Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 27-03-2026 | Other Corrigendum | Other | 10-04-2026 |
| Sl. No. | Item Description |
| 1 | SUB-HEAD I : SITC OF VCB PANEL, TRANSFORMER & LT PANEL |
| 2 | SITC of Indoor-type, floor mounted,metal clad,single tier, totally enclosed and fully interlocked, fully compartmentalized, free standing, 6 kV VCB Panel with 3 Nos 800 A VCBs (1 Incomer + 2 Outgoing) as per IS 13188, as ammended upto date and as per detail specification and approved make attached ( uploaded in the specification section) , suitable for use on 6 KV, 3 Phase,50 Hz AC supply to energise 2 nos 1000 KVA Mineral Oil Type Transformers . |
| 3 | SITC of 1000 KVA, 3 Phase , Mineral Oil Type Transformer suitable for operation in 6KV/0.433 KV, 415V, 50Hz power supply, having cable end box in the HV side & provision for bus truncking at LV side and all accessories and conforming to IS 11171-1985 & IS - 2026 with latest modification (if any) & CBIP Specification and as per detail specification and approved make attached ( uploaded in the specification section) |
| 4 | MAIN LT PANEL IN THE SUBSTATION (1ST FLOOR) : - SITC of floor mounted indoor type expandable cubical MV Switchboard with ACB/MCCBs in suitable enclosure having Short Circuit withstand capacity of 31 MVA (i.e, 45 KA) for one second, fabricated by CPRI Approved panel builder as per detail specification and approved make attached ( uploaded in the specification section) (To be installed at Sub-Station bldg)[I/C 1600A 4P ACB - 2 Nos & Buscoupler 1600A 4P ACB - 1 No with electrical-mechanical Interlock, BBC 2500A 4 Bars- 2 Set, O/G : 1250A 4P ACB - 02 nos + 400A 4P MCCB- 5 NOS + 160A 4P MCCB - 1 NO] |
| 5 | MAIN LT PANEL IN THE NEUROSCIENCE BUILDING (GROUND FOOR) : - SITC of floor mounted indoor type expandable cubical MV Switchboard with ACB/MCCBs in suitable enclosure having Short Circuit withstand capacity of 31 MVA (i.e, 45 KA) for one second, fabricated by CPRI Approved panel builder as per detail specification and approved make attached ( uploaded in the specification section) [I/C 1250A 4P ACB - 2 Nos & Buscoupler 1250A 4P ACB - 1 No with electrical-mechanical Interlock, BBC 2000A 4 Bars- 2 Set, O/G : 1000A 4P ACB - 02 nos + 400A 4P MCCB - 10 NOS + 250A 4P MCCB - 12 NOS + 160A 4P MCCB - 3 NOS + 125A 4P MCCB - 3NOS] |
| 6 | SUB-PANEL AT NEUROSCIENCE BUILDING (GROUND FLOOR): - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 400A 4P MCCB -2 Nos , & Buscoupler 400A 4P MCCB - 1 No with electrical-mechanical Interlock, BBC 600A 4 Bars- 2 Set, O/G : 160A 4P MCCB - 5 NOS + 125A 4P MCCB - 5 NOS + 80A 4P MCCB - 02 nos] |
| 7 | SUB-PANEL AT NEUROSCIENCE BUILDING (1ST FLOOR): - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 250A 4P MCCB -2 Nos , & Buscoupler 250A 4P MCCB - 1 No with electrical-mechanical Interlock, BBC 315A 4 Bars- 1 Set, O/G : 125A 4P MCCB - 4 NOS + 100A 4P MCCB - 02 nos] |
| 8 | SUB-PANEL AT NEUROSCIENCE BUILDING (2ND FLOOR to 4TH FLOOR): - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 250A 4P MCCB -2 Nos , & Buscoupler 250A 4P MCCB - 1 No with electrical-mechanical Interlock, BBC 315A 4 Bars- 1 Set, O/G : 125A 4P MCCB - 5 NOS] |
| 9 | SUB-PANEL AT NEUROSCIENCE BUILDING (5TH FLOOR & 6TH FLOOR): - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 400A 4P MCCB -2 Nos , & Buscoupler 400A 4P MCCB - 1 No with electrical-mechanical Interlock, BBC 600A 4 Bars- 1 Set, O/G : 160A 4P MCCB - 5 NOS +125A 4P MCCB - 3 NOS] |
| 10 | SUB-PANEL FOR UPS AT GROUND FLOOR : - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 80A 4P MCCB -2 Nos , & Buscoupler - 100A 4P on load Changeover - 1 No with electrical-mechanical Interlock, BBC 100A 4 Bars- 1 Set, O/G : 63A 4P MCCB - 2 NOS] |
| 11 | SUB-PANEL FOR UPS AT 5TH FLOOR : - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 160A 4P MCCB -2 Nos , & Buscoupler - 200A 4P on load Changeover - 1 No with electrical-mechanical Interlock, BBC 200A 4 Bars- 1 Set, O/G : 100A 4P MCCB - 3 NOS] |
| 12 | SUB-PANEL FOR UPS AT 6TH FLOOR : - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 160A 4P MCCB -2 Nos , & Buscoupler - 200A 4P on load Changeover - 1 No with electrical-mechanical Interlock, BBC 200A 4 Bars- 1 Set, O/G : 100A 4P MCCB - 4 NOS] |
| 13 | SUB-PANEL FOR INTERNAL SUB-STATION & COMPOUND LIGHT AT SUB-STATION BUILDING : - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) (To be installed at Sub-Station bldg)[I/C 160A 4P MCCB -2 Nos , & Buscoupler - 200A 4P on load Changeover - 1 No with electrical-mechanical Interlock, BBC 200A 4 Bars- 1 Set, O/G : 125A 4P MCCB - 3 NOS + 63A 4P MCCB- 6 NOS] |
| 14 | SUB-PANEL FOR WATER PUMP ROOM : - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 160A 4P MCCB -2 Nos , & Buscoupler - 200A 4P on load Changeover - 1 No with electrical-mechanical Interlock, BBC 200A 4 Bars- 1 Set, O/G : 80A 4P MCCB - 2 NOS + 63A 4P MCCB- 4 NOS] |
| 15 | SUB-PANEL FOR FIRE PUMP : - SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 400A 4P MCCB -1 Nos , BBC 600A 4 Bars- 1 Set, O/G : 315A 4P MCCB - 2 NOS + 125A 4P MCCB - 1 NO + 63A 4P MCCB- 1 NO] |
| 16 | Making testing arrangement and submitting the test report for high voltage testing of specified voltage incl. checking & testing of all HT / LT equipments by authorized firm of Directorate of Electricity & commissioning the installation after obtaining the Approval of Directorate of Electricity.The scope shall be also included the necessary approval from Authority also. |
| 17 | SUB-HEAD II : SITC OF BUS TRUNKING ARRANGEMENT |
| 18 | Supplying, installing by suspension on ceiling , testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.[From secondary (LT) terminal of 2 nos 1000 KVA Mineral oil type transformer to 2 nos 1600A incomer ACB of LT panel board ] |
| 19 | S&F 1600A copper braided link for Transformer bushing (Secondary) to Bus duct and Busduct to Incomer ACB of LT panel as per direction of EIC. |
| 20 | SUB HEAD III - HT CABLING IN SUBSTATION |
| 21 | Supplying and laying of 1 No. 11KV (E/UE) Grade XLPE Aluminium conductor, PVC sheathed, armoured cable confirming to IS 7098 with latest ammenment of following size in the existing Masonary Open Duct as required as per approved make uploaded herewith.[ From Supplier HT Gear to Consumer HT Gear and to Transformer]. |
| 22 | 3 Core x 300 Sq.mm |
| 23 | Making heat shrinkable joints to the ends of the following XLPE HT cable at the transformer end as well as at the VCB ends supplying with necy. jointing kits, sockets, sleeves, anti-corrossive paste, wires, solders, jointing compounds, rubber sheets etc. incl. supplying of necy. tools & tackeles for crimping the end sockets, soldering irons & making of glands at the both end of the cable as per directions of EIC |
| 24 | 3 Core x 300 Sq.mm |
| 25 | SUB HEAD IV - LT CABLING FROM SUBSTATION TO OUTSIDE BUILDINGS |
| 26 | Supplying of following size PVC insulated and PVC sheathed / XLPE Aluminium Armoured power cable of 1.1 KV grade of following size. |
| 27 | 1 core 800 sqmm ( for 3phase & 1neutral, sub station panel to building main panel for raw power and sub station panel to building main panel via AMF panel for DG power ) |
| 28 | 4 core 240 sqmm |
| 29 | 4 core 150 sqmm |
| 30 | 4 core 120 sqmm |
| 31 | 4 core 95 sqmm |
| 32 | 4 core 70 sqmm |
| 33 | 4 core 50 sqmm |
| 34 | 4 core 35 sqmm |
| 35 | 2 core 10 sqmm |
| 36 | Supply & Drawing 1.1 KV Grade 7 Core 2.5 sq.mm PVC unarmoured Copper Cable from Transformer WT relay to VCB WT relay for Power & Control Supply as per direction of EIC. |
| 37 | S & drawing 1.1KV grade 2 core 2.5 sq.mm. PVC insulated F.R copper conductor from Power DB to VCB Power pack. |
| 38 | Finishing the cable end of 2.5sqmm. PVC insulated copper conductor by crimping arrangement as to G.S. |
| 39 | S& laying 240 sq. mm. single core multistrand PVC insulated flexible Aluminium cable in following manners from earth electrode to neutral earth busbar and from earth busbar to transformer neutral point as required (for transformer neutral earthing) |
| 40 | Through prelaid GI pipe protection pipe from earth electrode to earth busbar |
| 41 | Through PVC flexible pipe(reinforced) of suitable size from earth busbar to transformer neutral partly concealed in floor & partly on wall/surface with saddles etc. as required |
| 42 | Finishing the end of single core 240 Sq.mm XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials |
| 43 | Laying of 1.1 KV grade one cable above 300 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand. |
| 44 | Laying of 1.1 KV grade one cable above 150 sqmm and upto 300 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand. |
| 45 | Laying of one No. cable of 1.1 KV in underground trench 460mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. |
| 46 | Upto 4Core 35 Sq. mm. |
| 47 | Above 4 Core 35 sq.mm. to 185 Sq. mm. |
| 48 | Above 185 Sq. mm. |
| 49 | Laying of cable of 1.1 KV grade following sizes on existing cable tray/L- channel angle and binding with suitable size GI wire/or D-clamp incl. with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, as mentioned below as to GS:- |
| 50 | Above 150 sqmm |
| 51 | Laying of cable of following sizes on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting as mentioned below as to GS. |
| 52 | 4 core 95/120/upto 150 sqmm |
| 53 | 4 core 70 sqmm |
| 54 | 4 core 50 sqmm |
| 55 | 4 core 35 sqmm |
| 56 | 2 core 10 sqmm |
| 57 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials |
| 58 | 2 core 10 sqmm |
| 59 | 4core 35 sqmm |
| 60 | 4 core 50 sqmm |
| 61 | 4 core 70 sqmm |
| 62 | 4 core 95 sqmm |
| 63 | 4 core 120 sqmm |
| 64 | 4core 150 sqmm |
| 65 | 4 core 185 sqmm |
| 66 | 4core 240 sqmm |
| 67 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : |
| 68 | 2 core 10 sqmm |
| 69 | 4core 35 sqmm |
| 70 | 4 core 50 sqmm |
| 71 | 4 core 70 sqmm |
| 72 | 4 core 95 sqmm |
| 73 | 4 core 120 sqmm |
| 74 | 4core 150 sqmm |
| 75 | 4 core 185 sqmm |
| 76 | 4core 240 sqmm |
| 77 | Supply & making end termination with Brass double compression gland and finishing the end of conductor by crimping method by aluminium lugs for 800 sqmm XLPE insulated aluminium conductor cable of1.1 kv Grade as required. |
| 78 | S & F suitable angle/flat iron bracket for holding the HT/LT cables in proper place with all necy. For making hole, wellding and painting as required and rigidly fixed as per direction of the EIC. |
| 79 | Supply & Fixing of perforated GI cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia GI suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl.Incl. GI support or Al painting of MS support. |
| 80 | (i) With out angle iron support |
| 81 | 100 mm width X 50 mm depth X 1.25 mm thickness |
| 82 | 150 mm width X 50 mm depth X 1.25 mm thickness |
| 83 | (ii) With 25x25x3mm GI angle iron support |
| 84 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 85 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 86 | Supply & Fixing of perforated GI cable tray(Galvanisation thickness not less than 50 microns) bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia GI suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Incl. GI support or Al painting of MS support. |
| 87 | 100 mm width X 50 mm depth X 1.25 mm thickness |
| 88 | 150 mm width X 50 mm depth X 1.25 mm thickness |
| 89 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 90 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 91 | Supply & Fixing of perforated GI cable tray tee with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia GI suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Incl. GI support or Al painting of MS support. |
| 92 | 100 mm width X 50 mm depth X 1.25 mm thickness |
| 93 | 150 mm width X 50 mm depth X 1.25 mm thickness |
| 94 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 95 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 96 | Supply & Fixing of perforated GI cable tray cross member with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia GI suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. GI support or Al painting of MS support. |
| 97 | 100 mm width X 50 mm depth X 1.25 mm thickness |
| 98 | 150 mm width X 50 mm depth X 1.25 mm thickness |
| 99 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 100 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 101 | Supply & Fixing of perforated GI cable tray reducer with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the reducer incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Incl. GI support or Al painting of MS support. |
| 102 | 100 mm width X 50 mm depth X 1.25 mm thickness |
| 103 | 150 mm width X 50 mm depth X 1.25 mm thickness |
| 104 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 105 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 106 | For Out Door Use |
| 107 | Supply and installation of Special type of cable carrier made of 65X65X8mm thick GI angle iron channel and 65X8mm thick GI Flat. The GI cable carrier consist of 4 nos semi circular(not less than 65mm dia to hold upto 1 core 800 sq mm cable ) cable hanger made of GI Flat welded in GI angle. The Gap between two semi circular cable hanger is to be at least 75 mm.The cable carrier should be grouted in the wall by legs or fixed on beam by fast nut incl all assessories,mending goods the damages as per direction of EIC. (The cable carrier structure should be approved by EIC) |
| 108 | Supply and installation of Special type of cable carrier made of 65X65X8mm thick GI angle iron channel and 65X8mm thick GI Flat. The GI cable carrier consist of 2 nos semi circular(not less than 65mm dia to hold upto 1 core 800 sq mm cable ) cable hanger made of GI Flat welded in GI angle. The Gap between two semi circular cable hanger is to be at least 75 mm.The cable carrier should be grouted in the wall by legs or fixed on beam by fast nut incl all assessories,mending goods the damages as per direction of EIC. (The cable carrier structure should be approved by EIC) |
| 109 | SUB HEAD V - EARTHING |
| 110 | Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. |
| 111 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. |
| 112 | Earthing with 50 mm dia GI pipe (TATA-Medium) 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: [ 2(a)/G-1] |
| 113 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 114 | Insulating the 65 x 8 mm M.S. flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC. (for transformer neutral earth bus bar) |
| 115 | S&F 50 mm x 6 mm galvanized (Hot Dip) steel strip (beyond 4 Mts. For each earthing & equipment connection) incl. S & F heavy type heat shrinkable PVC sleeve protection for entire GI strip |
| 116 | S & F solid G.I wire(Hot Dip) of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. asrequired and mending good damages. |
| 117 | No.6 SWG |
| 118 | No.10SWG |
| 119 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe |
| 120 | Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S. |
| 121 | Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil. |
| 122 | Srpplying & fixing medium gauge GI Pipe (ISI-Medium) Protection with necessary fitting and jointing materials as required. |
| 123 | 80 mm GI Pipe |
| 124 | 50 mm GI Pipe |
| 125 | Supply & fixing 150x75 mm \\"C\\" channel having length of 2 mtr. each channel incl. nuts, bolts and washer etc on floor after cutting CC concrete & mending good the damages to original finish for fixing arrangement of transformer as per direction of EIC. |
| 126 | Supply & fixing 75x40 mm \\"C\\" channel having length of 2 mtr. each channel incl. nuts, bolts and washer etc on floor after cutting CC concrete & mending good the damages to original finish for fixing arrangement of HT 3 panel, LT panel as per direction of EIC. |
| 127 | Supply & fixing 75x40 mm \\"C\\" channel having length of 1 mtr. each channel incl. nuts, bolts and washer etc on floor after cutting CC concrete & mending good the damages to original finish for fixing arrangement of HT 3 panel, transformer and LT panel as per direction of EIC. |
| 128 | SUB HEAD - VI - SAFETY EQUIPMENT |
| 129 | Providing & fixing danger plates made of mild steel at least 2mm thick & vitreous enameled white on both sides & with inscription in signal red colour on front side as required. |
| 130 | High Voltage - size 250mm x 200mm |
| 131 | Medium Voltage - size 200mm x 150mm |
| 132 | Providing and fixing carbon dioxide (CO2) type fire extinguishers conforming to IS 15222-2002 and cylinders fully charged of following capacity of (4.5 Kg ) |
| 133 | S&F 5 Kg capacity gas pressure (DCP) fire extinguisher on wall with suitable iron bracket. |
| 134 | Supply and fixing safety instruction chart in word duly framed with 5mm thick glass as required (approx. Front area 1.20 sq.mt.) |
| 135 | Providing of set of 9.5 litre capacity GI bucket painted in post office red colour with prior coat of red-oxide paint and written with white paint 'FIRE' and mounted on MS angle iron frame with bracket and suitable base of appropriate size & capacity incl filling sand etc. |
| 136 | Providing First Aid Box as approved by St. John Ambulance Brigade / Indian Red Cross conforming to IS 13115-1991. |
| 137 | Supply and fixing shock treatment chart duly mounted on a wooden frame with 5mm thick glass as reqd. (approximate front area 1.20 sq.metre). |
| 138 | Providing of rubber mat 2 mtrs Length x 1 m. wide and 12mm thick to withstand 15 KV dielectric strength as per IS 15652-2006. |
| 139 | Providing of rubber mat 2 mtrs Length x 1 m. wide and 6mm thick to with stand 3.3 KV dielectric strength as per IS: 5424-1969. |
| 140 | S&F 15 KV grade Rubber Hand Gloves. |
| 141 | Supply and delivery out door type Helmet,Weight-480g minimum,size- 29 x 23 x 13 Centimeters, to give most extreme security to the head in high-hazard conditions like building destinations, businesses, workshops, side of the road, and so on from falling items, sway with different articles, trash, downpour, and electric stun.Safety Helmet is designed to provide utmost protection to the head in high-risk environments like construction sites, industries, workshops, roadsides, etc. from falling objects, impact with other objects, debris, rain, and electric shock. The headband is made of non-irritant and soft fabric to provide maximum comfort to the user.(Make-DARIT) |
| 142 | Supply of Heavy Duty Type 33 KV Grade Safety Hand Gloves reuseable type as per choice of EIC |
| 143 | Supply of Full PVC Water Proof Gumboot AS PER BIS 12254 (Bata-PVC-BI or as per choice of EIC) (Size 6-10) |
| 144 | SUB-HEAD VII : EXECUTION OF MISCLLENEOUS WORKS |
| 145 | Making masonary cable trench after cutting all sorts of soil. The inside mearsurment of trench 900 mm clear width x 900 mm clear depth by providing 250 mm thick brick work with 1st class brick cement mortorr (1:4) on both sides and bottom of the trench consisting with 100 mm thick cement concrete (1:3:6) with stone chips over a layer of jhama brick flat soling 15mm thick (1:4) cement plaster to inside wall & 3mm thick neat cement finish. |
| 146 | Making & placing split type RCC slab cover of size 1400 mm x 400 mm x 150 mm thick each in 150 mm x 80 mm x 80 mm x 6 mm thick fabricated MS channel frame with inside welded reinforcement steel rods (12mm & 10mm dia) and the slabs to be placed over masonary cable trench properly recessed on both side walls and the cover slabs shall be capable of bearing minimum 200 Metric Ton load. |
| 147 | Core cutting of 125mm thick RCC slab by suitable core cutting machine for passing necessary vertical run of Electrical Bus duct/ cables/ cable tray/ protection pipes/ earthing strip etc including mending good the damages as per direction of the EIC. |
| 148 | Cutting floor/ brick wall by suitable tools for passing electrical cables/ cable tray/ protection pipes/ earthing strip etc including mending the damages as per direction of the EIC. |
| 149 | Supply, fabrication and placing/fixing MS checkered plate made of 6mm thick incl 30mm x 30mm x 6mm MS angle iron structure welded by fixing for insert plates at 4 sides in cable trench top with 2 nos 3/8\\" TMT handle rod incl gas cutting, grinding & drilling with one coat of red laid primer and one coats of synthetic enamel paint as per direction of EIC. |
| 150 | S&D of portable dewatering Pump-motor set type - CDS308S, 1 HP, single phase, 220V AC, 50Hz, 2830 RPM, 4.9A, Insu Class - E, Head Max 18 Mtr, Discharge 18 Cu.Mtr/Hour, Delivery size 80mm / 50mm [Make : Crompton Greaves/ Aquasub Engineering/ KSB] |
| 151 | The agency must prepare & submit planned & as-built G.A. drawings and Single Line Diagrams (SLD) of the proposed Electrical power distribution system of main building and Sub-station mentioning ducts, trenches along with the cable sizes at different levels and the drawings to be made in Autocad software in standard symbols and to be presented both in softcopies and hardcopies (5 copies of each set of drawing) in A1 sheets as per direction of the EIC for the following :1. For Main building from the sending end Sub-station to the receiving end main panels of the building and from the main panel upto the SPN DB level.2. For the proposed Sub-station of Main building from HV source to Sub-Station LT panel including interconnection with other Sub-Station mentioning different LT feeder destinations.3. Earthing LC System as directed by EIC |
| 152 | Sub Head- VIII: Compound Light |
| 153 | SITC of 12.5 Mtr. HDG High Mast, 3,3 shaft thickness in MS Condition before Galvanization ,Top Section 6250 mm Bottom Section 6250 mm, Top A/F 150, Bottom A/F 360 , Base Plate 520 (O/D)x25 dimension as per manufacture design to suitable for wind speed 180 Km/hr.(50m/sec) as per IS:875 with head frame, luminaries carriage suitable to install 6-8 no 150 W led flood light fixtures lightning finial along with the other accessories like double drum SWL 350 kg winch, 6mm diameter 2 Rope system 316 Grade SS wire rope, , ERP insulated pcp sheathed trailing cable 5cx2.5 sq mm, connector, integral power tool motor0.75 HP with Plug socket PVC Board, Torque Limitor , manual handle, junction box with 6 Nos. M24x750 “I” Type Foundation Bolts as per EN-8 (Min UTS-600)A) Material grade of shaft shall be of S355JO/JR as per BSEN 10025 or Equivalent IS: 2062 grade E350 (BR)B) Materials grade of Base Plate shall be E250(BR) as per IS:2062C) Galvanization as per BSEN ISO:1461D) Fusion Welding as per ISO 3824-2:2021E) Make –Transrail/ Valmont/Bajaj/ Equivalent make Note: Following documents from manufacturer(OEM) are to be submitted to process the bills and avoid duplicity of Manufactures:1) Factory License of OEM (manufacture of Pole) with validity2) NABL Accredited Certificate of OEM (manufacture of Pole) with validity |
| 154 | 3) Raw Material Test Certificate of Pole Shaft (IS:2062 grade E-350 BR) Make of HR Coil- TATA/SAIL/JSW/JSPL/RINL4) Raw Material Test Certificate of Base Plate (IS:2062 grade E-250 BR) Make of Plate TATA/SAIL/JSW/JSPL/RINL5) Raw Material Test Certificate of bracket Pipe (IS:1161 grade) from any reputed BIS Make.6) Raw Material Test Certificate of Zinc (Zn) Make-Hindustan Zinc(Vedanta)7) Raw Material Test Certificate of Foundation bolts (EN Grade EN-8 and UTS.>600) any reputed BIS Make |
| 155 | LED Single Dome Aviation Lap Transrail Make(APUS 3.0) |
| 156 | Outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TPN contactor for the automatic switching of luminaries, power toll with 2 no 9A contactors and raise lower push button, Incoming 25 sq. mmand outgoing 4c x 16 sq mm & 3 cr. X 2.5 sq. mm cu cable |
| 157 | Construction of suitable Shallow foundation for 12.5 Mtr. High Mast with M-25 grade concrete for solar mini mast considering soil bearing capacity (SBC) 10T/sq. mtr. at 2 Mtr. depth with all materials and labour and payment made as per PWD civil schedule & as per direction of EIC. |
| 158 | Earthing with 50mm dia GI pipe 3.64 mm thick x3.04 Mtr. long and 1x4 SWG GI (Hot Dip) wire (4Mtr. Long), 13 mm dia x80 mm long GI bolts double nuts, double washers including supply and fixing 15mm dia taction (1 Mtr. Long) to be field with bitumen partly under the ground level and partly above ground level driven to an average death of 3.65 Mtr. below the ground level and restoring surface duly rammed as below for morrum Soil by GI Pipe medium Class (Tata Make) with excavation of soil for installation of earthing electrode below the ground level suitable for 3.05 mtr. Long GI Pipe |
| 159 | Erection of 12.5 Mtr. Mast and Feeder Pillar by using of lifting equipment like hydra etc. and fixing and wiring of Luminaires with 3cx2.5 sq mm flexible cable , 32 Amps 4 Pole MCBc etc.with necessary arrangement with labour cost. |
| 160 | Supply & delivery of 7 Mtr. HDG Octagonal Poles in 3mm shaft thickness in MS Condition before Galvanization with Top A/F 70 mm, Bottom A/F 135 mm, Base Plate 225x225x16 mm suitable for wind speed 180 Km/hr. as per IS:875 and 4 Nos. M20x600 “J” Type Foundation Bolts as per EN-8 (Min UTS-600) & Anti-theft locking door arrangement for safety of MCBs, Terminal etc.A) Material grade of shaft shall be of S355JO/JR as per BSEN 10025 or Equivalent IS: 2062 grade E350 (BR)B) Materials grade of Base Plate shall be E250(BR) as per IS:2062C) Galvanization as per BSEN ISO:1461D) Fusion Welding as per ISO 3824-2:2021 |
| 161 | Note: Following documents from manufacturer(OEM) are to be submitted to process the bills and avoid duplicity of Manufactures:1) Factory License of OEM (manufacture of Pole) with validity2) NABL Accredited Certificate of OEM (manufacture of Pole) with validity3) Raw Material Test Certificate of Pole Shaft (IS:2062 grade E-350 BR) Make of HR Coil- TATA/SAIL/JSW/JSPL/RINL4) Raw Material Test Certificate of Base Plate (IS:2062 grade E-250 BR) Make of Plate TATA/SAIL/JSW/JSPL/RINL5) Raw Material Test Certificate of bracket Pipe (IS:1161 grade) from any reputed BIS Make.6) Raw Material Test Certificate of Zinc (Zn) Make-Hindustan Zinc(Vedanta)7) Raw Material Test Certificate of Foundation bolts (EN Grade EN-8 and UTS>600) any reputed BIS Make |
| 162 | Erection of upto 7 Mtr octagonal GI (Hot Dip Galvanised in single dip) pole 1.6 Km from the store to work-site with foundation of M20 grade concrete for 7.0 Mtr GI Octagonal Pole with all the materials like sand, cement, stone chips, reinforcement steel, binding wire etc as relavent IS Code. soil bearing capacity at site as 10 T/sqmtr., by PCC Base foundation having (L-1000mm x W-1000mm x H-100mm) & RCC foundation having dimention (L- 500mm x W-500mm x H-1400mm) including neatly cemented finish (3mm thick) partly below and above ground level. There should be multiple alkathene pipes upto 1.2 mtrs of 50 mm dia of adequate length for distribution of incoming & outgoing cables for street light wiring as directed by EIC in the CC foundation of octagonal poles. |
| 163 | S&F 50 mm. dia 1.5 mtr. long detachable type G.I. Single arm bracket, suitable for pole head. The arm bracket shall be properly welded with 15 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC. |
| 164 | Supply & Fixing of 240V, 250 Watt LED flood lights with optic lens and polycarbonate diffuser h aving following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) h aving minimum luminous 15 efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 165 | Supply & Fixing of 240V, 90 Watt LED street lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous 14 efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] as per direction of the EIC |
| 166 | Supply & Fixing of 240V, 60 Watt LED street lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous 14 efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] as per direction of the EIC |
| 167 | Supply & Fixing of 240V, 120 Watt LED flood lights with optic lens and polycarbonate diffuser h aving following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) h aving minimum luminous 15 efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 168 | Supply & Fixing post top type decorative street light fitting of 45 watt LED(CW/WW/NW) made of spun alumminum housing polycarbonate diffuser portector with IP 65 protection for optical compartment with inbuilt dirver as per direction of EIC. |
| 169 | Supply & Fixing of 240V, 40 Watt LED flood lights with optic lens and polycarbonate diffuser h aving following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) h aving minimum luminous 15 efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [LED lamps & accessories shall have BEE certification] as per direction of the EIC |
| 170 | Supply & Fixing of hoode (outdooor) type 2mm thick CRCA sheet (total Height 1000 mm with leg),W=600 mm Depth= 450 mm (or as desired) single side opening with earh stud, on 4 pc 35mm x 35 mm (5mm thick) MS angle ,600mm Height, MS powder coated control panel box with 63A FP pole MCB isolator as I/C 240 V, 63 A Aluminium Bus bar of Dimension 2 x 20x5mm and 63A TP power contactor with 230V coil, 1 NO and 4 No. 40A DP MCB as Outgoing 24 hours programmable digital time switch (L&T make crono 67 DDTO) the internal wiring between isolator to power conductor and power conductor to TP MCB should be done by 4 Sqmm copper wire and netural wire will be 4 Sqmm copper wire also, & duly internally wired with Indicator lamp 2pc reputed make be fixed on concrete foundation atleast 100mm depth.incl making suitable base foundation for installation of pilar box with its foundation bolts. as per direction of EIC. |
| 171 | Supply & Fixing of hoode (outdooor) type 2mm thick CRCA sheet (total Height 1000 mm with leg),W=600 mm Depth= 450 mm (or as desired) single side opening with earh stud, on 4 pc 35mm x 35 mm (5mm thick) MS angle ,600mm Height, MS powder coated control panel box with 80A FP pole MCB isolator as I/C 240 V, 80 A Aluminium Bus bar of Dimension 2 x 20x5mm and 63A TP power contactor with 230V coil, 1 NO and 2 No. 32A FP MCB and 2 No. 32A DP MCB as Outgoing 24 hours programmable digital time switch (L&T make crono 67 DDTO) the internal wiring between isolator to power conductor and power conductor to TP MCB should be done by 4 Sqmm copper wire and netural wire will be 4 Sqmm copper wire also, & duly internally wired with Indicator lamp 2pc reputed make be fixed on concrete foundation atleast 100mm depth.incl making suitable base foundation for installation of pilar box with its foundation bolts. as per direction of EIC. |
| 172 | Supplying & Fixing of PVC water proof type Loop box (Make-Sintex) of size 8\\"X10\\" comprising of 2 way 63 Amp. Capacity brass stud/terminal make- AC /DC. & C-Characteristics,240V,16A SP MCB having hinged PVC top cover & 4 mm thick with rubber gasket lining,railway type mechanical locking arrangement,one NL on porcelain insulator etc. on wall as per direction of EIC. |
| 173 | S/D following sizes PVC insulated Cu wire in 20mm dia PVC rigid conduit pipe (Precision) to power points as follows incl. making connections as to G.S.:- |
| 174 | 3 x 1.5 mm² in 20mm dia PVC rigid conduit pipe |
| 175 | 2 x 4 + 1x 2.5 mm² in 20mm dia PVC rigid conduit pipe |
| 176 | Supply & drawing of 1.1 kV grade 4-core 16sqmm XLPE/Ar. Al. with 2 x 10 SWG GI Wire cable in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed as directed by EIC. |
| 177 | Supply & drawing of 1.1 kV grade 2-core 6sqmm XLPE/Ar. Al. cable with 2 x 10 SWG GI Wire in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed as directed by EIC. |
| 178 | Supply & Laying 1.1 Kv gr. 2 Core 6 mm² XLPE Ar./Al. Cable with 2 x 10 SWG GI Wire on Surface of wall as to G.S. |
| 179 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armored cables as below |
| 180 | 4 core 16 sq mm |
| 181 | 2 core 6 sq mm |
| 182 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts incl. connection to Pole earth terminal with 25x3 mm GI flats with materials & labour. (2nos per mast required) as to GS. |
| 183 | Connecting the equipments body to earth busbar incl. S & F 25 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc as per GS. |
| 184 | Sub Head- IX: INTERNAL E.I. OF SUB- STATION AND OTHER BUILDINGS |
| 185 | S&F of double door 6 way Vertical TPN MCB Distribution board with IP-42/43 protection, flushed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.INCOMING- 415 V, 125A FP MCCB 35kA -1No. OUTGOING- i) 415V 63A TP MCB 10kA & C characteristics - 4 nos. ii) 415V 6-32A SP MCB 10kA & C characteristics -6 nos. |
| 186 | S/F Double Door 6-Way TPN MCB PDB in S.S. enclosure with IP-42/43 protection flushed in wall consisting with 1 No. 63A 4-Pole Isolator, 18 nos. 32 A SP MCB as outgoing complete with DIN Channel, Neutral Bar, Earth Bar, both side cable end box and other accessories & connection with suitable size of Cu. wire with proper socketing incl. necsy.earthing attachment. as per direction of EIC. |
| 187 | S/F Double Door 2+12 way SPN MCB DB in S.S. enclosure with IP-42/43 protection flushed in wall consisting with 1 No. 40 A DP Isolator, 12 nos. 6/36 A. SP MCB as outgoing, complete with DIN Channel, Neutral Bar, Earth Bar and other accessories & connection with suitable size of Cu. wire with proper socketing incl. necy.earthing attachment. as per direction of EIC. |
| 188 | Distribution wiring in 1.1 KV grade 3x1.5 sqmm single core stranded 'FRLS' PVC insulated & unsheathed copper wire partly in 20mm size PVC rigid conduit 'FR' (Precision make) and in 19mm bore, 3mm thick polythene pipe to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board to be embedded & flushed in wall incl. mending good damages to original finish complete with 3 nos. “Ph, N & E” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. (PVC rigid conduit only for ceiling and horizontal run and Vertical run Concealed) [Av. Run 8 Mtrs.] |
| 189 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire in 19 mm bore, 3 mm thick polythene pipe complete with all accessories embedded in wall to 240 V 5A 3 pin plug point incl. S&F 240 V 5A 3 pin flush type plug socket & piano key type switch (Anchor make) incl. S&F earth continuity wire, fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3 mm thick) flushed in wall incl. mending good damages to original finish 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC (On Board) |
| 190 | Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite /perspex cover and making necessary connections as required |
| 191 | Supply & Fixing 240 V, 2nos 6A, plug socket with separate 2nos 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required |
| 192 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/ perspex cover and making necessary connections as required |
| 193 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. |
| 194 | a)100 mm |
| 195 | b)80 mm |
| 196 | Supply & fixing 4 pole MCB enclosure with 1no. 415V 63 Amp 4-pole MCB to be fixed concealed in wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per direction of E.I.C. |
| 197 | Supply & fixing 4 pole MCB enclosure with 1no. 415V 32 Amp 4-pole MCB to be fixed concealed in wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per direction of E.I.C. |
| 198 | S&F 24\\" long MS frame with both side D clamp, drilled holes made of 30x30x5mm MS angle with nuts, bolts, washers and grouted in the cement concrete on wall suitable for fixing of different 4 core 400 sqmm XLPE armoured cable complete with fastner and mending good the damages as per direction of EIC |
| 199 | S & Drawing following sizes PVC insulated FRLS Cu.wire in suitable mm dia PVC rigid conduit pipe on wall complete with all accessories incl. making connections as to G.S. :- |
| 200 | 4x35mm² + 2x25 mm² |
| 201 | 4x25mm² + 2x16 mm² |
| 202 | 4x10mm² + 2x6 mm² |
| 203 | 2 x 6mm² & 1 x 4 mm² copper wire |
| 204 | 2 x 2.5 mm² & 1 x 1.5 mm² copper wire |
| 205 | 3 x 1.5 mm² for separate plug boards |
| 206 | Finishing the end of following sizes copper wire end with dowells solderless socket by crimping method as per GS as follows:- |
| 207 | 4x35mm² + 2x25 mm² |
| 208 | 4x25mm² + 2x16 mm² |
| 209 | 4x10mm² + 2x6 mm² |
| 210 | 2 x 6 & 1 x 4 mm² copper wire |
| 211 | 2 x 2.5 & 1 x 1.5 mm² copper wire |
| 212 | Supply and Delivery of 4 feet Industrial box type single LED tube fitting incl. Supply & Delivery of 1 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification as per direction of EIC. |
| 213 | Supply and Fixing of 4 feet Industrial box type twin LED tube fitting incl. Supply & Delivery of 2 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 105 Lm/ Watt or better & 50,000 LED burning hours or more,as directed by EIC. [Mal{e- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] as per direction of EIC. |
| 214 | Fixing only single/twin LED light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed by 2 nos steel bullet fastner nut-bolt and other side connected with the suitable size of bolts and nuts incl. S&F EI conduit “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated Cu flexible wire , ceiling plate, ceiling rose where it is required and mending good damages to original finish and painting etc. |
| 215 | Supply & Fixing of 240V,24 Watt recess mounted 2'x2' LED downlight having following wattage in white powder coated pressure die cast aluminium housing , with glare free uniform illumination, suitable for 2' x 2' grid ceiling with CCT (5700K- 6500K) having minimum luminous efficiency of 120 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification]with all necessary connection as per direction of EIC |
| 216 | Supply and fixing of 24 watt 240V recess mounted round LED downlight having following wattage, in white powder coated pressure die cast aluminium housing with glare free uniform illumination, suitable for 2' x 2' grid ceiling with CCT (5700K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] with all necessary connection as per direction of EIC |
| 217 | S & F of 48'' sweep, 230V, 1-phase AC ceiling fans incl. all accss., the capacitor of fan must be P-2 type brust proof & must have safety wire directly linked from fan hook to stator of fan, complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire, as directed by EIC. [Ref.: Non Schedule & Page No.-C-3,Sl. No.-21(a)] |
| 218 | Supplying & Fixing of Box type fan clamp of 150mm dia & 80mm depth made of 16 SWG CRCA sheet with one end duly sealed by cover, properly welded, incl. S&F 12mm dia 600mm long MS rod duly bent by heat treatment at the centre position of rod to grip fan bobbin properly, incl. binding the rod and fan box with reinforcement by 22 SWG steel binding wire, incl. supplying & covering the box with alkathene sheet, placed in order to prevent concrete from entering the box. as per direction of EIC. |
| 219 | S & F of 240V, Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. as per direction of EIC |
| 220 | S&F of 230V grade 450 mm 1440 rpm sweep (18\\") wall mounting bracket fan (metal body & metal 4 blade) on wall incl. S&F of MS fastners and nut & bolts etc. as per direction of EIC |
| 221 | S&F of 230V grade 450 mm 1440 rpm sweep (18\\") pedestal fan (metal body & metal 4 blade) on wall incl. S & F of MS fastners and nut & bolts etc. as per direction of EIC |
| 222 | Supply and fixing of 240V, 9 '' 1400 rpm AC exhaust fan(EPC Make) after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of given diameter.as per direction of EIC |
| 223 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for 23 cm Exhaust fan (9\\") as per direction of EIC. |
| 224 | Supply and fixing of 240V, 12 '' 1420 rpm AC exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of given diameter. as per direction of EIC. |
| 225 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for 30 cm Exhaust fan (12\\") as per direction of EIC. |
| 226 | Supply and fixing of 240V, 15 '' , 1420 rpm AC exhaust fan(EPC Make) after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of given diameter. |
| 227 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for 38 cm Exhaust fan (15\\") |
| 228 | S & F fan down rod wire incl. necessary connection wire (2X1.5sqmm cu wire) and painting the down rod as per direction of EIC. |
| 229 | Supply of 240V Timer DB(equivalent of 2+12 way SPN Double Door DB in size) with steel sheet enclosure double door, phosphitised powder coated, neutral bar, Din Rail with IP- 43 protection comprises with 1 No.40A DP MCB('C\\" Curve,10KA),1 No.24 hours programming Time Switch( L&T/ Aproved make) with 15 min minimum switching time of any time and any day and 1no 32A contractor complete with internal wiring by suitable sizze of copper wire and Provision for earthing attachment including LED indication light for running condition with locking arrangement & including ON/OFF push button. |
| 230 | SITC of Glowsign Board (Router cutting) with liquid Acrlyic letters with adhesive on ACP Board of 3 mm Thick of suitable size to accommodate all the matters / contains as approved by the authority to be made with 25 x25 x 4 mm M.S angle Iron, 18 S.W. G square/ Round Hollow bar , Base plate (10mm Thickness) required for fixing the necessary Nuts , Bolts , Washers , supporting angle Iron , Clamp etc. and ACP Sheet on Front sides & edges only & back side to be covered by GI Sheet (with proper ventilation arrangement),All side to be moulded unifornmly, Side fabricated by Aluminium 'L' Channel , upon which elevated or box type letter made from imported liquid acrylic will be fixed. The Thickness of Acrylic will be 5 mm (for small letters) , 8mm (for Big letters) and 10 mm (for very big letters). The Back Side of the letters is covered by 3 mm thick ACP (Make- Aludecor/Alstone). The inside of the letter Supplying and Fixing of best Quality LED Lighting arrangement of fully water proof 10 nos LED light fittings of 20 watt (100 lumen/watt). The letters are sealed by exterior grade Silicon. The back side of the Board Covered by 22 S.W.G G.I sheet with Nuts & Bolts. Intensity : Same & smooth uniform throughout without any dark patch Visibility : upto 250 meters for normal eyes |
| 231 | The complete sign board would be fixed on roof of the bulding with providing necessary CC muffing , 1 no CI water proff 200x150x100 mm loop Box, 50x50x6mm MS angel for supporting the board of required length by nuts, bolts, washers etc. After drilling hols on the frame front facia. GSB would have 2 nos hinge type doors in back side to have the inside access including mending goods the damages to original finish. |
| 232 | Painting of any steel/ iron surface of the above Glow sign board with no. of coats of paints as given below with ready mixed paint/ primer of approved make and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint1st coat of aluminium paint over one coat of RO priming 2nd coat of aluminium paint over one coat of RO priming. |
| 233 | Terms and Conditions |
| 234 | a. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. |
| 235 | b. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. |
| 236 | c. If any refurbished material is supplied and installed, penal action will be taken as per existing rules. |
| 237 | The rate quoted by the manufacturer should be inclusive of cost for providing 2 years DLP after completion of work. |
| 238 | Defect Liability period 1 (One) Year |
| 239 | Rates are Inclusive GST @ 18% & LWC @ 1% Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail