| 1 | NOTE: Schedule ‘A’ Part I to VIII under Ser No. 1.01 to 1.08 are Prepriced by MES. |
| 2 | Lump sum price worked out by the Contractor for “BUILDING WORK” as listed in Schedule ‘A’ Part-I |
| 3 | Lump sum price worked out by the Contractor for “EXCAVATION AND EARTH WORKS” as listed in Schedule ‘A’ Part-II |
| 4 | Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION WORKS” as listed in Schedule ‘A’ Part-III |
| 5 | Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY WORKS” as listed in Schedule ‘A’ Part-IV |
| 6 | Lump sum price worked out by the Contractor for “PLUMBING WORKS” as listed in Schedule ‘A’ Part-V |
| 7 | Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL WORKS” as listed in Schedule ‘A’ Part-VI |
| 8 | Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY WORKS” as listed in Schedule ‘A’ Part-VII |
| 9 | Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY WORKS” as listed in Schedule ‘A’ Part-VIII |
| 10 | SCHEDULE `A' PART - IX MISC B/R & E/M ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only. |
| 11 | INTERNAL ELECTRIFICATION WORKS |
| 12 | S&F prewired VTPN Distribution board with provision for & including MCCB as incommer 100 Amp, 04 pole IP 54, 04way (for incomming MCCB & outgoing MCBs), with copper busbar for each phase, with Neutral bar, Earth bar and cable ties for cable managemet, fully insulated busbar & shrouded Neutral bars, with 100 Amps MCCB, 16 KA, 4 pole, as incomer and SP MCB's of capacity 10-32amps as outgoing complete all as specified and as directed. Note: (i) The DB shail be VTPN series. (ii) The DB shail be flush fixed and making good the distrubed surface maching with existing specifications shall be part of work no extra cost. (iii) Connection of the MCCBs and MCBs with cable shall be made through appropriate size pin/bottle type thimble properly crimped. (iv) All the vacant hoies of the DB shall be provided with biank plates of appropriate size. (v) Double continuous earth wire shall be provided tor each three phase DB from earthing mains dolly. (vi) MCCB and MCB rate considered in separate item of schedule. |
| 13 | M&L for earthing with galvanished steel earth plate electrode 600 x600 x 6.0mm thick buried directly in ground pit not less than than 3.25 mtr deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to 4.00mm dia GI wire & PVC insulated solid copper conductor of size 4mm by means of nuts and GI washers including PCC pit in PCC 1.2:4 type B-1 RCC Cover, 20mm dia (MG) GI watering pipe with funnel wire mesh and protection pipe of Gl of 15mm dia up to 7.5 Mtr length including charcoal black cotton soil as required at site to achieve the earthing result and common salt, excavation earth work etc in any type of strala complete all as shown in electrical plate No 5 of MES SSR Part 1 as specified. GI wire & 4mm dia solid conductor PVC insulated for continuity earth wire from test point to main distribution board and all as specified and as directed. Note: Rate for achieving required depth by compressor machine if required is deemed to be included on the quoted unit rate. |
| 14 | S & F RJ-11 Telephone jack singie with shutter 1M all as specified and directed by Engr-in-charge. |
| 15 | S & F TV Co axial socket 1M all as specified and directed by Engr-in-charge. |
| 16 | SEWAGE DISPOSAL WORKS |
| 17 | Providing and laying Rodent Repelent DWC ID pipe (SN8) (HDPE BLACK) confirming to IS-16098-2, 150mm nominal bore (160mm OD) laid in trenches including all accessories/fitting/jointing and testing, commissioning complete all as specified and directed. |
| 18 | EXTERNAL ELECTRIC SUPPLY WORKS |
| 19 | Supply Installation testing & commisioning of totally enclosed feeder piller box outdoor type (IP-65) fabricated out of 3.15mm thick CRCA sheet angled framed dust and vermin proof powder coated double door type (independent cabin including locking arrangement for each MCBs, bus bar chamber (enclosed) including locking arrangement complete suitable for operating on 415 Volt 50 Hz AC, supply internally wired with copper conductor, TPN bus bar of aluminium strip (4 Nos) insulated by heat shrinkable sleaves the capacity of bus bar should be 1.5 times current capacity of main incoming switch gear & clips on shrouds for joints busbar shall be designed to withstand a fault lavel at 415 Volts having legs 45cms made out of 65x65x6mm angle iron grouted on brick masonary plateform upto 30cms .Brick masonary platform should be 60 cms above the Ground Level. (i) The panel shall be front operated with cable entry from the bottom with cable (ii) Fabrication of feeder piller box to be approved by CPRI width of the panel not less than 60cmsNote:- Cost for construction of platform for panel of brick masonary work in CM 1:6 with foundation PCC 1:4:8 type D-2 including plaster work, PCC copping 1:2:4 (using 40 mm crushed stone aggerate), deemed to be included in the item rate. No extra payment will be made.(Note: This panel shall be a front operated with cable entry from the bottom .The fault with standing capacity shall be 25 KA. Earth bus shall be part of the main feeder pillar.) |
| 20 | LT panel shall comprise the following:(i) MCCB 4 Pole 160 A 36 KA - 01 No (for Incoming)(ii) MCCB 3 pole, 63 A, 415 volt 50 Hz 25 KA- 03 Nos (for outgoing)(iii) MCB SPN 40 AMPS, - 02 Nos (for outgoing).(iv) Three phase Tamper proof electronic meter 100 Amps CT Operated- 01 No(v) Digital Ammeter 0 to 1000 Amp with selector switch & suitable range of CTs - 01 No(vi) Digital Voltmeter 0 to 500 V with selector switch - 01 No(vii)LED phase indicating lamp (Set of three) - 03 Nos (RYB)(viii) Manual change over switch open execution type Frame 2 of capacity 160Amps, 415 V. 4 pole - 01 No Please Enable Macros to View BoQ information |