old plastered surfaces and applying 02 coats premium acrylic emulsion paint of exterior grade, having VOC (Volatile Organic Compound) content less than 50 grams/litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour over 01 coat water thinnable cement primer over o coat of putty of approved brand and manufacture complete as per manufacturer's specification all as specified and directed. |
| 142 | M&L for preparation of old wooden surface and applying two coats of synthetic enamel paint complete all as specified and directed. |
| 143 | M&L for preparation of old steel surfaces and applying two coats of synthetic enamel paint (ordinary tint) complete all as specified and directed. |
| 144 | M&L for providing and injecting chemical emulsion for Post Constructional Antitermite Treatment along external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc., in apron of the vertical surface of the sub-structure to a depth of 300 mm complete all as specified and directed by Engineer-in-Charge. |
| 145 | M&L for providing and injecting chemical emulsion for Post Constructional Antitermite Treatment of soil under existing floors using emulsion @ one litre per hole, 300 mm apart including drilling and plugging 12 mm dia holes with cement mortar 1:2 (1 cement : 2 coarse sand) to match the existing floors complete all as speicified and directed. |
| 146 | Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth complete all as specified and directed. |
| 147 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) 0.50 mm (+ 0.05%) total coated thickness with zinc coating 120 grams per sqm as per IS:277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-Charge. |
| 148 | The sheet shall be fixed using self drilling / self tapping screws of size (5.5 x 55 mm) with EPDM seal, complete upto any pitch in horizontal / vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required complete all as specified and directed. |
| 149 | Providing and fixing Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer complete all as specified and directed. |
| 150 | Designing, fabricating, testing, installing & fixing in position curtain wall with aluminium composite panel cladding with open grooves for linear as well as curvilinear portions of the building for all heights and all levels etc., including:(a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. |
| 151 | (b) Providing, fabricating & supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4 mm thick aluminium composite panel material consisting of 3 mm thick FR grade mineral core sandwiched between two aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face 1 and polymer (service) coating on face 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. |
| 152 | (c) The fastening brackets of aluminium alloy 6005 T5 / MS with Hot Dip galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing. The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection |
| 153 | of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium items. The contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete as per item description as specified as per the approved shop drawings and as directed by the Engineer-in-Charge. |
| 154 | Note: For the purpose of payment, only the actual area on the external face of the curtain wall with aluminum composite panel cladding (including width of groove) shall be measured in sqm. upto two decimal places. |
| 155 | Wiring for group control light / fan point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 1 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc., as required complete all as specified and directed. |
| 156 | Wiring for circuit / submain wiring alongwith earth wire with 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required complete all as specified and directed. |
| 157 | Wiring for circuit / submain wiring alongwith earth wire with 2 x 4 sq.mm + 1 x 4 sq.mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required complete all as specified and directed. |
| 158 | Wiring for circuit / submain wiring alongwith earth wire with 4 x 6 sq.mm + 2 x 6 sq.mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required complete all as specified and directed. |
| 159 | Wiring for circuit / submain wiring alongwith earth wire with 4 x 10 sq.mm + 2 x 6 sq.mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required complete all as specified and directed. |
| 160 | Supplying and fixing modular switch 6A one way on the existing modular plate & switchbox including connections but excluding modular plate as required complete all as specified and directed. |
| 161 | Supplying and fixing modular switch 16A on the existing modular plate & switchbox including connections but excluding modular plate as required complete all as specified and directed. |
| 162 | Supplying and fixing modular socket 2 module 3 pin 6A on the existing modular plate & switchbox including connections but excluding modular plate as required complete all as specified and directed. |
| 163 | Supplying and fixing modular socket 2 module 3/5 pin 16A on the existing modular plate & switch box including connections but excluding modular plate as required complete all as specified and directed. |
| 164 | S&F in replacement ceiling rose two to three terminal surface backelite type AC 50 HZ 230 Volt, complete all as specified and directed. |
| 165 | Supplying and fixing 3 Module (100 mm x 75 mm), GI box alongwith modular base & cover plate for modular switches in recess etc., as required complete all as specified and directed. |
| 166 | Supplying and fixing 8 Module (125 mm x 125 mm), GI box alongwith modular base & cover plate for modular switches in recess etc., as required complete all as specified and directed. |
| 167 | Supplying and fixing 12 Module (200 mm x 150 mm), GI box alongwith modular base & cover plate for modular switches in recess etc., as required complete all as specified and directed. |
| 168 | Supplying and fixing cable end box (loose wire box) for 8 way, double door SPN MCB DB suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface / recess, complete with testing and commissioning etc., as required complete all as specified and directed. |
| 169 | S&F in replacement, recess mounting 42 W, 2 x 2 LED luminaire suitable for Armstrong / Grid ceiling with high performance LEDs complete with all accessories including driver pre-wired complete all as specified and directed. |
| 170 | S&F in replacement, recess mounting 28W, 4 x 1 LED luminaire suitable for Armstrong / Grid ceiling with high performance LEDs complete with all accessories including driver pre-wired complete all as specified and directed.Note for Sl item No 153 & 154: a) Any accessories or frame required for proper fixing of light fixture will be provided by contractor without any extra cost.b) If ceiling cutting required skilled labour will be provided by contractor for proper fixing and finish after installation of light without any extra cost. |
| 171 | S&F in replacement, basic all purpose surface or wall mounted 20W LED batten with polycarbonate housing and integrated electronic driver complete all as specified and directed. |
| 172 | S&F, sheet metal enclosure for pre-wired distribution board double door, powder coated VTPN, 8 way with MCCB, three phase 415 volt with 100 Amps rated tinned electrolytic copper bus bar with neutral link complete all as specified and directed. |
| 173 | Supplying and fixing MCB SPN, 5 A to 32 A rating, 240/415 V, 10 kA, 'C' curve, miniature circuit breaker suitable in the existing MCB DB complete with connections, testing & commissioning etc., as required complete all as specified and directed. |
| 174 | S&F, MCB SP, 5 A to 32 A rating, 240/415 V, 10 kA, 'C' curve, miniature circuit breaker suitable in the existing MCB DB complete with connections, testing & commissioning etc., as required complete all as specified and directed. |
| 175 | S&F, MCB three pole neutral (TPN) 10 kA, 32 Amps capacity 240 Volts 50 HZ complete all as specified and directed. |
| 176 | S&F, CRCA sheet metal enclosure with metal clad plug and socket single pole and neutral enclosure 240V with a two pin and earth plug and socket complete with one single pole MCB 20A complete all as specified and directed. |
| 177 | S&F, 2 loop main control panel an addressable analogue type fire control panel with zonal indication with battery power pack and testing complete fire control panel complete all as specified and directed. |
| 178 | Supply and install, auto dialing system (E-dialer) suitable for addressable type fire panel system consisting of stronge capacity of 15 to 20 telephone numbers programmable type, including connection to the existing fire alarm panel and connecting to the fire station with demonstration complete all as specified and directed. |
| 179 | S&F, multi detector (Photo-electric Smoke + heat) complying with and type certified to EN-45 with heat and smoke combination complete all as specified and directed. |
| 180 | S&F, manual call point suitable for analogue addressable type fire alarm system complete all as specified and directed. |
| 181 | S&F, new electric sounder cum strobe suitable for addressable type alarm system complete all as specified and directed. |
| 182 | S&F, beam master detector with transmitter and receiver (add power supply unit & module) complete all as specified and directed. |
| 183 | S&F, laying 2 core 1.5 Sqmm PVC sheathed armoured copper conductor cable 1100 Volts grade FRLS cable complete all as specified and directed. |
| 184 | S&F, rigid steel conduit, welded of 20 mm dia to the wall surface using clips of necessary size complete all as specified and directed. |
| 185 | S&F, an integrated a public address and talk back facility alongwith 06 Nos loud speakers with minimum 1KW and necessary connected accessories complete all as specified and directed. |
| 186 | S&F, fire alarm sounders / sirens electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 meter with sound output variation of + 5 DB for 3500 meter range complete all as specified and directed. |
| 187 | S&F, fire exit route indicator board with in-built LED luminaire complete set complete all as specified and directed. |
| 188 | S&F, repeater panel suitable for two loop addressable type panel complete all as specified and directed. |
| 189 | M&L for laying 6 core 1.5 Sqmm armoured, multistranded copper cable complete all as specified and directed. |
| 190 | S&F, short circuit isolators complete all as specified and directed. |
| 191 | S&F, RCCBs for earth leakage, short circuit and over load protection of capacity 63Amps and leakage current upto 300 mA complete all as specified and directed. |
| 192 | S&F, fire hydrant landing valve type 'A' (single head outlet) of 63mm dia conforming to IS-5290 complete all as specified and directed. |
| 193 | S&F, fire hydrant stand post with provision of single outlet conforming to IS-908 complete all as specified and directed. |
| 194 | S&F, Hose box made of 18 gauge MS sheet 800mm x 600mm x 50mm with double door with 4 mm thick glass and door frame made of 16 gauge MS sheet painted fire red outside and brilliant white inside yard complete all as specified and directed. |
| 195 | S&F, Hose box made of 18 gauge MS sheet 800mm x 600mm x 50mm with double door with 4 mm thick glass and door frame made of 16 gauge MS sheet painted fire red outside and brilliant brilliant white inside yard for internal complete all as specified and directed. |
| 196 | S&F, 63 mm dia 15 meter long hose conforming to IS-636 complete with male and female coupling conforming to IS-903 complete all as specified and directed. |
| 197 | S&F, hose reel of 20 mm dia and 30 meter length conforming to IS 5132 complete all as specified and directed. |
| 198 | S&F, Pressure switch in M.S. pipe line including connection as required complete all as specified and directed. |
| 199 | S&F, gun metal fire brigade inlet connection for connecting to external fire hydrant ring main consisting of two nos 63 mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet complete with all accessories complete all as specified and directed. |
| 200 | S&F, electric motor siren conforming to IS-1941 suitable for three phase 415 V supply with motor not exceeding 3.75 KW power and able to deliver 143 DB noise level complete all as specified and directed. |
| 201 | S&F, MS flanged pipe 100mm NB heavy duty for multi storied building duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer complete all as specified and directed. |
| 202 | S&F, non raising type sluice valve both ends flanged with CI body, ISI marked, IS-14846, pressure PN 1.6 with SS spindle, clamps and check nuts, operating hand wheel for the size of 100mm dia complete all as specified and directed. |
| 203 | S&F, non return sluice valve of size 100 mm dia complete all as specified and directed. |
| 204 | S&F, 50mm bore steel water tubing, medium grade, ISI marked, galvanized, including all fittings such as bends, tees, elbows, reducers, unions, plugs, sockets etc., laid in trenches or fixed to walls and ceilings or concealed in walls, ducts / ceilings or laid in floors complete all as specified and directed. |
| 205 | S&F, 25 mm bore steel water tubing, medium grade, ISI marked, galvanized, including all fittings such as bends, tees, elbows, reducers, unions, plugs, sockets etc., laid in trenches or fixed to walls and ceilings or concealed in walls, ducts / ceilings or laid in floors complete all as specified and directed. |
| 206 | S&F in repairs, 50 mm dia gun metal, globe or gate valves with iron wheel head, ISI marked screwed both ends for iron / GI pipe and fixed complete all as specified and directed. |
| 207 | S&F in repairs, 25 mm dia gun metal, globe or gate valves with iron wheel head, ISI marked screwed both ends for iron / GI pipe and fixed complete all as specified and directed. |
| 208 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation etc., or for shafts, wells, cesspits, manholes, pier holes etc., not exceeding 10 sq m on plan and not exceeding 1.5 m in depth and getting out in hard/dense soil complete all as specified and directed. |
| 209 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in soils complete all as specified and directed. |
| 210 | Removing excavated material (soils) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 211 | M&L for filling approved river sand in trenches for sand cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc., complete all as specified and directed.Note: Thickness of sand cushion after punning down shall be measured as 18cm for payment purpose. |
| 212 | Supplying and laying reinforced precast concrete cable cover, class LV, type I, flat, size 250 mm x 150 mm x 40 mm complete all as specified and directed. |
| 213 | Cuttings existing DI/CI/MS pipe line of 150/100 mm dia for insertion of new tees, collars for branch connections etc., into 100mm dia complete all as specified and directed. |
| 214 | S&F, booster motor pump for 440V, 3 phase, 50Hz, conforming to IS-12469:1988 with CI casing bronze impeller and stainless steel shaft mounted on heavy duty bearing suitable for 440V 3 phase 50Hz 30m head 450 LPM discharge complete all as specified and directed. |
| 215 | Supplying, laying, jointing, testing & commissioning 1100 volts grade, 16 Sqmm 4 core LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 galvanized steel strip or wire armoured, heavy duty, electric cables with multistranded aluminium conductor laid in trenches / passing through pipe / duct / road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including taking down unserviceable cable complete all as specified and directed.Note: Earthwork excavation, sand cushioning GI pipe and cable protection will be measured and paid separately. |
| 216 | Supply, install, testing & commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on the floor, separate cable alley for all the feeders, suitable for 400 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3.15mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement, prewired with suitable size of PVC insulated copper conductor, copper control wiring of required size of instruments and duly powder coated on outside and inside |
| 217 | including air ventilation for heat of dissipation, suitable size knock out holes for cable of glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B2 using 40mm graded stone aggregate one meter around of panel board, cable gland and lugs for incoming and outgoing cable etc., independent multi layer chambers to accommodate including the following accessories:-(a) MCCB 4 pole, 63 Amps with adjustable thermal and magnetic settings, 16 KA rupturing capacity at 415 volt, conform to IEC-60947-II / IS-13947-II - 01 No (incoming). |
| 218 | (b) MCCB 4 pole, 40 Amps with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415 volt, conform to IEC-60947-II / IS-13947-II - 03 No (outgoing).(c) DOL starter in sheet metal enclosure suitable for maximum motor output at 415 V, 3 phase 7.5 HP - 02 Nos.(d) Digital Ammeter 0 to 200 Amps with selector switch & CTs - 01 set.(e) Digital Voltmeter 0-500 Volts with selector switch, 7 position and 2A HRC fuses / MCBs - 01 set.(f) Indicator lamp R, Y, B LED type with 03 Nos of 2 A HRC fuses - 01 set. |
| 219 | M&L for earthing complete with GI earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including GI earth strip of 25 x 5 mm by means of rivetting and brazing and protected by GI pipe 32mm dia light grade upto the test point upto 7.5 mtr, including providing alternate layers upto full volume of pit by charcoal dust and common salt, watering pipe of 50 mm dia medium grade GI pipe upto the top of the plate having funnel complete and RCC cover, connecting to the test point and testing on ground complete and |
| 220 | including excavation and earth work in any type of strata and cleaning of site in MES SSR Part-I complete all as specified and directed.Note: Earth strip beyond 7.5 m, if required shall be measured and paid separately under respective item of Schedule. |
| 221 | S&F, aluminum strip 25 x 3 mm complete with saddles and fixing screws for roof / down conductor on porcelain / epoxy spacer insulator or fixed in GI pipe complete all as specified and directed. |
| 222 | S&F, porcelain / epoxy white / brown / green spacer insulator with one GI stud bolt with nut and washer with necessary drilling for bolt hole for holding / fixing roof conductor / down conductor of lightning conductor complete all as specified and directed. |
| 223 | Supply & erect, GI medium grade pipe of 20 mm dia for fixing air termination rod and earth strip on roof complete all as specified and directed. |
| 224 | S&F, single pointed air termination aluminium rod 12 mm dia 300 mm long with fixing arrangement complete all as specified and directed. |
| 225 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to pole or any other indicated situation for loop earthing etc., as required 25 x 5 mm GI earth strip complete all as specified and directed. |
| 226 | S&F, test point terminal block made of gum metal or phosphorus bronze size (75 x 75 x 25 mm) drilled and screwed including 03 Nos 8 mm dia 25 mm long hex head screw complete all as specified and directed. |
| 227 | S&F, GI pipe 40 mm dia light grade for protection of GI earth strip laid in trenches or fixed on walls with necessary clamps complete all as specified and directed. |
| 228 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc., with charcoal / coke and salt as required complete all as specified and directed. |
| 229 | S&F, testing Advanced Earthing System A) Advance Earthing Electrode:Copper banded rod (tested as CPRI) 76.3 MM OUTER DIA X 3 MTR LENGTH COPPER BONDED (250MICRONS COATED) PIPE, FILLED WITH CONDUCTIVE CRYSTALLINE COMPOUND, FITTED WITH 50 X 6 X 3100 MM COPPER BONDED STRIP.B) HIGH GRADE EARTHING compound (NABL & IEC 62561-7 TESTED)eco friendly maintenance free earthing compound to enhance soil conductivity packed in eco-friendly HDPE laminated paper bags 25 Kgs x 3 paper bag. (0.19 OHMS PER MTR) |
| 230 | (C) Concrete Inspection Pit: Heavy duty, precast concrete earth pit inspection chamber with cover size 320 mm (W) x 320 mm (L) x 192 mm (H), load bearing capacity : 5000 Kgs.(D) Installation: Installation of each earth pit. |
| 231 | Earth continuity conductor with 25 x 5 mm copper strip fixed to wall on batten or recess or chases with necessary epoxy insulators or buried in ground or drawn in conduit / pipe / wall or fixed to poles or any other indicated situation for loop earthing complete all as specified and directed. |
| 232 | S&F, epoxy spacer insulator with one GI stud bolt with nut and washer with necessary drilling for bolt hole for holding / fixing earth continuity conductor complete all as specified and directed. |
| 233 | Supply, installation, testing & commissioning of silent type (DG) Diesel Engine driven generating set confirming to CPCB-IV plus having prime power rating of 100 KVA / 80 KW at a power factor of 0.8 lagging, 415 volts, AC 3 phase, 4 wire, 50Hz, 1500 RPM, alternator directly coupled with diesel engine, mounted on common base frame complete with Acoustic enclosure with inbuilt fuel tank, fuel line & accessories, PCC foundation work as per manufacturer's instructions, anti vibration pads, OEM recommended standard panel showing standard accessories and comprising the following: - |
| 234 | (A) ENGINE (Prime Mover): Diesel Engine, multi stroke, inline multi cylinders, liquid / water cooled, turbo charged, after cooled, confirming to IS, capable of giving adequate 1500 RPM to drive alternator capable of delivering minimum 100 KVA (80 KW) at outdoor atmospheric conditions at Hyderabad and capable of taking 10% overload for one hour after 12 hours of continuous operation, complete with all standard fittings / fixtures.(i) Fly wheel housing and fly wheel.(ii) Air cleaner dry type replaceable element type with restriction indicator. |
| 235 | (iii) Electronic governor.(iv) Dual fuel filter including water separator, fuel pump, fuel injection pump (FIP) and injectors(v) Radiator, fan & water pump assembly.(vi) Forced lubrication - pump, lub oil filter & lub oil cooler.(vii) Exhaust silencer.(viii) Exhaust gas driven turbo charger.(ix) First fill lub oil and coolant and diesel during commission and testing. |
| 236 | (B) ALTERNATOR: Alternator shall be self excited, self regulated, brushless for 200 KW / 160 KVA at the speed of 1500 RPM at 415 volts, 50 Hz, 3 phase, 4 wire system with advance electric voltage regulator to ensure high voltage accuracy with + 1% with class H insulation and IP 23, directly coupled with engine through flexible coupling and confirming IS-4722.(C) BASE FRAME & FOUNDATION: Common base frame for engine & alternator made from structural steel channel. PCC foundation including adequate number of suitable anti-vibration pads all as per the recommendation of manufacturer. |
| 237 | (D) ELECTRICAL STARTING SYSTEM: Electric starting system with battery charging alternator and self starter including adequate number of maintenance free lead acid battery 180AH capacity including interconnecting cables / leads with terminals complete with starting / stopping switch and voltmeter. |
| 238 | (E) ACOUSTIC ENCLOSURE: Corrosion resistant, acoustic and weather proof enclosure with durable industrial locking system on doors, doors with gasket made of high quality EDPN material with arrangement for fresh air intake for cooling of engine & alternator, extraction and discharging of hot air to the atmosphere, made out of CRCA sheet with 11 tank pretreatment process and UV resistant powder coating and high quality noise absorbent & fire retardant grade acoustic insulation material (Rockwool) complying to IS 8183 well suitable for 100 KVA DG set to reduce noise level to 75db (A), measured at 1.00 meter distance under field conditions, confirming to CPCB IV plus norms. |
| 239 | Enclosure will have inbuilt base frame mounted fuel tank of capacity min to run the DG set for 08hrs fabricated out of 4 SWG MS sheet mounted inside the enclosure alongwith fuel piping from tank to engine capacity as recommended by OEM with drain valve, air vent, inlet, outlet connection and suitable exhaust pipe duty cladded with glass wool and covered with aluminium sheet and exhaust trail pipe with muffer.(F) DG SET MOUNTED INSTRUMENT PANEL: Fitted with & having digital display for the standard parameters as recommended by OEM. |
| 240 | Note: (i)(a) DG set shall be installed over the foundation as recommended by OEM however minimum 1.0 m space should be available all around the DG set and height of plinth shall not be less than 0.6m. Any civil work including miscellaneous work not covered under the scope of the work but required for satisfactory completion of job deemed to be inclusive in the unit quoted rate.(b) Contractor shall submit the detailed specification, particular model, make and literature of DG set alongwith drawings for approval of GE before placing of order. |
| 241 | (c) The switch gear, accessories and other items to be incorporated into AMF panel to be got approved from GE before placing the order.(d) The contractor shall arrange diesel / oil / coolant and artificial load for testing for testing, recording readings of DG set at site. The cost deemed to be included in the quoted rate.(e) Operation & maintenance catalogue, overhauling manual, spare parts list will be provided as per manufacturer standard practice.(ii) Output from alternator to panel would be through LT UG cable of suitable capacity (will be measured and paid separately under respective item of schedule) for DG set and termination at alternator end should be suitable for necessary termination and connection. |
| 242 | AMF CONTROL PANEL: OEM made cubicle type floor mounted panel board, indoor type made out of 2mm thick CRCA sheet for load bearing member and doors and covers made out of 1.6 mm thick CRCA sheet, front opening type, protection class IP-52, duly powder coated RAL 7035 (not less than 50 micron) after seven tank process, having aluminium bus bar of 200 Amps capacity for four poles with all standard switch gear and protection, internal wiring of adequate size PVC insulated multistranded copper conductor cable and consisting of following: - |
| 243 | (i) Microprocessor based four pole MCCBs for incoming and outgoing of rupturing capacity 35/36 KA.(ii) Heavy duty Power contactors, 160A, 415 volts AC 3 duty for incoming and outgoing complete with all accessories and control cabling of copper conductor. |
| 244 | M&L for earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 25 x 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point / equipment all as specified or indicated including testing on completion all as specified and directed. |
| 245 | Supply, install, testing & commissioning of ON LINE UPS 20 kva, 3 Phase input and 3 phase output, 30 min backup time 360 V with isolation transformer including external battery cabinet 1 UPM. (uninterrupted power module) comprising of battery suitable for 360 V/440 V and the UPS shall of key features such as: -(a) DSP technology with 1 GBT based inverter.(b) Smart LCD display for real time information.(c) CVCF (constant voltage constant frequency) operational with battery.(d) Adjustable battery in all 360 V modules. |
| 246 | (e) Innune to reverse phase sequence & no neutral operation.(f) Hot standby, cold start features available.(g) Built in maintenance bypass & static bypass switches.(h) Configuration output voltage setting.(j) Inbuilt charger of 20 Amps, parallel redundancy and battery reverse protection in all 360 volts.(m) Alarm mute mode and SNMP card (operational).(n) Space vector modulation & IGBT technology.(o) Advanced thermal protection of IGBT.(p) Power walk in upto 60 M sec.(q) Scalable upto 3 UPS.(r) Common battery configuration. |
| 247 | (s) Phase sequence protection.(t) Advance battery management.(u) Capacitor life minimum 15 years.(v) Built in all safety & protection mechanism. |
| 248 | Supply, installation, testing & commissioning of 2 TR capacity 230V, 50Hz, single phase split type air conditioning unit, 5 star rating, inverter type complete with drive motor, air cooled condenser with all accessories, varied speed and dual rotary compressor, including fixing the outdoor units as per manufacturer's recommendation and fixing of indoor (high wall) unit on wall, providing and marking interconnection including sufficient length refrigerant piping with nitrile rubber insulation and control cable from indoor unit to outdoor unit upto a distance of 3.0 mtr, power cabling (max 3.0 mtr from isolator / enclosure) to unit, first charging of |
| 249 | refrigerant gas (R32) including cordless remote control unit, drain piping of 25 mm dia for connecting drain lines from indoor unit to maximum of 3.0 mtr to nearest drain points, outdoor support stand etc., complete all as specified and directed. |
| 250 | Supply & install, cassette type units indoor / outdoor complete with cordless remote control unit, twin rotary compressor, single phase units 220 V/ 240 V, 50 Hz of capacity of 4 TR, BEE 4 star rated complete all as specified and directed. |
| 251 | S&F, automatic electronic voltage stabilizer of 5.0 KVA capacity, wall mounting type having features such as intelligent time delay system, low and high voltage cut out protection, latest IC technology to protect from power fluctuations, thermal over load protection, wide input variation between 170 V to 270 V with output voltage stabilized at 220 V to 240 V with accuracy of + 2.5% suitable for split type air conditioner complete all as specified and directed. |
| 252 | S&F, Visiontek embedded Linux based Aadhaar Biometric attendance system with L1 fingerprint scanner with warranty 03 years complete all as specified and directed. |
| 253 | S&F, MATRIX COSEC VEGA FAXQ embedded Linux based Biometric attendance complete device with 01 year warranty complete all as specified and directed. |
| 254 | S&F, Biometric attendance device with 01 year warranty complete all as specified and directed. |
| 255 | S&F, modular RJ 11 socket, 1 module, including connected items for fixing in flush box, modular plate and junction box complete all as specified and directed. |
| 256 | S&F, rigid non-metallic PVC conduit 40mm dia exclusive of boxes (junction / terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc., complete all as specified and directed. |
| 257 | S&F, 5MP IR Bullet Camera complete all as specified and directed. |
| 258 | S&F, 5MP Dome Camera complete all as specified and directed. |
| 259 | S&F, 2MP IR Dome PTZ with 25 X zoom complete all as specified and directed. |
| 260 | S&F, 16 channel NVR with 4K support and 2 HDD slot complete all as specified and directed. |
| 261 | S&F, 10 TB HARD DISK (60 DAYS BACKUP) complete all as specified and directed. |
| 262 | S&F, 43 INCH TV complete all as specified and directed. |
| 263 | S&F, 8 PORT POE SWITCH complete all as specified and directed. |
| 264 | S&F, 6U RACK complete all as specified and directed. |
| 265 | S&F, 4U RACK complete all as specified and directed. |
| 266 | S&F, WIRELESS MOUSE complete all as specified and directed. |
| 267 | S&F, HDMI CABLE 10 MTR complete all as specified and directed. |
| 268 | S&F, SPIKES complete all as specified and directed. |
| 269 | S&F, CAT 6 CABLE BUNDLE complete all as specified and directed. |
| 270 | S&F, CAMERA BACK BOX complete all as specified and directed. |
| 271 | INSTALLATION & COMMISSIONING CHARGES for all CCTV system from Sl item No 224 to 238 |
| 272 | S&F, modular RJ 45 socket, 1 module, including connected items for fixing in flush box, modular plate and junction box complete all as specified and directed. |
| 273 | Excavation over areas not exceeding 1.50 m deep and getting out in hard / dense soil complete all as specified and directed. |
| 274 | M&L for PCC 1:4:8 cement concrete type D2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed. |
| 275 | M&L for RCC design mix M-25 as in foundations including rafts, footings, foundation beams, plinth beams, bases for columns etc; basement slabs, underreamed piles and mass concrete complete all as specified and directed. |
| 276 | M&L for RCC design mix M-25 as in column, pillar pier, post and structs etc; complete all as specified and directed. |
| 277 | M&L for mild steel TMT bars 5 mm dia and over, upto and including 10 mm dia in stirrups, spacers and binders complete all as specified and directed. |
| 278 | M&L for mild steel TMT bars 8 to 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with MS wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed. |
| 279 | Removing excavated soil material to a distance exceeding 250 m but not exceeding 500 m and depositing where directed at a level not exceeding 1.50 m above starting point complete all as specified and directed. |
| 280 | Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams and similar work; vertical or to batter complete all as specified and directed. |
| 281 | Formwork to soffit of suspended slab such as roof slab complete all as specified and directed. |
| 282 | M&L for RCC design mix M-25 as in slab supported on wall, beam column etc; complete all as specified and directed. |
| 283 | M&L for Mild steel Frame work as in post of angle with gusset plate rails braces etc, confirming to Fe-410 grade E-250 complete all as specified and directed. |
| 284 | S&F, rotational moulded polyethylene water storage tanks 20000 ltrs capacity (cylindrical vertical with closed top, hoisted and fixed in position complete all as specified and directed. |
| 285 | Earthing complete with copper plate 60 x 60 cm x 3.15 mm thick electrode and 20 x 3 mm thick, copper strip buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. |
| 286 | S&F, epoxy spacer insulator with one GI stud bolt with nut and washer with necessary drilling for bolt hole for holding / fixing earth continuity conductor complete all as specified and directed. |
| 287 | Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out in hard / dense soil complete all as specified and directed. |
| 288 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres complete all as specified and directed. |
| 289 | Providing, laying, spreading & compacting graded stone aggregate (size range 53 mm to 0.075 mm) to Wet Mix Macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions. |
| 290 | M&L for 100 mm thick PCC 1:4:8 type D2, using 40 mm graded aggregate as in floors complete all as specified and directed. |
| 291 | M&L for 100 mm thick PCC 1:2:4 type B1, using 20 mm graded aggregate as in floors, finishing cement concrete surface even and smooth without using extra cement complete all as specified and directed. |
| 292 | Providing and applying crystalline mortar by mixing in the ratio of 4.5 : 1 (4.5 parts crystalline mortar : 1 part water) for the treatment of faulty construction joints, cracks, tie rod holes and spalled & honeycombed surface of RCC underground structures like basement, water tanks, bridge deck etc., to ensure water tightness. The crystalline mortar shall conform to the EN 15043 having compressive strength class R4 ≥45 MPa and adhesive bond strength class R3 ≥ 1.5 MPa. The work shall be carried out all complete as per specification and the direction of the Engineer-in-Charge. |
| 293 | The product performance shall carry guarantee for 10 years against any leakage for sealing cracks and faulty construction joints, routed out / making U-shape groove size 25 x 25 mm and then primed the area with integral crystalline slurry @ 0.05 kg/RM and while the surface is tacky filled the groove upto surface with crystalline mortar @ 1.50 kg/RM. Once crystalline mortar is touch dry then finally applied two coats of integral crystalline slurry @ 0.05 kg/RM per coat. |
| 294 | Supplying, testing & commissioning 120 Sqmm 3.5 core, 1100 volts grade, LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 galvanized steel strip or wire armoured, heavy duty, electric cable with multistranded aluminium conductor laid in trenches / passing through pipe / duct / road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type complete all as specified and directed. |
| 295 | Supplying, testing & commissioning 50 Sqmm 3.5 core, 1100 volts grade, LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 galvanized steel strip or wire armoured, heavy duty, electric cable with multistranded aluminium conductor laid in trenches / passing through pipe / duct / road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type complete all as specified and directed. |
| 296 | Supplying, testing & commissioning 35 Sqmm 4 core, 1100 volts grade, LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 galvanized steel strip or wire armoured, heavy duty, electric cable with multistranded aluminium conductor laid in trenches / passing through pipe / duct / road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type complete all as specified and directed. |
| 297 | Supply, install, testing & commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alloy for all the feeders, suitable for 440 Volts, 3 Phase 4 wire 50 Hz AC supply system, conforming to IS, IP-54 class protection and made of 3 mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65 mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 300 Amps rating for phase and neutral 4 strips with colour |
| 298 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories: -a) Aluminium bus bar suitable capacity TPN, full for phase and neutral with colour code PVC sleeves - 01 Job. |
| 299 | b) LED RYB indicating lamps - 01 set.c) LED Ammeter and voltmeter with necessary CTs and display of required rating.d) MCCB 200 Amps, 4 pole, 36 KA, 415 Volts - 01 No (incomer).e) MCCB 125 Amps, 4 pole, 25 KA, 415 Volts - 02 Nos (outgoing).f) MCCB 100 Amps, 4 pole, 25 KA, 415 Volts - 02 Nos (outgoing).g) Panel wiring with PVC insulated unsheathed single core, 1100 Volts grade cable with copper conductor, multi stranded of suitable size - 01 Job.h) Interconnection of busbar with MCCB, contactor with suitable size aluminium bus bar - 01 Job. |
| 300 | j) Provisioning of cable glands and cable lugs for all incoming and outgoing cables & connecting the earthing to an earthing test point to main switch board as specified and testing on completion - 01 Job. |
| 301 | Supplying and installing, 300 mm x 50 mm x 1.6 mm thick size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5% joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc., as required complete all as specified and directed. |
| 302 | Demolition / breaking up drain pipes (salt glazed stone ware) 150 mm bore, jointed in cement mortar of any description complete all as specified and directed. |
| 303 | Earth work in excavation by mechanical means (hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sqm on plan) in all kinds of soil including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil within a lead of 50 m complete all as specified and directed. |
| 304 | Providing, laying and jointed glazed stoneware pipes 150 mm dia class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc., complete all as specified and directed. |
| 305 | Providing and laying in position cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) of specified grade excluding the cost of centering and shuttering - all work upto plinth level complete all as specified and directed. |
| 306 | M&L for rendering 15 mm thick in CM 1:6 on fair faces of brick work or concrete surfaces, finished even and smooth without using extra cement complete all as specified and directed. |
| 307 | Providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25 of size 1000 x 450 x 50 mm, reinforced with 8 mm dia 04 Nos longitudinal and 09 Nos cross sectional TMT hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with MS flats of size 50 mm x 1.6 mm complete all as specified and directed. |
| 308 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering of 1:3:6 (1 cement : 3 coarse sand derived from natural sources : 6 graded stone aggregate 40 mm nominal size derived from natural sources) complete all as specified and directed. |
| 309 | M&L for Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with cement mortar 1:6 (1 cement : 6 coarse sand) complete all as specified and directed. |
| 310 | M&L for PCC 1:2:4 (1 cement : 2 coarse sand derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources), type B1 as in coping including necessary formwork, weathering, slightly rounded or chamfered angles and throating complete all as specified and directed. |
| 311 | Extra for forming fair finished to drain or channel 60 to 90 cm inner girth in cement concrete using extra cement including forms, moulds etc., complete all as specified and directed. |
| 312 | M&L for rendering 20mm thick in CM 1:4 over concrete / stone masonry surfaces and finished the surface even and smooth (without using extra cement) complete all as specified and directed. |
| 313 | Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe-500 grade @ maximum 100mm c/c on both ways, neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick, 100 mm wide MS sheet duly painted over priming coat, reinforcement to be welded at edges with MS sheet and providing 02 Nos. 12 mm dia bar for hooks including cost of cartage, all leads & lift, handling at site etc., as and where required complete all as specified and directed. |
| 314 | Providing and fixing on wall face unplasticised rigid PVC rain water pipes conforming to IS:13592 type 'A', including jointing with seal ring conforming to IS:5382, leaving 10 mm gap for thermal expansion, single socket pipes of 75 mm dia as in sweep hole complete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail