| 1 | BOQ Tender Inviting Authority: Executive Engineer (AC&R), AIIMS- Jodhpur Name of Work: Rate Contract for Refilling & Testing of various types of Fire Extinguishers, at AIIMS Jodhpur NIT no.: AIIMS-JDH/EE/AC&R/2025-26/04 (Second call) Name of the Bidder/ Company: NUMBER # NUMBER # S. No. Item Description Qty Unit Rate per Unit (inclusive of GST)Rs. Total Amount (inclusive of GST)Rs. A B C D E F |
| 2 | Supply, Installation, Testing & Commissioning of Bed Head Panel, wall-mounted, extruded aluminum alloy construction (minimum thickness 2 mm) with powder-coated finish, complete with the following:• Medical gas outlets, gas-specific, non-interchangeable, with NIST connection, metallic body, conforming to HTM 02-01 / EN ISO 9170-1 / EN ISO 7396-1 standards.• Combined universal electrical switch-socket units (6/16 A, with indicator), hospital-grade modular type, conforming to IEC 60601-1.• 1 no. flexible LED examination light with switch and 2 nos. data point (RJ45 CAT-6) integrated.• 1 no. equipment rail, anodized aluminum, conforming to EN 19054 / DIN 32623, for mounting medical accessories.• Copper pipe extensions of required size (BS EN 13348) brazed to outlets and terminated for connection to MGPS pipeline.• Wall bracket with mounting hardware for secure installation. |
| 3 | Horizontal type with 5 nos. medical gas outlets (O₂ – 2, VAC – 1, MA4 – 2) & 8 nos. universal electric sockets |
| 4 | Horizontal type with 3 nos. medical gas outlets (O₂ – 1, VAC – 1, MA4 – 1) & 6 nos. universal electric sockets |
| 5 | Vertical type with 5 nos. medical gas outlets (O₂ – 2, VAC – 1, MA4 – 2) & 8 nos. universal electric sockets |
| 6 | SITC of wall mounted individual Oxygen / Medical Air/ Vacuum outlet point suitable for MGPS, conforming to HTM 02-01 / NFPA 99 standards, made of high quality brass with chrome plated finish, non-interchangeable gas specific pin indexing system, self-sealing type with primary and secondary check valves, complete with back box, color coded front plate, identification label, necessary copper tail pipe connection (EN 13348 medical grade copper), brazing with silver alloy, including necessary accessories, testing for leakage and functionality, complete in all respects as required. |
| 7 | Supply, Installation, Testing & Commissioning of Microprocessor-based Digital Medical Gas Area Alarm Panel suitable for monitoring 03 gases (e.g., Oxygen, Medical Air, Vacuum or as specified), complete with the following features:• Individual digital LED/LCD display for each gas with real-time pressure indication• High/Low pressure audiovisual alarm with mute & test facility• Gas-specific color coding and labeling as per HTM/NFPA standards• Inbuilt pressure transducers/sensors for each gas• LED indicators for normal, high & low pressure status• Facility for repeat alarm / BMS connectivity (dry contact output)• ABS/CRCA powder-coated enclosure suitable for recessed/surface mounting• 230V AC power supply with inbuilt SMPS and battery backup• Complete with all necessary accessories, mounting hardware, internal wiring, calibration and testing• The panel shall comply with relevant standards such as HTM 02-01 / NFPA 99 / ISO 7396-1. |
| 8 | Supply of Gas Specific Stainless Steel (SS) Probe suitable for Oxygen (O₂), Medical Air (MA) and Vacuum, compatible with existing MGPS Bed Head Panel (BHP) outlets, complete with the following:• Made of high-grade Stainless Steel (SS 304/316) body• Gas specific indexing to prevent cross connection• Color coded and clearly marked as per HTM / ISO standards• Non-interchangeable design for O₂, MA & Vacuum• Suitable for direct insertion into compatible gas outlet• Leak proof design with proper sealing arrangement• Tested for pressure and leakage• Conforming to HTM 02-01 / ISO 7396-1 standards |
| 9 | Oxygen |
| 10 | Medical Air |
| 11 | Vacuum |
| 12 | Supply, Installation, Testing & Commissioning of Area Valve Service Unit (AVSU) for Oxygen (O₂), Medical Air (MA) and Medical Vacuum, recessed / surface mounted type, as required, complete with the following:• Transparent, lockable front cover with breakable glass / polycarbonate panel.• Clear gas identification labels with color coding as per standards.• Provision for pressure gauge (for O₂ & MA) and vacuum gauge, including gauges (0–16 bar for O₂/MA, and suitable range for vacuum).• Emergency shut-off functionality with proper tagging.• Supports, clamps, anchor fasteners, and necessary accessories.• Oxygen-compatible PTFE tape and consumables.• Necessary wall cutting, chasing, making good and finishing.• Testing for leak tightness, pressure testing, functional testing and commissioning. |
| 13 | Supply and fixing of hospital grade IV Rod made of stainless steel (SS 304), consisting of telescopic height-adjustable vertical rod with minimum four (04) SS hooks, suitable for saline/glucose bottles, mounted on suitable rail clamp compatible with standard bed head panel/medical rail system.The IV rod shall have:• Minimum height adjustment range: 1200 mm to 2100 mm• SS 304 construction with satin/matt finish• Smooth height locking mechanism• Load bearing capacity minimum 10 kg• Rail clamp with secure locking arrangement• Including all necessary fixtures, fasteners, hardware, and accessories. |
| 14 | Supply, Installation, Testing & Commissioning (SITC) of Imported Low Flow Suction Regulator suitable for MGPS vacuum outlet, with adjustable range 100–150 mmHg, suitable for neonatal/NICU applications, complete with the following:• Precision vacuum regulator with calibrated gauge (100–150 mmHg range)• 1000 ml autoclavable polycarbonate suction jar with overflow safety lid• Bacterial hydrophobic filter• Suction tubing set• Wall mounted suction jar holder with clamp• Compatible probe for existing MGPS outlet (as per site requirement – Ohmeda / Schrader / Chemetron / etc.)• All necessary accessories required for complete installation• The unit shall be CE marked / US FDA approved and compliant with relevant standards (ISO 10079 / HTM 02-01 / NFPA 99, as applicable). |
| 15 | Supply, Installation, Testing & Commissioning of Isolation Ball Valve for MGPS, full bore, quarter-turn, brass body, chrome-plated brass ball, PTFE seats, suitable for oxygen and medical gases. Valve shall be of antistatic design, with blow-out proof stem, leak tight in both directions, and conforming to HTM 02-01 / EN 7396 / BS EN ISO 7396-1 requirements. The valve shall be cleaned, degreased, and certified for oxygen service, provided with test certificate for oil & grease-free condition, capped/sealed until installation. End connections shall be copper tube fittings (solder / brazing type) suitable for EN 13348 copper pipes of respective sizes, including proper fixing, alignment, leak testing, cleaning, labeling, flow direction marking, and complete connections with existing MGPS copper pipe line using silver brazing alloy, nitrogen purging during brazing, final testing and certification as per ISO 7396-1 / HTM 02-01 standards, complete in all respects as required. |
| 16 | Size: 15 mm Isolation ball valve with Brass fittings |
| 17 | Size: 22 mm Isolation ball valve with Brass fittings |
| 18 | Size: 28 mm Isolation ball valve with Brass fittings |
| 19 | Providing and fixing Butterfly Valve to control MGPS supply (O₂ / MA4) for individual Bed Head Panel, forged brass body, nickel plated, PTFE/EPDM seat, quarter turn lever operation, degreased and tested for oxygen service as per HTM 02-01 / EN ISO 7396-1, complete with copper pipe connections, brazing and accessories as required. |
| 20 | Size: 12 mm |
| 21 | SITC of Medical Grade Copper Pipe conforming to EN 13348, manufactured from deoxidized non-arsenical copper (Cu-DHP, ≥99.90% Cu, P 0.015–0.040%), half-hard (R250) or hard drawn (R290), internally degreased, cleaned and capped at both ends, suitable for oxygen and medical gas/vacuum services, maximum residual carbon ≤0.20 mg/dm², supplied in 3 m straight lengths with protective polythene sleeving, duly marked with manufacturer’s name, EN 13348, “Medical Gas Use” and size; including installation, cutting, reaming, jointing by oxy-acetylene silver brazing, fittings, pipe supports (saddles, hangers, U-bolts, Unistrut/strut channels, anchor fasteners), proper clamping at 1.5 m intervals, sleeves at wall/floor crossings, nitrogen leak testing, cleaning, passivation, labeling and colour coding as per HTM 02-01/NFPA/ISO standards, and complete testing & commissioning of MGPS copper pipelines of following sizes, complete as required at site. |
| 22 | Diameter - 12mm |
| 23 | Diameter - 15mm |
| 24 | Diameter - 22mm |
| 25 | Diameter - 28mm |
| 26 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 27 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 28 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 29 | Single pole |
| 30 | Providing and fixing false ceiling at all heights, including providing and fixing the perimeter of ceiling fixed to wall / partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 × 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in three layers covering up to 150 mm on both sides of joint, all as per manufacturer’s specification and including the cost of making openings for light fittings, grills, diffusers, cut-outs made with frame of perimeter channels suitably fixed, including provision of trap doors in false ceiling, complete as per drawings, specifications and directions of the Engineer-in-Charge, but excluding the cost of painting, with 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095 (Part-I) : 2011. |
| 31 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. Total Amount (Inclusive of GST) Rs. 0.0 |