| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2 | Group A. Makes:- Legrand(Myrius),Schiender(Livia),Anchor Roma(Plus),L&T(Entice). |
| 3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 4 | Group B. Makes:- Legrand(Myrius),Schiender(Livia),Anchor Roma(Plus),L&T(Entice). |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required |
| 6 | 2X1.5Sq.mm+1X1.5Sq.mm Earth wire |
| 7 | 2X2.5Sq.mm+1X2.5Sq.mm Earth wire |
| 8 | 2X4Sq.mm+1X4Sq.mm Earth wire |
| 9 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. Makes: KEI/L&T/Anchor |
| 11 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 12 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 13 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Makes: Plaza/Finolex/Polycab |
| 14 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. Makes: Plaza/Finolex/Polycab |
| 15 | 3X1.5 Sq.mm |
| 16 | 3X2.5Sq.mm |
| 17 | 3X4Sq.mm |
| 18 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Makes:-Anchor Roma,L&T Entice,Legrand(Myrius) |
| 19 | 5/6 amp Modular switch |
| 20 | 3 pin 5/6 amp socket outlet |
| 21 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. Makes: Legrand(Myrius),Schiender(Livia),Anchor Roma(Plus),L&T(Entice) |
| 22 | Supplying and fixing suitable size GI box with modular plate and cover in FRLSont on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. Makes: Legrand(Myrius),Schiender(Livia),Anchor Roma(Plus),L&T(Entice). |
| 23 | Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required: Makes:- Legrand,Schiender,L&T. |
| 24 | Single pole. Cat-A. |
| 25 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. Makes:- Legrand,Schiender,L&T. |
| 26 | 63 Amps. Cat-A. |
| 27 | Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required. Makes:- Legrand,Schiender,L&T. |
| 28 | 63 Amps. Cat-A. |
| 29 | Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required.(But without MCB/RCCB/Isolator) Makes:- Legrand,Schiender,L&T. |
| 30 | Double door-4 way |
| 31 | Double door-16 way |
| 32 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 33 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthingas required. |
| 34 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, Copper tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 35 | Providing and Fixing of IP20 LED fixture of 12 watt +/- 1 W LED Surface/recess Mounted Downlighter Round/square Shape with minimum system lumen efficacy of 100 lm/W with Polycarbonate housing,pressure die cast heat sink and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 . The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K with CRI of minimum 80.The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects.)(Including 5Years Warranty). Makes: Havells,Bajaj,wipro,Panasonic |
| 36 | LED Surface/Recess mounting round/square downlighter 12 watt |
| 37 | Providing and Fixing of IP20 LED fixture of 18 watt +/- 1 W LED Surface/recess Mounted Downlighter Round/square Shape with minimum system lumen efficacy of 100 lm/W with Polycarbonate housing,pressure die cast heat sink and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 . The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K with CRI of minimum 80.The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. )(Including 5Years Warranty). Makes: Havells,Bajaj,wipro,Panasonic |
| 38 | LED Surface/Recess mounting round/square downlighter 18 watt |
| 39 | Supplying and fixing of LED Batten along with 20Watt LED Tube Light ,6500K ,(Five YEAR WARRANTY ) and it should be compatible with specification e.i. Power Factor > .9,Harmonic Distortion<10% and efficacy >100 Lumens per watt, suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc as required complete in all respects. )(Including 5Years Warranty). Makes: Havells,Bajaj,wipro,Panasonic |
| 40 | LED Tube Light 4 Feet Long |
| 41 | Providing and fixing of IP65 Bulkhead led fixture 10 W +/- 1 W Wall Mounted with minimum system lumen efficacy of greater than 100 lm/W with Pressure Die Cast Aluminum housing, Polycarbonate Opal Diffuser and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 .The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K only with CRI of minimum 80.The Input voltage range shall be 140V to 280V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. )(Including 5Years Warranty). Makes: Bajaj ,Havells ,wipro,Panasonic |
| 42 | LED 10 Watt Bulk Head |
| 43 | Supplying and fixing of LED Batton/LED Mirror Light 10WAtts, 6500K ,(Five YEAR WARRANTY ) and it should be compatible with specification e.i. Power Factor > .9,Harmonic Distortion<10% and efficacy >100 Lumens per watt, suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc as required of Approved Makes.(2 Feet Long)(Including 5Years Warranty).Makes:-Havells,Wipro,Bajaj. |
| 44 | LED Mirror Light 10 Watts |
| 45 | Supplying and fixing batten/ angle holder including connection etc. as required.Makes: Anchor, Goldmedal. |
| 46 | Supplying and fixing Ding dong bell suitable for single phase, 230 volts, complete as required.Makes: Anchor/Goldmedal. |
| 47 | Providing, Installation, testing and commissioning of BLDC ceiling fan with fan regulator,including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mmtwin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required. (Including 5Years Warranty). Make:- Usha(BLDC ),Bajaj,Crompton. |
| 48 | Ceiling Fan 1200 mm sweep, Category-A |
| 49 | Ceiling Fan 1400 mm sweep, Category-A |
| 50 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. Makes: Anchor. |
| 51 | Providing and installation exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: Make:Usha,Bajaj,Crompton. |
| 52 | Exhaust Fan, Light duty, (Domestic),300 mm Sweep |
| 53 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 25 amps modular socket outlet and 25 amps modular SP MCB \\"C\\" curve including connection,painting etc. as required. Makes: Legrand,Schiender,L&T. |
| 54 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T. Panel cum metering Panel. The Assembly charges of cubical type, indoor type,single door,Floor mounted, fixed type, free standing single front, dust proof &compartmentalized 6Way Meter Panel made out of M.S. CRC Sheet 16G/18G,Base Frame 40 X 40 X 5mm duly painted with Siemens Grey Powder Coated Paint as per specification Approximate Size (H)1850MM X(W)1300MM X (D)300MM X (L)150MM,assembly Charges of 150A 4Strip Copper Busbar (Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.66 Amp.) Copper shall be Electric Grade , Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black,Assembly Charges of Copper solid/ Copper flexible wire 10mm interconnection Busbar to MCCB,./MCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVAPower system & control or approved equivalent make). |
| 55 | MATERIAL: |
| 56 | MAIN INCOMER: MCCB-125A 4P 25 kA TMR with O/L & S/C Protecrtion-1 No., Spreader Link 125 A 4P-1Nos., Phase indicating Lamp-3 Nos, Control SP MCB -3Nos. |
| 57 | Outgoing: Space for S/Phase KWH Meter & MCB 63A DP 10KA . |
| 58 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wire with thimbles, printed sleeves, tie & belt etc; |
| 59 | The prices of complete job as per the specifications above shall be inclusive of gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 60 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T. Panel. The Panel shall be compartmentalized type having space and arrangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, base frame75X40X3MM angle duly painted with Siemens Grey Powder Coated paint, Assembly Charges of 100A 4 Strip Copper Busbar ( Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.0 Amp.) Copper shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. Approximate Size of Panel H- 700mmX W-500mmX D-200mm. The Assembly Charges of 100 Amps 4P Copper solid/ Copper flexible wire interconnection Busbar to MCCB & MCCB/MCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVAPower system & control or approved equivalent make). |
| 61 | MATERIAL: |
| 62 | MAIN INCOMER: MCCB-100A 4P 25 kA TMR with O/L & S/C Protecrtion-1 No., Spreader Link 100 A 4P-1Nos., Selector Switch-1No., Phase indicating Lamp-3 Nos, Control SP MCB -3Nos,Terminal switch -1No. |
| 63 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wire with thimbles, printed sleeves, tie & belt etc; |
| 64 | The prices of complete job as per the specifications above shall be inclusive of gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 65 | Providing & Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Makes: KEI/Anchor/L&T. |
| 66 | Armoured cable 25 Sq. mm (3.5 core) |
| 67 | Armoured cable 35Sq. mm (3.5 core) |
| 68 | Supplying and fixing sheet metal bus-bar chamber suitable for 100 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 300mm & cross-sectional area (25.4mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (380mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:- Please Enable Macros to View BoQ information |