Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | CIVIL WORK:- Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth a lead within CEERI campus and lift upto 1.5 m, as directed by Engineer-in- Charge: |
| 2 | All kinds of soil |
| 3 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, a lead within CEERI campus as per direction of Enginner In Charge. |
| 4 | All kinds of soil |
| 5 | Excavating trenches by mechinical / manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead within CEERI campus : All kinds of soil |
| 6 | Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia |
| 7 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering,lead within CEERI campus and for all lift |
| 8 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. |
| 9 | All kinds of soil |
| 10 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 11 | Providing and laying in position cement concrete of specified grade including the cost of centering and shuttering - All work up to plinth level |
| 12 | 1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 13 | Providing and fixing up to floor five level precast cement concrete string or lacing courses, copings, bed plates, anchor blocks, plain window sills, shelves, louvers, steps, stair cases, etc., including hoisting and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), cost of required Centering complete. |
| 14 | 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20mm nominal size derived from natural sources) |
| 15 | Making plinth protection 50mm thick of cement concrete 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth. |
| 16 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 17 | Foundations, footings, bases of columns, etc. for mass concrete |
| 18 | Suspended floors, roofs, landings, balconies and access platform |
| 19 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 20 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 21 | Stairs, (excluding landings) except spiral-staircases |
| 22 | Weather shade, Chajjas, corbels etc., including edges |
| 23 | Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). |
| 24 | Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) |
| 25 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 26 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 27 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. |
| 28 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 29 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 30 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. |
| 31 | All works upto plinth level Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 32 | All works above plinth level upto floor V level Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 33 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 34 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall confirm to ASTM 6063). |
| 35 | Floor Joint of 100 mm gap |
| 36 | Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063). |
| 37 | Wall Joint of 100 mm gap |
| 38 | Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates asper ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063). |
| 39 | Roof Joint of 100 mm gap |
| 40 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: |
| 41 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 42 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : |
| 43 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 44 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. |
| 45 | Cement mortar 1:4 (1 cement :4 coarse sand) |
| 46 | Brick edging 7cm wide 11.4 cm deep to plinth protection with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 cement : 4 fine sand). |
| 47 | Providing and fixing stone jali 40 mm thick in approved design throughout in cement mortar 1:3 (1 cement : 3 coarse sand), including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment, matching the stone shade etc. complete |
| 48 | Red sand stone |
| 49 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for staircase steps,riser, landings,kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels and preparation of surface etc complete |
| 50 | Granite stone slab of all colour and texture Area of slab over 0.50 sqm |
| 51 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. |
| 52 | Granite work |
| 53 | Providing and fixing Ist quality ceramic glazed wall tiles (Size not less than 300 mm x 450 mm) conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades (light,dark and designer etc ) of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand),having below rough plaster of average 20 mm of 1:4 ( cement :4 coarse sand) for surface preparation and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 54 | Providing and fixing aluminium body Cam Action Slide Channel Overhead hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment and 90 degree stop arrangement, of approved quality and make with necessary accessories and screws etc. complete. |
| 55 | Providing and fixing stainless steel tower bolts, ISI marked with necessary fiitingsand screws etc. complete : |
| 56 | Size 250x10 mm |
| 57 | Size 100x10 mm |
| 58 | Hook and eye 150 mm SS 304 |
| 59 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete |
| 60 | Size 125 mm |
| 61 | Providing and fixing bright SS finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of strainless steel 304 lever handles of approved quality and make with necessary screws etc. complete. |
| 62 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 63 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. |
| 64 | 80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 65 | Providing and fixing ball bearing for rolling shutters. |
| 66 | Extra for providing mechanical device chain and crank operation for operating rolling shutters. |
| 67 | Exceeding 10.00 sqm and upto 16.80 sqm in the area |
| 68 | Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer-in- charge, (area of grill to be measured). |
| 69 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 70 | Hot finished welded type tubes |
| 71 | Providing and fixing mild steel round holding down bolts with nuts and washer plates complete. |
| 72 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. |
| 73 | Plate in gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 74 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 75 | Providing and laying vitrified floor tiles with spacer in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 76 | Glazed Vitrified tiles Matt/Antiskid finish of size 600x600 mm |
| 77 | Providing and laying Vitrified tiles in different sizes with spacer (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. |
| 78 | Glazed Vitrified tiles Matt/Antiskid finish of size 600x600 mm |
| 79 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. |
| 80 | Size of Tile 600x600 mm |
| 81 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. |
| 82 | Granite stone slab of all colour and texture |
| 83 | 12 mm cement plaster of mix with fibre mesh for jointing : including proper double scoffolding system upto height 15.00 mtr |
| 84 | 1:6 (1 cement: 6 coarse sand) |
| 85 | 15 mm cement plaster on rough side of single or half brick wall of mix with fibre mesh for jointing: including proper double scoffolding system upto height 15.00 mtr |
| 86 | 1:6 (1 cement: 6 coarse sand) |
| 87 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade:including proper double scoffolding system upto height 12.00 mtr |
| 88 | New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 89 | Finishing walls with ready mixed Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives,including proper double scoffolding system upto height 12.00 mtr |
| 90 | New work (Two or more coats applied @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. |
| 91 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : |
| 92 | Two or more coats on new work |
| 93 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 94 | Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria Tremix system of flooring involving all required operations such as potter/surface vibrator, vaccum dewatering with suction matts with electrical pumns, side guide channels for side shuttering, screed vibrator, power drowelling, broom finish to the top surface, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately). Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately. |
| 95 | Cement concrete prepared with batch mixing machine |
| 96 | Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge. |
| 97 | Using grade 'A' sealing compound conforming to IS: 1834. |
| 98 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured to calculate volume for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 99 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. |
| 100 | 80 mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern |
| 101 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe and cp health facuet, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required : |
| 102 | W.C. pan with ISI marked white solid plastic seat and lid |
| 103 | Providing and fixing wash basin with C.I. brackets and dash fastner, 15 mm C.P. brass pillar cock , 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required : |
| 104 | White Vitreous China Wash basin size 550x400 mm with C.P. brass pillar basin mixer with central hole and long braided hoses |
| 105 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 106 | Semi rigid pipe 32 mm dia |
| 107 | Providing and fixing mirror of size 600x450 mm superior glass (of approved quality) and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing, fixed to wooden cleats with C.P. brass screws and washers complete. |
| 108 | Providing and fixing soil, waste and vent pipes : |
| 109 | 100 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 110 | 75 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 111 | Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete |
| 112 | 100 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 113 | 75 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 114 | Providing and fixing plain bend of required degree. |
| 115 | 100 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 116 | 75 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 117 | Providing and fixing terminal guard |
| 118 | 100 mm Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 119 | Providing and fixing shielded coupling for Hubless centrifugally cast iron pipe |
| 120 | 100 mm dia SS 304 grade coupling with EPDM rubber gasket |
| 121 | 75 mm dia SS 304 grade coupling with EPDM rubber gasket |
| 122 | Providing and fixing Steel finished clamps with base holder plate with accessories etc complete for sand cast iron/ centrifugally cast (spun) iron pipes of diameter : |
| 123 | 100 mm dia |
| 124 | 75 mm dia |
| 125 | Providing and fixing P-trap / Floor trap of self cleansing design with screwed down or CP hinged grating with frame with or without hole, vent arm complete, including cost of cutting and making good the walls and floors : |
| 126 | 100 mm inlet and 100 mm outlet Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 127 | 100 mm inlet and 75 mm outlet Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 128 | Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge. |
| 129 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls and floor etc. Internal work - Exposed on wall including synthetic enamel paint of approved brand and manufacture of required colour to give an even shade |
| 130 | 25 mm dia nominal bore |
| 131 | Providing and fixing G.I. Pipes complete with G.I. fittings and clamps,i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall |
| 132 | 20 mm dia nominal bore |
| 133 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling ,including painting with anti corrosive bitumastic paint and connection with main line with fillings etc complete |
| 134 | 25 mm dia nominal bore |
| 135 | 50 mm dia nominal bore |
| 136 | 80 mm dia nominal bore |
| 137 | Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : |
| 138 | 25 to 40 mm nominal bore |
| 139 | 50 to 80 mm nominal bore |
| 140 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete |
| 141 | 25 mm nominal bore |
| 142 | Providing and fixing uplasticised PVC connection pipe in SS finish with brass unions : |
| 143 | 45 cm length & 15 mm nominal bore |
| 144 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work : |
| 145 | 25 mm dia nominal bore |
| 146 | 50 mm dia nominal bore |
| 147 | 80 mm dia nominal bore |
| 148 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) : |
| 149 | 20 mm nominal bore |
| 150 | 25 mm nominal bore |
| 151 | 50 mm nominal bore |
| 152 | 80 mm nominal bore |
| 153 | Providing and placing on terrace (at all floor levels) polyethylene water torage tank,IS: 12701 marked,with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes with 03 nos tank nipples and the base suppport for tank & including providing and fixing 20mm dia ball valve (brass) of approved quality, High or low pressure, with plastic floats complete for each tank.including taking down existing pvc tank & deposited in store yard as per direction of Engineer in-Charge. |
| 154 | Providing and fixing C.P. brass bib cock with wall flange of approved quality conforming to IS:8931 as per direction by Engineer in charge. |
| 155 | 15mm nominal bore. |
| 156 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 with wall flange as per direction by Engineer in charge |
| 157 | 15mm nominal bore. |
| 158 | Cutting holes up to 30x30 cm in walls including making good the same: |
| 159 | with common burnt clay F.P.S. (non modular) bricks |
| 160 | Providing,laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints including trenching , refilling the same etc.complete : |
| 161 | 100 mm diameter S.W.pipe |
| 162 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : |
| 163 | 100 mm diameter S.W.pipe |
| 164 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight FRP/GRP cover with frame of 300 x300 mm size (inside) the load capacity of cover to be not less than 12.5T as per standard design: |
| 165 | 150 x 100 mm size P type without common burnt clay F.P.S (non modular ) bricks of class designation 7.5 |
| 166 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : |
| 167 | 150 mm dia. R.C.C. pipe |
| 168 | 250 mm dia. R.C.C. pipe |
| 169 | 300 mm dia. R.C.C. pipe |
| 170 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : |
| 171 | Inside size 90x80 cm and 45 cm deep including FRP cover with frame 455x610 mm internal dimensions, with 12.50T capcity of approved design and brand :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 172 | Extra for depth for manholes : |
| 173 | Size 90x80 cm With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 174 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 175 | Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete : |
| 176 | For pipes 100 to 250 mm diameter |
| 177 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm FRP/GRP horizontal grating with frame of capacity 12.50T complete as per standard design : |
| 178 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 179 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : |
| 180 | For fixed portion Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron) |
| 181 | For shutters of doors, windows & ventilators including providing and fixing strainless steel hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 182 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): |
| 183 | With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 184 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes,SS304 door handle 4 nos required size , Locking arrangements with necessary fittings etc complete for fixing required door fittings, all complete as per direction of Engineer-in-charge |
| 185 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge : |
| 186 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 187 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. |
| 188 | All types of soil 300 mm dia |
| 189 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. |
| 190 | 200 mm nominal size dia |
| 191 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 192 | Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance ≥ 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the Engineer-in-charge. |
| 193 | With 20 mm thick beveled tegular mineral fibre false ceiling tile (NRC 0.7) |
| 194 | Providing and fixing soil, waste and vent pipes as per directions of the Engineer-in-charge. : 150 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 195 | Providing and fixing plain bend of required degreeas per directions of the Engineer-in-charge. 150 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 196 | Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts completeas per directions of the Engineer-in-charge. 100 mm dia Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905 |
| 197 | Providing and fixing shielded coupling for Hubless centrifugally cast iron pipe :150 mm dia SS 304 grade coupling with EPDM rubber gasket etc complete as per directions of the Engineer-in-charge. |
| 198 | Providing and Fixing 0.50 mm thick PVDF (Poly Vinylidene fluouride) of aluminium thickness 3.00 mm overall thickness 4.00 mm on walls,in doors & ceiling with proper required haging system and having fire rating of 120 minutes and fixing with silicon tape/ adhessive material as required ,in opening shutters and fixed sections including cutting PVDF sheet as per required at site, preparing smooth surface and making holes/making good as required cutting hoisting and fixing aluminium members etc. as directed by Engineer Incharge etc. complete |
| 199 | Cleanroom interior and Gas system :- Designing, providing, installing and fixing of Double skin modular clean room wall panels 100 mm thick, double skin 0.6 mm thick PPGI / PCGI sheet on both sides PUF (40 ± 2 kg/m³ density) as infill, Walls shall be fixed on floor runner and including all fittings such as Aluminium coving R 50 powder coated with aluminium back up angle,Aluminium 2D/3D Corner covings for all corners,cut out in wall for switch & socket with proper required finishing,C Channel powder coated,2 Way Aluminium coving powder coated with aluminium back up angle For outer wall etc complete of approved brand and design as per direction of Engineer-In-charge.. All joints to be filled with silicon sealant. Electrical conduit shall be embaded at panels for power sockets wherever required as per approved design of Engineer-In-charge. (price for conduit under separate head) |
| 200 | Designing, providing, installing and fixing of Clean room Ceiling (walkable) double skin false ceiling of 50 mm thick, as per approved colour from Enginner-In-Charge. double skin 0.5mm thick PPGI / PCGI sheet on both sides PUF (40 ± 2 kg/m³ density) as infill. Necessary supporting member GI tie rod, turn buckle, anchor fastener etc as per suitable arrangement/site rquirement, sealant deemed to be included in pricing and making cut out in ceiling for HEPA TERMINAL & T grid for Light fixture fixing with proper required finishing etc complete of approved brand and design as per direction of Engineer-In-charge. |
| 201 | Designing, providing, installing and fixing of 46 mm thick flush doors made of 0.8 mm thick PU Painted sheet with PUF as infill. 0.8 mm thick GPSP Powder coated as per approved colour from Enginner-In-Charge, door frames of 100 mm size , double glazed toughened glass view panel 400x600x5 mm, SS push plates, door closures , SS D Handles, Lock & key, SS Ball bearings butt hinges & Drop seal with all complete of approved brand and design as per direction of Engineer-In-charge. |
| 202 | Single Leaf Door 900 mm X 2100 mm |
| 203 | Double leaf Door 1500 mm X 2100 mm |
| 204 | Double leaf Door 1800 mm X 2100 mm |
| 205 | Emergency Door 2000 mm X 2100 mm with push bar handle |
| 206 | Designing, providing, installing and fixing of Clean room windows/ vision Panels of flush double glazed fixed to the partition panels with proper framing 100 mm size for the required sizes and quantity Tempered Glass thickness minimum 5 mm Window glazed, Extruded aluminium midline (V-shape) frame in powder baked ‘designer white’ finish and gasket with all complete of approved brand and design as per direction of Engineer-In-charge. |
| 207 | Size : As per approved design and drawing |
| 208 | Supply and laying of self levelling compound on PCC floor of 3.00 mm average thickness. Top of self levelling should have undulation of +/- 1 mm in per sqm area etc complete as per direction of Engineer-In-charge. |
| 209 | Supply and laying of 2.00 mm thick ESD Vinyl flooring in roll on conductive glue and copper strip below vinyl. Copper strip will be connected to mother earth through copper strip at few locations. All vinyl joints shall be fusion welded to make it monolithic etc complete as per direction of Engineer-In-charge. |
| 210 | Supply and laying of coving between floor and wall. Coving back up shall be of rubber material and top will be vinyl of same sheet as that of floor. Coving joint with wall panel shall be sealed with silicon sealant etc complete as per direction of Engineer-In-charge. |
| 211 | Providing and applying 3.00 mm thinkness epoxy self levelling flooring system in required shade and colour with semi glossy finish which consist of surface preparation, primer coat with epoxy based primer of approved brand and manufacturer, followed by 1.5 mm thick epoxy self levelling screed , epoxy self levelling with the help of notch trowel etc complete as per direction of Engineer-in-Charge. |
| 212 | Providing and applying Epoxy coving size 50x50mm in required shade and colour with semi glossy finish of approved brand and manufacturer etc complete as per direction of Engineer-in-Charge. |
| 213 | Designing, providing, installing and fixing Single entry Air shower fabricated with SS-304, 20G sheet for movement of single person with all complete with H13 HEPA Filter, Pre- filter, blowers, ss adjustable nozzles, SS grated floor, two doors with inter-locking arrangement timer with fully adjustable, fully automatic with electronic logic control. Air shower shall confirm to clean room class 100 at nozzle outlet etc complete as per direction of Engineer-in-Charge. |
| 214 | Designing, providing, installing and fixing of Static Pass Box made out of SS 304 with, door inter locks, UV light with UV light meter, electronic buzzer.Dimensions mentioned are internal sizes. 600 x 600 x 600 mm etc complete as per direction of Engineer-in-Charge. |
| 215 | Designing, providing, installing and fixing Dynamic Pass Box made of SS 316 working size approx 600 x 600 x 600 mm with HEPA filtered air supply, blower motor assembly, door,interlock, UV light, UV counter etc complete as per direction of Engineer-in-Charge. |
| 216 | Designing, providing, installing and fixing SS 304 shoe rack cum cross over bench made of 18 swg SS304 Dimensions:3500mm (L) x 300mm (W) x 650mm (H) matt finish etc complete as per direction of Engineer-in-Charge. |
| 217 | Designing, providing, installing and fixing Ventilated Garments cabinet hanging arrangement made of SS304 Suitable for 10 set of hangers etc complete as per direction of Engineer-in-Charge. |
| 218 | Designing, providing, installing and fixing Garments cubicle storage rack made of SS 304. Suitable for 10 set of garments etc complete as per direction of Engineer-in-Charge. |
| 219 | Designing, providing, installing and fixing MS painted Emergency shower and Eye wash station with hand operated shower and foot / elbow operated eye wash. The unit shall have a common water inlet and drain point etc complete as per direction of Engineer-in-Charge. |
| 220 | Supply, Installation, Testing and commissioning of gas supply panel for Ar with 3000 PSI input pressure to safely regulate the pressure of gas present in cylinder to the pressure required at point of use along with 1/2\\" input and 1/2\\" output. The gas supply panel consists of the following components: 1) Isolation valve 2) Vent arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet Filter - 0.5 um and outlet filters- 0.003um 6) Pressure gauges All these components are to be assembled on an SS304 plate inside a cleanroom environment. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 221 | Supply, Installation, Testing and commissioning of gas supply panel for He with 3000 PSI input pressure to safely regulate the pressure of gas present in cylinder to the pressure required at point of use along with 1/4\\" input and 1/4\\" output . The gas supply panel consists of the following components: 1) Isolation valve 2) Vent arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet Filter - 0.5 um and outlet filters- 0.003um 6) Pressure gauges All these components are to be assembled on an SS304 plate inside a cleanroom environment. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 222 | Supply, Installation, Testing and commissioning of gas supply panel for CF4 with 3000 PSI input pressure to safely regulate the pressure of gas present in cylinder to the pressure required at point of use along with 1/4\\" input and 1/4\\" output . The gas supply panel consists of the following components: 1) Isolation valve 2) Vent arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet Filter - 0.5 um and outlet filters- 0.003um 6) Pressure gauges All these components are to be assembled on an SS304 plate inside a cleanroom environment. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 223 | Supply, Installation, Testing and commissioning of gas supply panel for SF6 with 3000 PSI input pressure to safely regulate the pressure of gas present in cylinder to the pressure required at point of use along with 1/4\\" input and 1/4\\" output . The gas supply panel consists of the following components: 1) Isolation valve 2) Vent arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet Filter - 0.5 um and outlet filters- 0.003um 6) Pressure gauges All these components are to be assembled on an SS304 plate inside a cleanroom environment. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 224 | Supply, Installation, Testing and commissioning of gas supply panel for O2 with 3000 PSI input pressure to safely regulate the pressure of gas present in cylinder to the pressure required at point of use along with 1/2\\" input and 1/2\\" output. The gas supply panel consists of the following components: 1) Isolation valve 2) Vent arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet Filter - 0.5 um and outlet filters- 0.003um 6) Pressure gauges All these components are to be assembled on an SS304 plate inside a class 100 cleanroom environment. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 225 | Supply, Installation, Testing and commissioning of gas supply panel for N2 with 3000 PSI input pressure to safely regulate the pressure of gas present in cylinder to the pressure required at point of use along with 1/2\\" input and 1/2\\" output. This will be for exchlusive use for purging to Gases in cabinets. The gas supply panel consists of the following components: 1) Isolation valve 2) Vent arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet Filter - 0.5 um and outlet filters- 0.003um 6) Pressure gauges All these components are to be assembled on an SS304 plate inside a cleanroom environment along with SS316 purifier of size 1/4\\" for N2 supply panel and maximum flow rate of 75 LPM with a pressure range of 600 PSIG. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 226 | Gas Cabinets - Supply, Installation, Testing and commissioning of Gas cabinet for BCl3, NH3, SiH4, N2O, Cl2, PH3, GeH4, B2H6 with 3000 PSI input pressure for safely regulating the pressure of gas present in cylinder to the pressure required at point of use along with 1/4\\" input and 1/4\\" output for each gas. The gas cabinet consists of the following components in 08 Nos : 1) Isolation valve 2) Vent & purge arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet and outlet filters 6) Pressure gauges 7) Vacuum generator 8) Pressure transducer 9) Check valve 10) Emergency shut off valve 11) Excess flow switch 12) Restricted orifice 13) Sprinkler 14) Gas Leak Detector 15) ROR sensor 16) Exhaust Differential Pressure Switch 17)Non retrun valve 18)PLC Controller for the cabinets with HMI with all other necessary accessories like emergency shutdown etc complete. All these components are to be assembled on an SS304 plate inside a Class 100 cleanroom environment complying to SEMI standards along with 03 Nos SS316 purifier of size 1/4\\" for Cl2, BCl3, NH3 in gas cabinet with flow rate 2 LPM a pressure range of 800 PSIG. The gas panels will be mounted inside an enclosure that is constantly exhausted and monitored. The gas cabinet will house a gas specific self- suction type gas leak detector. The enclosure shall be made of cold rolled sheet and have a explosion proof glass for viewing the panels. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count. Each Gas cabinet shall be for single cylinder for the respective speciality gases. Each cabinet shall have provision for purging etc complete as per direction of Engineer-in-Charge. |
| 227 | Supply, Installation, Testing and commissioning of Gas cabinet for H2 with 3000 PSI input pressure for safely regulating the pressure of gas present in cylinder to the pressure required at point of use along with 1/4\\" input and 1/4\\" output . The gas cabinet consists of the following components: 1) Isolation valve 2) Vent & purge arrangement 3) Pressure Regulator 4) Safety relief valve 5) inlet and outlet filters 6) Pressure gauges 7) Vacuum generator 8) Pressure transducer 9) Check valve 10) Emergency shut off valve 11) Excess flow switch 12) Restricted orifice 13) Sprinkler 14) Gas Leak Detector 15) ROR sensor 16) Exhaust Differential Pressure Switch 17) Non retrun valve 18) PLC Controller for the cabinets with HMI with all other necessary accessories like emergency shutdown etc complete.All these components are to be assembled on an SS304 plate inside a Class 100 cleanroom environment complying to SEMI standards. The gas panels will be mounted inside an enclosure that is constantly exhausted and monitored. The gas cabinet will house a gas specific self- suction type gas leak detector. The enclosure shall be made of cold rolled sheet and have a explosion proof glass for viewing the panels. The panels will be undergo 5 step testing and validation process for pressure test, Helium leak test, Trace moisture test, Trace oxygen & particle count etc complete as per direction of Engineer-in-Charge. |
| 228 | Heating Jacket Supply, Installation and testing of heating jacket for supplied BCl3 and NH3 cylinder etc complete as per direction of Engineer-in-Charge. |
| 229 | Gas Detector - Supply, Installation and testing of gas detector in Cleanroom for BCl3, NH3, SiH4, N2O, Cl2, H2 Gas at point of use etc complete as per direction of Engineer-in-Charge. |
| 230 | Point of use sticks - Supply, Installation and testing of 1/4\\" point of use stick including the following: - Pressure regulator etc complete as per direction of Engineer-in-Charge. |
| 231 | Flash Back arrestor Supply, Installation, and testing of point of flash pack arrestor for Oxygen gas supply panel and Hydrogen gas cabinet. MOC: BRASS INLET: 1/4 NPT FEMALE OUTLET: 1/4 NPT FEMALE SAFETY ELEMENTS : FA,NV, TV 105\\"C Pressure 10 Bar etc complete as per direction of Engineer-in-Charge. |
| 232 | Supply, Installation, and testing of the SS316 purifier of size 1/4\\" for N2 supply panel. The maximum flow rate of 75 LPM with a pressure range of 600 PSIG etc complete as per direction of Engineer-in-Charge. |
| 233 | Heat Tracing Cable - Supply, Installation, and testing of point of heat tracing for NH3 and BCl3 gas cabinet and tube for maintaining temperature at 40 °C etc complete as per direction of Engineer-in-Charge. |
| 234 | Co- axial pressure swtich - Supply, Installation, and testing of Co- axial pressure swtich consisting of Pressure Switch- Diaphragm valves- VCR gland with nut & gasket.-VCR blind nut- Fittings etc complete as per direction of Engineer-in-Charge. |
| 235 | SS316L EP Tubing - Supply, Installation, Testing, and commissioning of SS316L electropolished Tubes of 1/4\\" Upon installation completion, the tubes shall undergo 5 step testing and validation etc complete as per direction of Engineer-in-Charge. The steps are : - Pressure hold test ( 0 psi drop over 24 hours). - Helium Leak check 10 -9 mbar l/sec - Trace oxygen < 10 ppm - Trace moisture ppm< 10 - Trace particle < 0.1 micron |
| 236 | Supply, Installation, Testing, and commissioning of SS316L electropolished Tubes of 1/2\\" for N2, Ar, O2 gas headers Upon installation completion, the tubes shall undergo 5 step testing and validation. The steps are : - Pressure hold test ( 0 psi drop over 24 hours). - Helium Leak check 10 -9 mbar l/sec - Trace oxygen < 10 ppm - Trace moisture < 10 ppm - Trace particle < 0.1 micron etc complete as per direction of Engineer-in-Charge. |
| 237 | Co-axial EP Tube - Supply, Installation, and testing of Coaxial Tubes of 1/4\\" X 1/2\\" along with associated fittings. Upon installation completion, the tubes shall undergo 5 step testing and validation. The steps are: - Pressure hold test ( 0 psi drop over 24 hours) - Helium leak check ( 10^-9 mbar l/sec) - Trace oxygen ( <1ppm) - Trace moisture ( <1ppm) - Trace Particle ( <0.1 micron) etc complete as per direction of Engineer-in-Charge. |
| 238 | Oil Free Air Compressor - Supply, Installation, Testing, and commissioning of Air cooled oil free reciprocating compressor with Desiccant Drier & particle filter to achieve dew point of ADP (-40)°C and 24 m3/hr ( 400 l/min @ 10 bar) etc complete as per direction of Engineer-in-Charge. |
| 239 | Dryer with filter for CDA - Supply, Installation, Testing, and commissioning of Desiccant type drier with filter for CDA. Heatless and heat regenerative dryer that works on pressure swing adsorption or thermal swing adsorption. Must be capable of operating above 12 bar @400lpm. Should be of vertical design with minimum pressure drop. Should include an equivalent controller and auto drain. Pressure dew point of (-) 40°C to be attained using this drier. Coalescing filters for the removal of dirt, oil and water (Liquid, aerosol & vapour form), made of activated carbon and borosilicate microfiber material. Three stage filtration is required using 5 um filter, fine filter 1um and micro filter .01um as well as 0.01um activated carbon filter. Must be suitable for use above 400L/min @12 bar etc complete as per direction of Engineer-in-Charge. |
| 240 | Providing and installing 200L Storage tank, MOC - SS with Pressure gauge, auto drain, isolation valve, Relief valve etc complete as per direction of Engineer-in-Charge. |
| 241 | SS Ball Valves Supply, Installation, Testing and commissioning of stainless-steel ball valve of 1/2\\" etc complete as per direction of Engineer-in-Charge. |
| 242 | Supply, Installation, Testing and commissioning of stainless-steel ball valve of 1/4\\" etc complete as per direction of Engineer-in-Charge. |
| 243 | Pressure regulator - Pressure regulator with in & out pressure gauges NPT end-1/2\\" etc complete as per direction of Engineer-in-Charge. |
| 244 | SS316L BA Tube - Supply, Installation and testing of SS 316L BA Tubes of 1/4\\" Upon installation completion, the tubes shall undergo 5 step testing and validation. The steps are : - Pressure hold test ( 0 psi drop over 24 hours). - Helium Leak check 10 -9 mbar l/sec - Trace oxygen < 10 B168ppm - Trace moisture < 10 ppm - Trace particle < 0.1 micron etc complete as per direction of Engineer-in-Charge. |
| 245 | Supply, Installation and testing of SS 316L BA Tubes of 1/2\\" Upon installation completion, the tubes shall undergo 5 step testing and validation. The steps are : - Pressure hold test ( 0 psi drop over 24 hours). - Helium Leak check 10 -9 mbar l/sec - Trace oxygen < 10 ppm - Trace moisture < 10 ppm - Trace particle < 0.1 micron etc complete as per direction of Engineer-in-Charge. |
| 246 | Deionized water unit - Supply, installation, testing and commissioning of DI system should be: Resistivity at 25C should be 18.2 Megaohm-cm Total Organic Carbon (TOC) < 5 ppb Dispense rate should be up to 2 l/min DI storage tank of 50 litres (PPH) RO storage Tank - 200 Litres (PP) Flow capacity 2 LPM etc complete as per direction of Engineer-in-Charge. |
| 247 | Ball Valve Supply, installation, testing and commissioning of threaded end, PN 10 high purity PPH ball valve. 25mm etc complete as per direction of Engineer-in-Charge. |
| 248 | Supply, installation, testing and commissioning of threaded end, PN 8 high purity UPVC ball valve 1/2\\" etc complete as per direction of Engineer-in-Charge. |
| 249 | PPH 3 way diaphragm valve Supply, installation, testing and commissioning of threaded end, PN 10 high purity PPH 3 way diaphragm valve of size 1\\" x 1/2\\" x 1\\" etc complete as per direction of Engineer-in-Charge. |
| 250 | PPH Pipe Supply, installation, testing and commissioning of PN 10 High purity PPH pipe of 25mm etc complete as per direction of Engineer-in-Charge. |
| 251 | Supply, installation, testing and commissioning of PN 10 High purity PPH pipe of 15mm etc complete as per direction of Engineer-in-Charge. |
| 252 | UPVC Pipe Supply, installation, testing and commissioning of PN 6 high purity UPVC pipe of 25mm etc complete as per direction of Engineer-in-Charge. |
| 253 | Supply, installation, testing and commissioning of PN 6 high purity UPVC pipe of 15mm etc complete as per direction of Engineer-in-Charge. |
| 254 | Guns Supply, installation, testing and commissioning of DI water PPH gun of 1/2\\" etc complete as per direction of Engineer-in-Charge. |
| 255 | General Exhaust Blower Supply and Installation of SISW centrifugal low noise level Blower housing shall be made of PPFRP. Pedestal and base frame of blowers is M.S epoxy painted/powdered coated. Impeller with dynamic balancing. Motor make CG/ABB. (IE2) 4500 m3/hr @ 150mmwg (1 Working + 1 Standby ) etc complete as per direction of Engineer-in-Charge. |
| 256 | Wet Scrubber - Supply and installation of Vertical type wet scrubber with liquid recirculation tank, recirculation pump dosing tank & dosing pump, PH sensor with the transmitter, exhaust sensor, differential pressure switch, exhaust blower (1w+ 1s) of the static pressure of 200mmwg and stack. Material: PP-FRP, Pressure drop across the scrubber column should be below 50mm wg (approx.), The design velocity for the scrubber column shall be 1.5 m/s. Interconnection piping between the scrubber, Re-circulation tank, and Dosing tank shall be considered. complete with makeup water connection with control valve, water level indicator, drain with control valve, overflow pipe, scrubber recirculation pump without Mechanical seal, inlet flange connection with 'Y' Strainer, outlet flanged connections with nonreturn valve (NRV), Ball valve with gaskets & bolt nuts, single stage PP packing rings. The blower stack shall be 7M in height. liquid spray nozzle system , Including Dosing Plug with Valve, Mounting Bolt & Nuts with Anti Vibration Pads,. Scrubber Pump of suitable motor rating, 3phase 50Hz, 415Volts. Including all pumps cover, Ladders etc complete as per direction of Engineer-in-Charge. |
| 257 | Solvent Scrubber Supply and installation of Vertical type Solvent scrubber with liquid recirculation tank, recirculation pump dosing tank & dosing pump, PH sensor with the transmitter, exhaust sensor, differential pressure switch, exhaust blower (1w+ 1s) of the static pressure of 200mmwg and stack. Material: PP-FRP, Pressure drop across the scrubber column should be below 50mm wg (approx.), The design velocity for the scrubber column shall be 1.5 m/s. Interconnection piping between the scrubber, Re-circulation tank, and Dosing tank shall be considered. complete with makeup water connection with control valve, water level indicator, drain with control valve, overflow pipe, scrubber recirculation pump without Mechanical seal, inlet flange connection with 'Y' Strainer, outlet flanged connections with nonreturn valve (NRV), Ball valve with gaskets & bolt nuts, single stage PP packing rings. The blower stack shall be 7M in height. liquid spray nozzle system , Including Dosing Plug with Valve, Mounting Bolt & Nuts with Anti Vibration Pads,. Scrubber Pump of suitable motor rating, 3phase 50Hz, 415Volts. Including all pumps cover, Ladders etc complete as per direction of Engineer-in-Charge. |
| 258 | PP - FRP Ducts Supply, installation, testing and commissioning of PP/FRP duct of 3mm PP thickness & 3mm FRP thickness, of below diameters for Acidic exhaust and general exhaust system etc complete as per direction of Engineer-in-Charge. |
| 259 | Supply, installation, testing and commissioning of PP/FRP duct of 3mm PP thickness & 3mm FRP thickness, ID 3\\" etc complete as per direction of Engineer-in-Charge. |
| 260 | Supply, installation, testing and commissioning of PP/FRP duct of 3mm PP thickness & 3mm FRP thickness, ID 4\\" etc complete as per direction of Engineer-in-Charge. |
| 261 | Supply, installation, testing and commissioning of PP/FRP duct of 3mm PP thickness & 3mm FRP thickness, ID 6\\" etc complete as per direction of Engineer-in-Charge. |
| 262 | Supply, installation, testing and commissioning of PP/FRP duct of 3mm PP thickness & 3mm FRP thickness, ID 8\\" etc complete as per direction of Engineer-in-Charge. |
| 263 | Supply, installation, testing and commissioning of PP/FRP duct of 3mm PP thickness & 3mm FRP thickness, ID 12\\" etc complete as per direction of Engineer-in-Charge. |
| 264 | Non return valves |
| 265 | Supply, installation, testing and commissioning of PP non return valve with flanges and other accessories of 12\\" etc complete as per direction of Engineer-in-Charge. |
| 266 | Supply, installation, testing and commissioning of PP non return valve with flanges and other accessories of 8\\" etc complete as per direction of Engineer-in-Charge. |
| 267 | PP - FRP Dampers |
| 268 | Supply, installation, testing and commissioning of PPFRP volume control damper with flanges and other accessories of 3\\" etc complete as per direction of Engineer-in-Charge. |
| 269 | Supply, installation, testing and commissioning of PPFRP volume control damper with flanges and other accessories of 4\\" etc complete as per direction of Engineer-in-Charge. |
| 270 | Supply, installation, testing and commissioning of PPFRP volume control damper with flanges and other accessories of 6\\" etc complete as per direction of Engineer-in-Charge. |
| 271 | Supply, installation, testing and commissioning of PPFRP volume control damper with flanges and other accessories of 8\\" etc complete as per direction of Engineer-in-Charge. |
| 272 | Supply, installation, testing and commissioning of PPFRP volume control damper with flanges and other accessories of 12\\" etc complete as per direction of Engineer-in-Charge. |
| 273 | DRAIN SYSTEM |
| 274 | Storage Tank for Acid drain -Supply, installation of 200 liter PP / FRP tank (pp 3 mm and FRP 3 mm thick) storage tank for Acid drain collection Tank should have a float Valve etc complete as per direction of Engineer-in-Charge. |
| 275 | Sprinkler system for Gas Cabinet |
| 276 | Storage Tank-Supply, installation, and testing of 1000 liter triple layer Syntex water storage tank with make-up connection, Outlet Connection and drain connection. Tank also should have a float Valve and low-level switch and a Stand for mounting the tank. Required for sprinkler system for the gas cabinets etc complete as per direction of Engineer-in-Charge. |
| 277 | Centrifugal Pump Supply, Installation, testing, and commissioning of horizontal split casing type centrifugal pump-motor sets of 60GPM @ 100 m WC capacity complete with nitrile rubber insulation, VFD compatible electrical motor, with pressure transmitter and control panel with starter and other associated standard accessories etc complete as per direction of Engineer-in-Charge. |
| 278 | GI Piping Supply, installation, testing and commissioning of GI piping of following sizes & C class for chilled water system complete with all required flanges, fittings, gaskets, fasteners, Nitrile rubber insulation covered with aluminium cladding and supports etc. NB 20 mm class C etc complete as per direction of Engineer-in-Charge. |
| 279 | Ball valve/ Drain valve Supply, installation, testing and commissioning of threaded end, PN 16/class-150, CI ball valves of following sizes for chilled water system complete with all required nipples, fittings, Nitrile rubber insulation covered with aluminium cladding etc complete as per direction of Engineer-in-Charge. |
| 280 | Non Return valve Supply, installation, testing and commissioning of threaded end, PN 16/class-150, CI NRV of following sizes for chilled water system complete with all required nipples, fittings, Nitrile rubber insulation covered with aluminium cladding etc complete as per direction of Engineer-in-Charge. |
| 281 | Electrical work :- cleanroom compatible Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 282 | Group C (Irrespective of any length) |
| 283 | Supplying and fixing cleanroom compatible following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 284 | 10 amp Switch |
| 285 | 6 amp socket |
| 286 | 6 amp 2 pin socket |
| 287 | Wiring cleanroom compatible for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required |
| 288 | Supplying and fixing cleanroom compatible following size/ modules, GI box alongwith modular base, cover & blanking plate for modular switches in recess etc. as required. etc as required. |
| 289 | 1 or 2 Module (75mmX75mm) |
| 290 | 3 Module (100mmX75mm) |
| 291 | 8 Module (125mmX125mm) |
| 292 | Supplying and fixing cleanroom compatible following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 293 | Telephone socket outlet RJ 11 |
| 294 | Supplying & Fixing cleanroom compatible of 3Pin, 5Amp. Ceiling rose on juction box with provinding round phinolic sheet, including making connections etc. as required. |
| 295 | Supplying and fixing of cleanroom compatible suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,after removing recessed existing board, disconnection making connections and testing etc. as required. |
| 296 | Supplying and fixing of cleanroom compatible suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 Nos. 3pin, 6 amps modular socket outlet with 1 No. 16 amp moduler switch and 1No. 6 pin 5/6 & 15/16 amps modular socket with 1no 16 amp moduler switch, blanking ,connection, painting etc. as required (different in colour of cover plate from general power for UPS / computer applications), making good the wall with matching colour distemper/ white wash etc. as required. |
| 297 | Supplying and fixing of cleanroom compatible suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 modular socket outlet and 10 A modular switch,after removing recessed existing board, disconnection making connections and testing etc. as required. |
| 298 | Supplying & fixing cleanroom compatible following amps rating, 240 volts, \\"C\\" curve, MCB suitable for inductive load of folloing pole with suitable size MCB box encloser with complete with connections, testing and commissioning etc. as required. |
| 299 | 32 amp Double Pole with encloser |
| 300 | 32 amp Four Pole with encloser |
| 301 | 63 amp Four Pole with encloser |
| 302 | Supplying and fixing of cleanroom compatible 32 A, 415 V, TPN (3P+N+E)Industrial type socket outlet, with 4 pole and earth plug top alongwith 32 A \\"C\\" curve, TP MCB, Housing made of self-extinguishing polymer/ sheet steel enclosure, on surface or in recess, cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 303 | Supplying and fixing of cleanroom compatible 32 A, 240 V, SPN (3P) Industrial type socket outlet, with 2 pole and earth plug top alongwith 32 A \\"C\\" curve, DP MCB, Housing made of self-extinguishing polymer/ sheet steel enclosure, in recess, cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 304 | Supplying and fixing of cleanroom compatible 63A, 415 V, TPN (3P+N+E) Industrial type socket outlet, with 4 pole and earth plug top alongwith 63 A \\"C\\" curve, TP MCB, Housing made of self-extinguishing polymer/ sheet steel enclosure, on surface or in recess, cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 305 | SITC of cleanroom compatible MCCB in CRCA sheet steel enclosure complete with four pole Moulded Case Circuit Breaker (Ics Value 18KA), Adjustable Thermal & Fixed Magnetic setting, suitable for incoming & outgoing termination including powder coating etc. complete as per specification & as required. |
| 306 | 125 Amp FP MCCB. |
| 307 | 63 Am FP MCCB |
| 308 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with cover (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 309 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 310 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 311 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 312 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 313 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 314 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" with cover (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 315 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 316 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 317 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 318 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 319 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 320 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" with cover (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient with G.I. suspenders including G.I. bolts & nuts, etc. as required |
| 321 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 322 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 323 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 324 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 325 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 326 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross memberwith cover\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required |
| 327 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 328 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 329 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 330 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 331 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 332 | Supplying and installing cleanroom compatible following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer with cover\\" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. |
| 333 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 334 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 335 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 336 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 337 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. sections, joined with connectors, suspended from the ceiling |
| 338 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 339 | 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire |
| 340 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 341 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 342 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 343 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 344 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 345 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. |
| 346 | 2 x 1.5 Sq. mm |
| 347 | 3 x 1.5 Sq. mm |
| 348 | 4 x 1.5 Sq. mm |
| 349 | 5 x 1.5 sq. mm |
| 350 | 6 x 1.5 Sq. mm |
| 351 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 352 | 2 Pair |
| 353 | Supply installation and testing and commissioning of follwing size of Telephone distribution board in a M.S. box with hinged cover/ door complete with krone type tag block with double jumpering facility mounted on a bakelite sheet etc. including terminations of cable as required. |
| 354 | 50 Pair telephone distribution board |
| 355 | Supply of follwing sizes of 0.61mm/.50mm diameter annealed tinned copper conductor PVC insulated and PVC sheathed armoured telephone cable conforming to ITDS/WS-113C & 114 on existing cable tray and or surface or existing surface/ recess steel conduit complete as required. |
| 356 | 20 Pair |
| 357 | Laying and fixing of one number Telephone armoured cable (PVC insulated and PVC sheathed/XLPE power cable ) of 1.1 KV grade of following sizes direct in ground including excavation, sand cushioning protective covering and refilling the trench etc. as required. |
| 358 | 20 Pair |
| 359 | Laying and fixing of one number Telephone armoured cable (PVC insulated and PVC sheathed/XLPE power cable ) of 1.1 KV grade of following sizes on wall surface as required. |
| 360 | 20 Pair (Clamped with 1mm thick saddle) |
| 361 | Supplying & Fixing of following sizes of steel conduit along with heavy duty accessories, junction box etc. in surface / recesse including painting in case of surface conduit, or cutting the wall, repair and making good the same as required. |
| 362 | 20 mm |
| 363 | 25 mm |
| 364 | 32 mm |
| 365 | Supplying and drawing of 23 AWG UTP Data Cable (CAT 6) gigaspeed LAN Cable in the existing surface/ recessed Steel/ under floor trunking as required. |
| 366 | 1 run of cable |
| 367 | P & F of cleanroom compatible following modular accessories made out of unbreakable and fire retardant poly carbonate with silver contacts Simplex Faceplate with RJ-45, information outlet with shutter with colour coding on existing modular plate, including making connections testing etc. as required |
| 368 | Light and Fan |
| 369 | Supply of following sizes of BLDC energy saver ( 5 star rated) ceiling fan without regulator complete with double ball bearing, motor, blades, down rod, canopy, etc. complete as required. |
| 370 | Size 1400 mm. |
| 371 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of length upto 30 cm with 1.5sq.mm FRLS PVC insulated copper conductor single core cable etc. complete as required. |
| 372 | P & F 18 swg M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. |
| 373 | Supplying of recessed mounted 36 Watt full glow, slim energy efficient, Green Square 2'x2' LED 110 lu/w, 6500 K lighting luminaires approved make complete with hanging arrengment all accessories, metallic CRCA powder coated housing etc. complete as required. |
| 374 | Supplying of recessed mounted 36 Watt full glow, slim energy efficient, PIR based 2'x2' LED lighting luminaires with THD 10% (+5% ) <, Efficiency > 90 % , oprating voltage 140-270V, body made of CRCA approved make complete with hanging arrengment all accessories, metallic CRCA powder coated housing with OEM 3 year Guarantee etc. complete as required. |
| 375 | Installation, testing and commissioning of above LED tube light fittings complete with all accessories on surface of wall/ ceiling or suspended from ceiling including providing hanging arrengment , transperent/suitable connection wire/ 1.5Sq.mm FR PVC copper conductor etc. as required. |
| 376 | Supplying of surface mounted of 75 watt, flood Light efficency 110 lm/W, 6500K, IP66/ IK08, input voltage 140-270V, 50Hz, oprating temprature -10⁰C to 45⁰C (Ta45⁰C), material- Housing: Aluminum Die-casting Cover: Tempered glass of high transmittance Lens: PC with BIS Certification LED Flud Light with approved make. |
| 377 | Installation, testing and commissioning of above LED Flood light fittings complete with all accessories on surface of wall/ ceiling or suspended from ceiling including providing hanging arrengment, U clamp , suitable connection wire/ 1.5Sq.mm FR PVC copper conductor etc. as required. |
| 378 | Design, supply, installation, fixing, and testing of the complete surface mounted 36 Watt full glow, energy efficient monochromatic yellow colour Teardrop Cleanroom compatible LED Light with hanging arrangment like T-Grid slot etc, oprating voltage 220-240V, 105 Lum/w, Ingress protection IP40 [Wire-protected], Fixation material Stainless steel, Overall length 1100 mm approved make complete with fixing arrengment all accessories, with OEM 2 year Guarantee etc. complete as required. |
| 379 | Design, supply, installation, fixing, and testing of the complete surface mounted 36 Watt full glow white fluorescent white CCT 5700 K colour Tear Drop Cleanroom compatible LED light 40W with hanging arrangment like T-Grid slot, oprating voltage 220-240V, 105 Lum/w, Ingress protection IP40 [Wire-protected], Fixation material Stainless steel, Overall length 1100 mm approved make complete with fixing arrengment all accessories, with OEM 2 year Guarantee etc. complete as required. |
| 380 | Supplying of Surface / Ceiling mounted LED light fixture-145 x 1200mm, 30/32 W Cool White Smart Brite Surface Light, 6500 K with approved make including, connection wire of suitable length, all accessories etc. as required. |
| 381 | Supplying of Surface / Ceiling mounted LED Batten, extruuded Aluninium housing light fixture- 1127 x 40 x46mm, 40 W Cool White Smart Brite Surface Light, 6500 K, 105lm/w, safty class II, input volatge 220-240 V, Ingress protection IP20 connection wire of suitable length, all accessories etc. as required. |
| 382 | Installation, testing and commissioning of above LED tube light fittings complete with all accessories on surface of wall/ ceiling or suspended from ceiling including providing 1.5Sq.mm FR PVC copper conductor etc. as required. |
| 383 | Supplying and installation of surface mounted 18 Watt full glow, energy efficient, circuler LED lighting luminaires, 6500K, Housing Material Aluminium pressure die cast, approved make complete with fixing arrengment all accessories, ABS/metallic CRCA powder coated housing etc. complete with installation as required. |
| 384 | SITC of wall/ surface mounted dust and vermin SMC Junction box (200 x 140 x 95) with 4 Point connector and 6 amp MCB approved make with mcb Din rail detachable gland plate, locking arrangement for equipment/ switchgear |
| 385 | P & F of heavy duty capacitor start Exhaust fan Size-300 mm sweep, 900 RPM, single phase, IS: 2312 marked of approved make in existing opening including grouting of metal fastener with bolts, nuts making connections , testing etc. as reqd. |
| 386 | P & F of heavy duty capacitor start Exhaust fan Size-380 mm sweep, 1400 RPM, single phase, IS: 2312 marked of approved make in existing opening including grouting of metal fastener with bolts, nuts making connections , testing etc. as reqd. |
| 387 | P & F of gravity louver shutter of superior quality made out of frame of 18 SWG MS sheet & louvers made from 24 swg Al. sheet with nut bolts enamel paint etc as required. Size Up to 380mm. ( for 300 mm and 380mm Exhaust Fan) |
| 388 | Supply of XLPE insulated PVC sheathed 1.1 kv. Grade Cu./Al. conductor armoured Cable IS: 7098 Part-1 of approved make. |
| 389 | 4 X 6 Sqmm Cu.. Cable |
| 390 | 3 X 10 Sqmm Cu.. Cable |
| 391 | 4 X 10 Sqmm Cu.. Cable |
| 392 | 4 X 16 Sqmm Cu.. Cable |
| 393 | 4 X 25 Sqmm Cu.. Cable |
| 394 | 3.5 X 35 Sqmm Cu.. Cable |
| 395 | 3.5 X 50 Sqmm Cu.. Cable |
| 396 | 3.5 X 95 Sqmm Cu.. Cable |
| 397 | 3.5 X 240 Sqmm Cu. Cable |
| 398 | 3 X 10 Sqmm Al.. Cable |
| 399 | 3.5 X 300 Sqmm Al. Cable |
| 400 | 3.5 X 400 Sqmm Al. Cable |
| 401 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 402 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (upto 180 CM below ground level as required) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 403 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 404 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 405 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing existing RCC/HUME/ METAL /GI /CI /Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air as required. |
| 406 | Upto 35 sq. mm |
| 407 | Above 35 sq. mm and upto 95 sq. mm |
| 408 | Above 185 sq. mm and upto 400 sq. mm |
| 409 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade on wall/ roof/ shaft including fixing by means of screws & rag bolts, suitable size MS U clamps complete as per specifications, repairing works etc as reqd. of following sizes of cables. |
| 410 | upto 35 Sqmm.(clamped with 1mm thick saddle) |
| 411 | above 35 sqmm upto 95 Sqmm.(clamped with 1mm thick saddle) |
| 412 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. |
| 413 | Above 185 sq. mm and upto 400 sq. mm |
| 414 | Supply& making one end termination with heavy duty single compression brass gland SIBG type, aluminium/ copper lugs duly crimped with crimping tool, PVC tape etc. for following size of XLPE insulated & PVC sheathed aluminium/ copper cable of 1.1 KV grade as required. |
| 415 | 2 X 6 sq. mm |
| 416 | 3 X 10 sq. mm |
| 417 | 4 X 10 sq. mm |
| 418 | 4 X 16 sq. mm |
| 419 | 4 X 25 sq. mm |
| 420 | 3½ X 35 sq. mm |
| 421 | 3½ X 50 sq. mm |
| 422 | 3½ X 95 sq. mm |
| 423 | 3½ X 240 sq. mm |
| 424 | 3½ X 300 sq. mm |
| 425 | 3½ X 400 sq. mm |
| 426 | Supply of HT cable of 11 KV grade (earthed) stranded compact circular aluminium conductor, condutctor screen with extruded semi conductor compound, XLPE insulated, insulation screening with extruded semi conductor compound in combination with copper tape (0.3 KA for 1 sec), cores laid up, inner sheath of PVC tape, galvanized steel flat strip armoured, overall PVC Sheathed cable confirming to IS 7098 (Part II) 1985 (amended upto date) of following size |
| 427 | 3 Core, 240 Sq.mm. |
| 428 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground below 1.2mtr. including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 429 | Above 120 sq. mm and upto 400 sq. mm |
| 430 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/HUME/ METAL pipe as required. |
| 431 | Above 120 sq. mm and upto 400 sq. mm |
| 432 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required. |
| 433 | Above 120 sq. mm and upto 400 sq. mm |
| 434 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
| 435 | 240 sq. mm |
| 436 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
| 437 | 240 sq. mm |
| 438 | Supplying and fixing of ,4 Way three pole and neutral, prewired, sheet steel, per phase isolation ( PPI ) MCB distribution board, 415 volts on surface / recess, complete with loose wire box, Incomer 1No. 63A, 4 Pole isolator, Outgoings- 3Nos. DP RCCB 40A, 240 volts, having a sensitivity current 30 milliamperes, 12 Nos. SP AC MCB-32A, 10KA, 240V ( 'C' curve ), terminal blocks, duly prewired with suitable size FRLS PVC insulated copper conductor upto terminal blocks, tinned copper bus bar, seperate neutral links for each phase, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted, making internal DB terminations with copper lugs including all the existing incoming/ outgoing connections, earthing, testing, repair & making good the wall with matching colour distemper/ white wash etc. as required. |
| 439 | Supplying and fixing of ,4 Way three pole and neutral, prewired, sheet steel, per phase isolation ( PPI ) MCB distribution board, 415 volts on surface / recess, complete with loose wire box, Incomer 1No. 63A, 4 Pole isolator, Outgoings- 3Nos. DP RCCB 40A, 240 volts, having a sensitivity current 30 milliamperes, 12 Nos. SP AC MCB-10A, 10KA, 240V ( 'C' curve ), terminal blocks, duly prewired with suitable size FRLS PVC insulated copper conductor upto terminal blocks, tinned copper bus bar, seperate neutral links for each phase, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted, making internal DB terminations with copper lugs including all the existing incoming/ outgoing connections, earthing, testing, repair & making good the wall with matching colour distemper/ white wash etc. as required. |
| 440 | Supplying and fixing of ,6 Way three pole and neutral, prewired, sheet steel, per phase isolation ( PPI ) MCB distribution board, 415 volts on surface / recess, complete with loose wire box, Incomer 1No. 100A, 4 Pole isolator, Outgoings- 3Nos. DP RCCB 63A, 240 volts, having a sensitivity current 30 milliamperes, 18 Nos. SP AC MCB-32A, 10KA, 240V ( 'C' curve ), terminal blocks, duly prewired with suitable size FRLS PVC insulated copper conductor upto terminal blocks, tinned copper bus bar, seperate neutral links for each phase, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted, making internal DB terminations with copper lugs including all the existing incoming/ outgoing connections, earthing, testing, repair & making good the wall with matching colour distemper/ white wash etc. as required. |
| 441 | Supplying and fixing of ,12 Way SPN, MCB distribution board, 240 volts on surface / recess, complete with loose wire box, Incomer 1No. 40A, DP isolator, Outgoings- 1No. DP RCCB 40A, 240 volts, having a sensitivity current 30 milliamperes, 8 Nos. SP AC MCB-32A, 10KA, 240V ( 'C' curve ), terminal blocks, duly prewired with suitable size FRLS PVC insulated copper conductor, tinned copper bus bar, seperate neutral links for phase, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted, making internal DB terminations with copper lugs including all the existing incoming/ outgoing connections, earthing, testing, repair & making good the wall with matching colour distemper/ white wash etc. as required. |
| 442 | P & F Recessed/ surface mounting vertical type heavy duty Double door type TPN-4 way sheet steel phosphatised powder painted Distribution Board with loose wire box, with incomer 1No. 4 pole MCCB-160A, 25 KA and 4 Nos. TP AC MCB-63A 10KA ( 'C' breaking characteristic) for outgoing circuits, 250 Amp busbar, neutral link, earth bar & din rail etc conforming to IS; 13032, IS; 8623, BS; 5486 of approved make including making all the incoming/ outgoing connections, internal DB terminations with copper lugs, testing etc. as required. |
| 443 | P & F Recessed/ surface mounting vertical type heavy duty Double door type TPN-6 way sheet steel phosphatised powder painted Distribution Board with loose wire box, incomer 1No. 4 Pole MCCB-125A, 18KA and 2 Nos. TP AC MCB-63A 10KA ( 'C' breaking characteristic), 3 Nos. TP AC MCB-32A 10KA ( 'C' breaking characteristic) and 3 Nos. SP AC MCB-32A 10KA ( 'C' breaking characteristic)for outgoing circuits, 125 Amp busbar, neutral link, earth bar & din rail etc conforming to IS; 13032, IS; 8623, BS; 5486 of approved make including making all the incoming/ outgoing connections, internal DB terminations with copper lugs, testing etc. as required. |
| 444 | P & F Recessed/ surface mounting vertical type heavy duty Double door type TPN-6 way sheet steel phosphatised powder painted Distribution Board with loose wire box, incomer 1No. 4 Pole MCCB-125A, 18KA and 3 Nos. TP AC MCB-32A 10KA ( 'C' breaking characteristic) and 9 Nos. SP AC MCB-32A 10KA ( 'C' breaking characteristic)for outgoing circuits, 125 Amp busbar, neutral link, earth bar & din rail etc conforming to IS; 13032, IS; 8623, BS; 5486 of approved make including making all the incoming/ outgoing connections, internal DB terminations with copper lugs, testing etc. as required. |
| 445 | P & F Recessed/ surface mounting vertical type heavy duty Double door type TPN-8 way sheet steel phosphatised powder painted Distribution Board with loose wire box, incomer 1No. 4 Pole MCCB-160, 25KA and 4 Nos. TP AC MCB-63A 10KA ( 'C' breaking characteristic), 3 Nos. TP AC MCB-32A 10KA ( 'C' breaking characteristic) and 3 Nos. SP AC MCB-32A 10KA ( 'C' breaking characteristic)for outgoing circuits, 250 Amp busbar, neutral link, earth bar & din rail etc conforming to IS; 13032, IS; 8623, BS; 5486 of approved make including making all the incoming/ outgoing connections, internal DB terminations with copper lugs, testing etc. as required. |
| 446 | P & F Recessed/ surface mounting vertical type heavy duty Double door type TPN-12 way sheet steel phosphatised powder painted Distribution Board with loose wire box, incomer 1No. 4 Pole MCCB-250A, 25KA and 6 Nos. TP AC MCB-63A 10KA ( 'C' breaking characteristic), 5 Nos. TP AC MCB-32A 10KA ( 'C' breaking characteristic) and 3 Nos. SP AC MCB-32A 10KA ( 'C' breaking characteristic)for outgoing circuits, 250 Amp busbar, neutral link, earth bar & din rail etc conforming to IS; 13032, IS; 8623, BS; 5486 of approved make including making all the incoming/ outgoing connections, internal DB terminations with copper lugs, testing etc. as required. |
| 447 | Plate Earthing as per IS: 3043 with copper earth plate 600 x 600 x 3 mm thick by embodying 4 mtr below the ground lavel with alternate layers of salt and charcoal (95 kg. each) with 20 mm dia G.I. B class watering pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete and testing of earth resistance as required. |
| 448 | P/F 25mm x 5mm copper strip in 40mm dia G.I. Pipe from earth electrode. including connection with brass nut bolt spring washer excavation and refilling as rqd. |
| 449 | Providing and fixing 25 mm X 5 mm copper strip on surface/wall with providing insulating support for connections etc. as required. |
| 450 | Earthing as per IS:3043 with G.I earth plate 600 x 600 x 6 mm thick including accessories embodying by digging 4mtr below the ground lavel with alternate layers of salt and charcoal (95 kg. each) with 20mm dia G.I. B class watering pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete and testing of earth resistance as required. |
| 451 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 452 | Providing and fixing 25 mm X 5 mm G.I strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 453 | Providing & fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. Tube, having single prong at top, with 85mm dia 6mm thick G.I. Base plate including holes etc. complete as required. |
| 454 | Rivetting, sweating and soldering of copper/GI tape (with another copper/GI tape, base of the finial or any other metallic object) as required. |
| 455 | Providing and fixing GI tape 20mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run) |
| 456 | Providing and fixing GI tape 20mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run) |
| 457 | Providing and fixing testing joint made of 20mm x 3mm thick GI strip 125mm long with 4No. G.I. bolts, nuts, check nuts, spring washer etc. complete as required. |
| 458 | Design, supply, installation, fixing, and testing commissioning of the complete of micro processor based intelligent addressable main fire alarm panel, central processing unit with the Two Loop Panel modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 459 | Two Loop Panel |
| 460 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 461 | Supplying, installation, testing & commissioning of cleanroom compatible intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 462 | Supplying, installation, testing & commissioning of cleanroom compatible smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 463 | Supplying, installation, testing & commissioning of cleanroom compatible response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 464 | Supplying, installation, testing & commissioning of cleanroom compatible intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 465 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 466 | Supplying, installation, testing & commisssioning of cleanroom compatible intelligent addressable programmable sounder complete as required. |
| 467 | Supplying, installation, testing & commissioning of addressable fire control module complete as required |
| 468 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 469 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
| 470 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 471 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 472 | Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or separate) complete with emitter and receiver including connections with remote test features etc complete as required. |
| 473 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH outer sheath complete as required |
| 474 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 475 | Supply, Installation, Testing & Commissioning of D.P. Structure with AIR BREAK SWITCH having following specifications: DP :double pole structure on 2no ISMB 125mm x 70mm, 10 mtr high pole using 7 no MS channel each of size (100mm x 50mm x 6mm) x 2500mm (9.5Kg per mtr.)complete in all respect in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling and secured with holding clamps, springs washers, clamps bolts, nuts, etc. as required. GO: 11 KV outdoor type 3 Pole gang operated, tripple pole, 400 Amps rating, Central pot rotating double break GO switch on the existing DP structure complete with all accessories for assembly and operation as per the specification and IS – 1818/1972 and IS – 9920 (Part I to IV / Latest version), 9Nos. post insulators of 12KV (IS: 2554 & IS:5350 part III), bimetallic connector mounted horizontal or vertical position on provided cross arm with adequate length of G.I. Pipe 'B' class- 32mm dia. including S/E of operating pipe and handle supporting arrangement of MS flat 50 x 6 mm and channel iron 100mm x 50 mm size with required Nos. and size of MS nuts and bolts for operating handle erected on extended square shaft. The operating handle provided with locks in ‘ON’ position & locks in ‘OFF’ position with key at suitable height( 3' ) from ground level with necessary clamps, hot dipped galvanised hardware, nut, bolts etc complete in all respect. |
| 476 | (Tested by ERDA/ CPRI & The entire G.O.switch assembly/ unit should be properly bonded to the existing earth and the job is to be completed to the entire satisfaction of the Engineer-in-Charge DO: 3nos 11 KV, rated current 400 Amps, DO fuse assembly as per relevant IS on existing DP structure complete with mounting base, post insulators, hot dipped G.I. harware , clamps, operating rod, terninal connector including fuse rating 60Amps etc. LA: 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv OH line with rated voltage of 9kv rms & nominal discharge current rating of 10 KA & complete with galvanized clamping arrangement GI bolts, nuts, washer, fitted on existing DP structure etc as required. JUMPERS: 3 Nos. 11kv ACSR conductors mounted on pin type insularors as required. |
| 477 | Supplying and erection of galvanised stay set for 11 kV over head lines complete with 19/ 20 mm dia X 1.8 meter long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle (20 mm X 600 mm), 7/ 4.00 mm dia G.I. stay wire and 11 kV strain insulator etc. in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 478 | Supply, installation, testing and commissioning of following capacity (continuous loading) BEE 5 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender), 11/0.433 KV step down, 3 Phase,50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for outdoor/indoor applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) forautomatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 1x185 sqmm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS: 2026 (Part 1 to Part 5), IS: 1180 and duly ISI Marked and as per standerd specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percentcombined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 40 dg.C for oil and 45 dg. C for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. |
| 479 | For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition: a) air temperature 50 deg C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked.Fitting and Accessories: The following fittings shall be provided: -a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oillevel at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal sizethread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above; k) Onefilter valve on the upper side of the tank Inspection hole; n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators with suitable tripping mechanism above permissible limit s) t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug, bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. 1000 KVA |
| 480 | Supplying, installation testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB Panel with VCBs (1 No. incoming & 1 Nos. outgoing) totally enclosed & fully interlocked, horizontal drawout, horizontal / vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto / manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz. A.C. supply with short circuit fault level of 350 MVA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 800 Amps. capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO. + 4 NC and equipped with following switchgears and accessories i/c connections suitable for 3x240 Sqmm. XLPE 11 KV cable (cable entry from bottom / top / side) end termination with heat shrinkable jointing material etc. ( Note : cost of end termination not included in this item) Incoming Panel & Outgoing i) 630 Amp. 350 MVA 26 KA VCB = 1 Set ii) Breaker control switch. = 1 Set iii) 24 V DC Tripping Coil. = 1 Set iv) 24 V DC Closing Coil. = 1 Set v) 240 V AC spring charge motor. = 1 Set vi) Set of ON &OFF indicating lamps. = 1 Set vii) Phase indicating lamps (RYB).= 3 Set viii) Clear lamp for trip circuit health supply. = 1 Set ix) (0-80 A) dual scale digital type ammeter, selector switches for ammeters. = 1 Set x) Aux. relays for Anti Pumping & indication = 1 Set xi) Tripping relay for fault = 1 Set xii) Trip circuit supervision relay = 1 Set xiii) In built Power Pack with 220 volt AC input from auxilary supply and 24 volt DC continuous output suitable for closing/ tripping/indication of 3 Nos. HT Panel boards, charging unit, capacitor bank for emergency delivering for trip system complete with suitable capacity of ammeter & voltmeter i/c connection etc. as required = 1 Set xiv) Microprocessor based numerical relay with O/L, E/F and S/C protection communication ready = 1 Set |
| 481 | xvi) Dual core dual ratio 3 No. CTs 80/40/5/5 A of 15 VA burden and accuracy Class-0.5 for metering and class 5P10 for protection. = 1 Set xvii) 11 KV /110 Volts PT Class 0.5 accuracy and 100 VA burden with 1 No. Digital type Voltmeter (0 15 KV), digital type selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer. = 1 Set xviii) Cable end box for termination of 1 No. 3 C x 240 sq.mm XLPE cable as incoming. xix) Necessary strip heater to prevent absorption of moisture during winter and monsoon. xx) Alarm annunciator with buzzer, ACK, test push button for transformer faults and electrical faults. =2 Sets xxi)Test terminal block, fuses , circuit lables. Indicating Amps. As per standard practice. xxii) Necessary strip supply healthly indicator lamp. xxiii) 1 No - Amber for Trip indication. xxiv) Rear cable entry box suitable for termination of cable of size 3 x 240/300 Sq.mm XLPE cable. |
| 482 | Supply of following items for substation. |
| 483 | Rubber hand gloves suitable for 11KV. |
| 484 | Supply & fixing of shock treatment chart both in Hindi & English for treating person suffering due to electric shock mounted on wall hooks. |
| 485 | Providing and fixing H.T. danger notice plate of 250 mm x 200mm, made of mild steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required. |
| 486 | Providing and fixing M.V. danger notice plate of 200 mm x 150mm, made of mild steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required. |
| 487 | Supplying & fixing of CO₂ type fire extinguisher 4.5 Kg capacity ISI marked confirming to IS:15683:2006 complete with delivery hose horn, squeeze grip release valve, locking arrangement, operation manual, bracket with two screw and sleeve etc. as required. |
| 488 | Supplying and fixing ABC Fire Extinguisher 6 kg capacity (Stored pressure type) duly ISI marked conforming to IS 15683:2006 with IS14609 ABC powder complete with Squeeze grip release valve discharge pipe locking arrangment operation manual valve suspendet bracket with complete as reqd. |
| 489 | Supply and fixing safety instruction chart on wall duly framed with 5mm thick glass required. |
| 490 | Providing of set of 4 Nos. 9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red - oxide paint and written with white paint 'Fire' and mounted on MS angle iron frame with bracket of appropriate size and cpapcity including filling sand etc. |
| 491 | Providing of rubber mat 1 mtr. (wide) and 12mm thick to withstand 33KV dielectric strength as per IS 15652- 2006. |
| 492 | Design, Supply, Installation, Testing and Commissioning of cubical type Main L.T. panel suitable for 415V, 3 Phase, 4 wire, 50Hz AC supply system fabricated in compartmentalized (perferably) designed from CRCA sheet steels of 2mm thick for frame work and cover, 3mm thick for gland plates, face area 3.2 sqmtr and 1000mm deep including cleaning and finishing complete with 7 tank process for powder coating in approved shade and having 2500Amp capacity extensible type TPN copper bus bars of high conductivity, DMC / SMC bus bar supports, with short circuit withstand capacity of 31MVA for 1 Sec. bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar size of 50mm x 10mm at the rear with 2 Nos. earth stud, solid connections from main bus bars to switchgears with required sizes of copper bus bar and control wiring with 2.5sq.mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half including providing following switch gears :- INCOMER TPN copper bus bars of minimum 2500 Amp capacity with shrinkable coloured sleeves and including DMC / SMC bus bar supports at required intervals complete for cross section, size supports and their spacing etc. for withstanding fault level of 31MVA for 1 Sec. OUTGOING 2 Nos. 1600 Amps four pole horizontal Drawout type Air Circuit Breaker for fault breaking capacity of 50KA (ICS = Icu upto 433 Volts) manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON / OFF and service / test / isolated position indicators and frame earthing contact, conforming to IS : 13947-2, 1993 as amended upto date complete with following accessories for each ACB. |
| 493 | Incomer shall have one set of the following items: 1 No. Independent manual spring closing mechanism. 1 Set Microprocessors release (EMI & EMC certified) for over current, earth fault & short circuit protection. 1 Set 96mm square flush pattern digital type voltmeter (0-500 V) with selector switch & back up MCBs.1 Set 96mm square flush pattern digital type Ammeter (0-2500 Amp) with selector switch & one set of 3 Nos. CT's of Ratio 2500 /5A class - I accuracy and 15VA burden. 6 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker \\"ON\\" indicating light with 2A MCB test terminal block set, MCB, circuit as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. Shunt trip coil 220V A.C. 3 No. 1600 / 5 Amp CT for APFC Panel |
| 494 | Design, Fabrication, supplying, installation, testing and commissioning of cubical type LT panel suitable for 415 V, 3 phase, 4 wire 50 Hz AC supply system having minimum front area of panel as face area should be 12.6 Sq. Mtr. and 950 mm deep fabricated in compartmentalised design from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates including cleaning and finishing complete with 7 tank process for powder coating in approved shade, having 2000 Amp capacity extensible type TPN Copper bus bars of high conductivity, DMC/SMC bus bar supports, with short circuit withstand capacitiy of 31 MVA for 1 sec. bottom base channel of MS section not less than 100mm x 50mm x 5mm transportable sections, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of aluminium bus bars and control wiring with 2.5 Sq. mm PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears:- Incoming:- 2 No. 1600. Amps four pole horizontal motorised drawout type air circuit breaker of fault breaking capacity 50 KA (Ics= Icu) electrically drawout type/Motorized spring charged mechanism (control On/off by TNC ) with manual charging facility, fitted with inerlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS:13947-2 1993 as amended with automatic spring charging upto date with battery backup with charger for TNC Control etc complete with following accessories for each ACB. Independent manual spring closing mechanism -- 1 No. for each ACB. Microprocessor release for over current, earth fault and short circuit protectiion -- 1 Set for each ACB. Digital Voltmeter 96 mm square flush pattern type voltmeter (0-500 Volt), with selector switch and back up 2 Amps. SP MCB-- 1 Set for each ACB. Digital Ampear 96 mm square flush pattern type ammeter (0-1500 Amp), with selector switch and one set of 3 Nos. CTs of ratio 2000/5A Class I accuracy and 15 VA burden -- 1 Set for each ACB. |
| 495 | 3 Nos. phase indication LED lamp with 2 Amp back up SP MCB , breaker 'ON'or 'OFF' indicating light with 2A SP MCB, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. --- 1 Set for each ACB. Shunt trip coil 220V AC. Auto Manual Salecter switch. Bus Couplers :- 1 No. 1600. Amps four pole horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics= Icu) electrically drawout type, fitted with inerlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS:13947-2 1993 as amended with automatic spring charging upto date with battery backup with charger for TNC Control etc complete with following accessories for each ACB (but without O/C and E/F protection.Independent manual spring closing mechanism -- 1 No. for each ACB. Breaker 'ON' indicating light with 2A SP MCB , test terminal block set, fuses, circuits as per standard practice, auxiliary contacts as required for positive interlocking of the breakers as required -- 1 Set. Breaker ON/OFF control with TNC Control . Bus Bar:-TPN Copper Bus bars of minimum of 2000 Amp capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports and their spacing etc for withstanding fault level of 31 MVA for 1 Sec. Interlocking:-Electrical through advance contacts in ACBs (Incomer and bus couplers) and mechanical (castle key) interlocking should be provided to ensure that only one supply is available at a time on each section of bus and to eliminte any possibility of accidentally approaching two supplies at one bus section.Outgoings:- 1 No. 1000. Amps four pole horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics= Icu) electrically drawout type, fitted with inerlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS:13947-2 1993 as amended with automatic spring charging upto date complete with following accessories for each ACB (but without O/C and E/F protection. |
| 496 | 4 No- quick make and quick break current limiting 4P MCCB 320 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required.4 No- quick make and quick break current limiting 4P MCCB 400 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required.7 No- quick make and quick break current limiting 4P MCCB 125 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required.3 No- quick make and quick break current limiting 4P MCCB 160 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required.3 Nos. phase indication LED lamp with 2 Amp back up SP MCB, breaker 'ON' or 'OFF' indicating lights with 2A SP MCB, test terminal block set, fuses, circuits as per standard practice as required -- 1 set for each MCCB -- 1 Set for each MCCB.40 Amps DP MCB.19 sets suitable size TP&N Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for outgoing ckts. |
| 497 | Design, Supply of free standing floor mounted dust and vermin proof, compartmentalised cubical panel made out of CRCA sheet, face area 3.57 sq. mtr. and 400 mm deep, required hardware, duly painted by 7 tank process powder coating with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate, 100x50x6mm M.S. base channel, hinged door with locking arrangement for equipment/ switchgear/ busbar chamber/ cable alley . Thickness of sheet shall not be less than 2.0mm of any compartment. Load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls compartments having bolted type doors with detachable extension type structure. S/F of following accessories and their inter connections with lugs, terminating all the outgoing and incoming supply terminals in cable alley fixed on SMC/DMC type insulators (as per requirement) with suitable size copper strip with heat shrinkable PVC sleeves/ wire, suitable 25 X 5 size earth copper strip through out run at the bottom of the panel testing etc as required.INCOMER -a) 1No- quick make and quick break 4 Pole current limiting MCCB 630 Amp., 50 KA adjustable O/L & adjustable S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required for incoming supply.BUSBARS.- b) 1Set-TPN copper bus bars of minimum 800 Amp capacity with heat shrinkable coloured sleeves including DMC / SMC bus bar supports at required intervals complete for cross section, size supports and their spacing etc. c) 1Set- 96mm square flush pattern digital type voltmeter (0-500V) with builtin selector switch & 2Amp. back up MCBs. d) 1Set- 96mm square flush pattern digital type Ammeter (0- 200Amp) with builtin selector switch & one set of 3 Nos. CT's of Ratio 600 /5A for each set, class - I accuracy and 15VA burden. e) 3Nos. Phase indication LED lamps with 2Amp back up MCBs. |
| 498 | f) 1set TP&N suitable size Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for incoming ckt. OUTGOING:- a) 3 No- quick make and quick break current limiting 4P MCCB 400 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required. b) 1 No- quick make and quick break current limiting 4P MCCB 250Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required. c) 3 Nos- quick make and quick break current limiting 4P MCCB 160 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required. d) 2 Nos- quick make and quick break current limiting 4P MCCB 125 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required. e) 9 sets suitable size TP&N Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for outgoing ckts. |
| 499 | Design, Supply of free standing floor mounted dust and vermin proof, compartmentalised cubical panel made out of CRCA sheet, face area 1.80 sq. mtr. and 350 deep, required hardware, duly painted by 7 tank process powder coating with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate, 100x50x6mm M.S. base channel, hinged door with locking arrangement for equipment/ switchgear/ busbar chamber/ cable alley . Thickness of sheet shall not be less than 2.0mm of any compartment. Load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls compartments having bolted type doors with detachable extension type structure. S/F of following accessories and their inter connections with lugs, terminating all the outgoing and incoming supply terminals in cable alley fixed on SMC/DMC type insulators (as per requirement) with suitable size copper strip with heat shrinkable PVC sleeves/ wire, suitable 25 X 5 size earth copper strip through out run at the bottom of the panel testing etc as required.Area of board should not less than 5.49 Sqmtr.(as per line diagram). INCOMER - a) 1No- quick make and quick break 4 Pole current limiting MCCB 400 Amp., 50 KA adjustable O/L & adjustable S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required for incoming supply. BUSBARS.- b) 1Set-TPN copper bus bars of minimum 400 Amp capacity with heat shrinkable coloured sleeves including DMC / SMC bus bar supports at required intervals complete for cross section, size supports and their spacing etc. c) 1Set- 96mm square flush pattern digital type voltmeter (0-500V) with builtin selector switch & 2Amp. back up MCBs. d) 1Set- 96mm square flush pattern digital type Ammeter (0- 200Amp) with builtin selector switch & one set of 3 Nos. CT's of Ratio 300 /5A for each set, class - I accuracy and 15VA burden. e) 3Nos. Phase indication LED lamps with 2Amp back up MCBs. |
| 500 | f) 1set TP&N suitable size Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for incoming ckt. OUTGOING:- a) 1 No- quick make and quick break current limiting 4P MCCB 160 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required. b) 4 Nos- quick make and quick break current limiting 4P MCCB 250Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required. e) 5 sets suitable size TP&N Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for outgoing ckts. |
| 501 | Design, Supply of free standing floor mounted dust and vermin proof, compartmentalised cubical panel made out of CRCA sheet, face area 1.80 sq. mtr and 350 mm deep, required hardware, duly painted by 7 tank process powder coating with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate, 100x50x6mm M.S. base channel, hinged door with locking arrangement for equipment/ switchgear/ busbar chamber/ cable alley . Thickness of sheet shall not be less than 2.0mm of any compartment. Load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls compartments having bolted type doors with detachable extension type structure. S/F of following accessories and their inter connections with lugs, terminating all the outgoing and incoming supply terminals in cable alley fixed on SMC/DMC type insulators (as per requirement) with suitable size copper strip with heat shrinkable PVC sleeves/ wire, suitable 25 X 5 size earth copper strip through out run at the bottom of the panel testing etc as required. INCOMER - a) 1No- quick make and quick break 4 Pole current limiting MCCB 400 Amp., 50 KA adjustable O/L & adjustable S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required for incoming supply. BUSBARS.- b) 1Set-TPN copper bus bars of minimum 400 Amp capacity with heat shrinkable coloured sleeves including DMC / SMC bus bar supports at required intervals complete for cross section, size supports and their spacing etc. c) 1Set- 96mm square flush pattern digital type voltmeter (0-500V) with builtin selector switch & 2Amp. back up MCBs. d) 1Set- 96mm square flush pattern digital type Ammeter (0- 200Amp) with builtin selector switch & one set of 3 Nos. CT's of Ratio 600 /5A for each set, class - I accuracy and 15VA burden. e) 3Nos. Phase indication LED lamps with 2Amp back up MCBs. |
| 502 | f) 1set TP&N suitable size Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for incoming ckt. OUTGOING:-a) 2 No- quick make and quick break current limiting 4P MCCB 250 Amp., 36KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required. b) 2 Nos- quick make and quick break current limiting 4P MCCB 160Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required. c) 1 No- quick make and quick break current limiting 4P MCCB 125 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required. e) 5 sets suitable size TP&N Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for outgoing ckts. |
| 503 | Supply of free standing floor mounted dust and vermin proof, compartmentalised cubical panel made out of CRCA sheet, face area not less the .77 sq. mtr and 350 mm deep, required hardware, duly painted by 7 tank process powder coating with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate, 100x50x6mm M.S. base channel, hinged door with locking arrangement for equipment/ switchgear/ busbar chamber/ cable alley . Thickness of sheet shall not be less than 2.0mm of any compartment. Load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls compartments having bolted type doors with detachable extension type structure. S/F of following accessories and their inter connections with lugs, terminating all the outgoing and incoming supply terminals in cable alley fixed on SMC/DMC type insulators (as per requirement) with suitable size copper strip with heat shrinkable PVC sleeves/ wire, suitable 25 X 5 size earth copper strip through out run at the bottom of the panel testing etc as required. INCOMER -a) 2No- quick make and quick break 4 Pole current limiting MCCB 400 Amp., 50 KA adjustable O/L & adjustable S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required for incoming supply. BUSBARS.-b) 3Nos. Phase indication LED lamps with 2Amp back up MCBs. |
| 504 | c) 2set TP&N suitable size Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for incoming ckt. OUTGOING:- a) 2 sets suitable size TP&N Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for outgoing ckts. |
| 505 | Design, Supply of free standing floor mounted dust and vermin proof, compartmentalised cubical panel made out of CRCA sheet, face area not less then 1.96 mtr. and 350 mm deep, required hardware, duly painted by 7 tank process powder coating with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate, 100x50x6mm M.S. base channel, hinged door with locking arrangement for equipment/ switchgear/ busbar chamber/ cable alley . Thickness of sheet shall not be less than 2.0mm of any compartment. Load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls compartments having bolted type doors with detachable extension type structure. S/F of following accessories and their inter connections with lugs, terminating all the outgoing and incoming supply terminals in cable alley fixed on SMC/DMC type insulators (as per requirement) with suitable size copper strip with heat shrinkable PVC sleeves/ wire, suitable 25 X 5 size earth copper strip through out run at the bottom of the panel testing etc as required. INCOMER -a) 1No- quick make and quick break 4 Pole current limiting MCCB 400 Amp., 50 KA adjustable O/L & adjustable S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required for incoming supply. BUSBARS.-b) 1Set-TPN copper bus bars of minimum 400 Amp capacity with heat shrinkable coloured sleeves including DMC / SMC bus bar supports at required intervals complete for cross section, size supports and their spacing etc. c) 1Set- 96mm square flush pattern digital type voltmeter (0-500V) with builtin selector switch & 2Amp. back up MCBs. d) 1Set- 96mm square flush pattern digital type Ammeter (0- 200Amp) with builtin selector switch & one set of 3 Nos. CT's of Ratio 600 /5A for each set, class - I accuracy and 15VA burden. |
| 506 | e) 3Nos. Phase indication LED lamps with 2Amp back up MCBs. f) 1set TP&N suitable size Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for incoming ckt. OUTGOING:- a) 2 Nos- quick make and quick break current limiting 4P MCCB 160Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter hangeability including making connections with lugs, spreaders etc. as required. b) 3 No- quick make and quick break current limiting 4P MCCB 125 Amp., 36 KA adjustable O/L & fixed S/C setting with Rotary handle Operating Mechanism, thermal Magnetic Release and conforming to IS:13947-2/ IEC 60947-2 with front face and centralized adjustable, line load inter changeability including making connections with lugs, spreaders etc. as required. e) 5 sets suitable size TP&N Terminals to receive XLPE aluminium / copper cable of 1.1KV grade for outgoing ckts. |
| 507 | Capacitor Panel (MPP Type) Design, Fabrication, Supplying, Installation Testing and commissioning of Cubical type compartmentalized 430 KVAR Automatic Power Factor Correction Capacitor Panel, 900 mm deep made out of of 2 mm Thick CRCA Sheet Steel, Dust and Vermin Proof, Front Openable having locking arrangement with angle iron frame having 800 Amp 4 Strip aluminium bus bar suitable for use on 415 Volt 50 Hz AC Supply. The APFC Panel shall be comply with IEC 60439-1&2 and IEC 61921, IS-16636-2017. The degree of protection of enclosures system of the APFC Panel shall be min. IP42 in accordance with IEC 60529. The capacitor bank shall be Internet of things (IoT) enabled and communicable/ integrable with BMS with including wiring, The APFC Panel shall be (Indoor) type conforming to IS13341:1992 & IS 13440:1993 floor mounted design i/c Seven tank powder coating paint, Fan filter + Lower cutting 6\\" etc. as required as per specification.NOTE : The Drawing of the panel is to be got approved from the Department before fabrication. part automatically as and when required. Capacity of Static capacitor should be accommodated from the overall rating of the panel and should be designed to switch in independently . a) 1 No. CAPACITOR PANEL, (25x3+50x3+25x3+50x2+10x2 +5x2) with 3 Nos 800/5 Amp sensing CT's of Power Factor correction for each Phase. INCOMINGS (For each set):- 1 No. 800. Amps four pole horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics= Icu) electrically drawout type, fitted with inerlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS:13947-2 1993 as amended with automatic spring charging upto date complete with following accessories for each ACB (but without O/C and E/F protection. Independent manual spring closing mechanism -- 1 No. for each ACB.Breaker 'ON' indicating light with 2A SP MCB , test terminal block set, fuses, circuits as per standard practice, auxiliary contacts as required for positive interlocking of the breakers as required -- 1 Set. |
| 508 | b) 3 nos Cast resin current transformers of 1600/5 ratio, 15 VA Class 1.0 for metering. c) 3 Nos. - Phase indication LED lamps with 2 Amps.back up MCB, breaker ON/OFF indicating light with MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. d) 1 No. digital Ammeter 96 mm x 96 mm scaled 0-400 amps with 3 way and OFF selector switch. e) 1Set- 96mm square flush pattern digital type voltmeter (0-500V) with builtin selector switch & 2Amp. back up MCBs.f) Auto manual Salecter switch. Instruments :- a) Real Time Power Factor Controller with Dual P.F Control , 3 CT Operated. Outgoings:- 1) 3 sets of 25 KVAR 3phase banks. Each bank shall have following components :a) 63 amp TP MCCBs 25 KA, for each b) 1 No. Capacitor Duty Contactor 25 KVAR With Add ON Block c) 1 No. 25 KVAR MPP heavy duty capacitor at 480V 50 Hz. d) Indication Lamp ON/OFF e) ON-OFF Push Button 2) 3 sets of 50 KVAR 3phase banks. Each bank shall have following components : a) 100 amp TP MCCBs 25 KA b) 1 No. Capacitor Duty Contactor 50 KVAR With Add ON Block c) 1 No. 50 KVAR MPP heavy duty capacitor at 480V 50 Hz.d) Indication Lamp ON/OFF e) ON-OFF Push Button 3) 3 sets of 25 KVAR 3phase banks. Each bank shall have following components :a) 63 amp TP MCCBs 18 KA, b) 1 No. Capacitor Duty Contactor 25 KVAR With Add ON Block c) 1 No. 25 KVAR MPP heavy duty capacitor at 480V 50 Hz.d) Indication Lamp ON/OFF e) ON-OFF Push Button |
| 509 | 4) 2 sets of 50 KVAR 3phase banks. Each bank shall have following components :a) 100 amp TP MCCBs 25 KA b) 1 No. Capacitor Duty Contactor 50 KVAR With Add ON Block c) 1 No. 50 KVAR MPP heavy duty capacitor at 480V 50 Hz.d) Indication Lamp ON/OFF e) ON-OFF Push Button 5) 2 sets of 10 KVAR 3phase banks. Each bank shall have following components :a) 32 amp TP MCBs 10 KA, \\"D\\" Curve b) 1 No. Capacitor Duty Contactor 10 KVAR With Add ON Block c) 1 No. 10 KVAR MPP heavy duty capacitor at 480V 50 Hz. d) Indication Lamp ON/OFF. e) ON-OFF Push Button 6) 2 sets of 5 KVAR 3phase banks. Each bank shall have following components : a) 16 amp TP MCBs 10 KA, \\"D\\" Curve b) 1 No. Capacitor Duty Contactor 5 KVAR With Add ON Block c) 1 No. 5 KVAR MPP heavy duty capacitor at 480V 50 Hz. d) Indication Lamp ON/OFF e) ON-OFF Push Button |
| 510 | Design, Supplying, installation, testing and commissioning of 2X 160 kVA(3 Phase Input and 3 Phase Output) online double conversion fully microprocessor based ,indoor type, suitable for parallel operation with battery banks, compact UPS system with IGBT based PWM technology to achieve THD =< 3% and unity power factor having efficiency higher than 95.5% and capable to handle 125-150% load for 60 Sec & 101-125% load for 10 min., built in automatic and maintenance bypass arrangement having noise level less than 62db at i mtr. suitable for Three phase dual AC input voltage 415+/- 20% , 50 Hz +3% / - 3 % and Three phase AC output voltage 415 ± 1% volts & frequency 50 ± 0.5 Hz , inbuilt isolation transformer, back feed protection, necessary SMF batteries of suitable size having 30 minutes combined back up time , |
| 511 | MS mounting rack including and suitable size connecting cable (for UPS to Battery and battery to battery), SNMP card for RS232/ ethernet IP computability for operation and monitoring port open protocol for BMS integration including wiring for BMS etc. with all components as mentioned in BOQ, specifications and schedule, complete etc. as required. Provision for automatic UPS functional testing at 100% load at site without any additional load bank, and if this facility is not in-built in the UPS, then SAT with load bank with necessary cabling is mandatory. UPS vendor to consider load bank charges with mounting racks and cabling charges. Note : Concerning vendor needs to furnish the battery sizing calculations at the time of GA approval and battery size has to be as per the approved GA drawing. |
| 512 | Design, Supplying, installation, testing and commissioning of Indoor floor mounted modular,sectionalised, compartmentalized, extendable type cubicle panel having 25 MVA breaking capacity and having front surface area minimum 5.88 Sq. Mtr. & 1000 mm deep of suitable size fabricated from CRCA steel of 2 mm thick for frame work, enclosure and doors, 3 mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity Copper busbar extensible type, DMC/SMC busbar supports, complete with 1000KVA DG and 1600 KVA Transformer AMFs with battery charger and DG Control Relay with all required safeties, fully capable to sense the main failure and start the DG Set complete with all accessories required like Power supply with backup, charger etc, suitable for 3 phase 415 V 50 HZ AC supply i/c providing and fixing the following switchgear mounted thereon complete with gaskets and interconnections, connections as per specifications complete as required. (The board shall be dust & vermin proof with degree of protection of IP 42 as per IS : 12063, free standing type, mounted on base channel of MS Section not less than 100 mm X 50 mm X 5 mm) MICRO PLC having Poer supply unit, UPS, Battery Charger, DC voltmeter , ammeter, Crenckin reley, breaker control switch, Emergency push button, Hooter, annunciator, Interposing relay, louver with fan, space heater, power socket, door limit swich etc as require ffor panel fully functional.All ACBs Multifunction Meters shall be communication ready with good speed of data transfer (with at least 10mbps speed on Ethernet network for BMS). Panel should have single ethernet port to access all ACB, MCCB and MF Meters.The advanced communication system should be able to show the required data of the trip unit of ACBs with or without using any external software (if external software is required the firm provide it free of cost to the department). |
| 513 | This is required for three purposesa) Communication testing of the circuit breakers at panel builder’s shop floor and generating the communication check reportb) Easy replacement of the Ethernet modules without the involvement of system integrators, in case the modules become faulty.c) One set of communication Cables provided by the Panel Builder at the time of delivery. ACB trip unit shall have a display for measurement of current, voltage and energy. It shall be possible to view last 10 trip cause on trip unit. One 96x96 display unit shall be provided with each ACB which displays the data inside the trip unit on a bigger display. This display unit shall be mounted on the panel door. (I) INCOMINGS (Main Supply-1000 KVA Transformer):- i) 1600 Amp. 50 KA FP EDO (Ics=Icu=Icw for 1sec). ACB Microprocessor based release with over current, earth fault & short circuit protection and Current, Voltage & Energy Parameters measurement on inbuilt display with last 10 Trip History. Release should have inbuilt ZSI feature for Total Discrimination. No derating upto 55 Deg C and Fully rated neutral with inbuilt protection with all accessories like terminal adopters for proper termination, safety shutter & 4 NO+4NC Aux Contacts, 230 V AC Charging motor, 230V shunt release, 230V AC opening & closing coil and frame earthing contact, thermal memory, conforming to IS-13947-2 1993 as amended up-to-date and IEC60947 complete for each of the ACB. - 1 Nos. (a) LED Multifunction Meter(V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Interrupts, RPM, % Unbalance (V,A), Phase angle, THD, Neutral current, % Load, Maximum Demand (kW & kVA), MD reset, Class Accuracy 0.5 complete with accessories = 1 Set. (b) CTs 2500/5A, CL-0.5, 15 VA cast Resin for metering - 3 Set (c) Indication lamp LED type (Red/Yellow/Blue)-220 V AC- 3 Nos. (d) Breaker control switch, 25A (T-N-C).- 1 Set. i) 2A SP MCBs 10kA for control circuits. ii) Following Protection shall be provided : a) Under Voltage with time delay & Over Voltage b) Phase reversal relay.c) Master Trip Relay d) Surge Protection Device |
| 514 | e) Emergency stop push button - 1 nos f) auxilury conractor- 3 nos and add on block 2 NO +2 NC g) Test terminal block and breaker control switch h) Auto mannual salecter switch i) ON /OFF Trip indicating LED j) 63 amp four pole MCB 10 KA and 32 Amp neutral link (II) INCOMINGS (DG Sets-750 KVA) b) For 750 KVA DG Set - 01 Nos. i) 1600 Amp. 50 KA FP EDO (Ics=Icu=Icw for 1sec). ACB Microprocessor based release with over current, earth fault & short circuit protection and Current, Voltage & Energy Parameters measurement on inbuilt display with last 10 Trip History. Release should have inbuilt ZSI feature for Total Discrimination. No derating upto 55 Deg C and Fully rated neutral with inbuilt protection with all accessories like terminal adopters for proper termination, safety shutter & 4 NO+4NC Aux Contacts, 230 V AC Charging motor, 230V shunt release, 230V AC opening & closing coil and frame earthing contact, thermal memory, conforming to IS-13947-2 1993 as amended up-to-date and IEC60947 complete for each of the ACB. - 1 Nos. (a) LED Multifunction Meter(V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Interrupts, RPM, % Unbalance (V,A), Phase angle, THD, Neutral current, % Load, Maximum Demand (kW & kVA), MD reset, Class Accuracy 0.5 complete with accessories = 1 Set. (b) CTs 1600/5A, CL-0.5, 15 VA cast Resin for metering - 3 Set (c) Indication lamp LED type (Red/Yellow/Blue)-220 V AC- 3 Nos (d) Breaker control switch, 25A (T-N-C).- 1 Set. i) 2A SP MCBs 10kA for control circuits. ii) Following Protection shall be provided : a) Under Voltage with time delay & Over Voltage b) Phase reversal relay. c) Master Trip Relay d) Surge Protection Device e) Emergency stop push button - 1 nos f) auxilury conractor- 3 nos and add on block 2 NO +2 NC g) Test terminal block and breaker control switch h) Auto mannual salecter switch i) ON /OFF Trip indicating LED j) 63 amp four pole MCB 10 KA and 32 Amp neutral link |
| 515 | Design, Fabrication, Supply and erection of flange mounted hot dip Galvanized Octagonal Poles of 7 mtrs. height made from 4 mm thick HT Steel plate, having bottom dia of 135 mm. & top dia of 70 mm complete with window type flash cover at a height of 2 mtrs from the of existing cement concrete pedestal as required size 240mm x 240mm x 16mm thick on termination block etc. and galvanized base plate base for cable i/c supplying and fixing of the following in the window box providing for cable termination: -a) Supplying and fixing 6 mm thick laminated mounted sheet inside the window mounted on and i/c providing and welding 3 nos. G.I strips 4mm thick of suitable length and having 10 nos. suitable size tapped holes as reqd. b) Supplying and fixing of 63 Amp termination block suitable pdg. and fixing DIN channel of suitable length - 2 links -5 nos. On DIN channel I/cnos. on the existing laminated sheet.c) Supplying and fixing 6 Amp 10 KA, SPMCB,'C' Characteristics Curve - 1 nos. Earth stud 1Nos. Welded at suitable height two nos. washers,springs & nuts. Cable from window to fitting. d). Supplying and laying of 3 x 1.5 Sq.mm Copper |
| 516 | Providing and laying in position M-15 (1:2:4) reinforced cement concrete foundation of size 600 mm (L) x 600 mm (W) and 1500 mm (D) i/c excavation of earth, Providing cutting, bending and placing in position, reinforcement TMT bars of 12 mm dia 1600 mm long (approx.) -8 nos.and reinforcement ring of cold twisted bar of 8 mm dia-2800 mm (aprox.) - 10 nos. (with 150 mm spacing) as required with positioning of 4 Nos. foundation anchar bolts M 24X 750mm and providing 90 mm (O.D) DWC, HDPE pipe for cable entry and exit as required. |
| 517 | Supply, Erection and Fixing of hot dipped galvanised Overhang canopy with cap (250 x 137.9 x 4.05 mm) over the existing poles etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work |
| 518 | Double arm overhang ( at right angle and 180 degree) |
| 519 | P/ F IP-65/ 66 protected 60 watt LED street light luminaries of following sizes on existing bracket. Fixture made from powder coated single piece pressure die cast aluminum housing with heat dissipation fins on housing with high power LEDs , LED lights and driver should have minimum 2 year warranty. Diffuser / glass cover for ensuring IP-65 protection for lamp and control gear compartment, Integrated driver having efficiency more than 85 % and in compliance to IEC standards etc. as required. |
| 520 | Supply and Drawing of 3 x 1.5Sqmm FRLS PVC insulated flexible copper conductor cable ISI marked (IS: 694) of 1.1kv grade & approved make in existing pole/ bracket, making connections, testing etc as required. |
| 521 | Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required. |
| 522 | 40 mm dia., B Class pipe |
| 523 | Supply, Installtion ,Testing ,Commissioning of 750 kVA rating Sound attenuated DG set (silent type) comprising of engine coupled to 415 V alternator both mounted on comman base MS rail frame,4 stroke cycle, radiator based water cooled, developing maximum BHP at 1500 RPM,under NTP conditions ISO 3046. The engine should be provide with electrical starting arragement and may give the electrical out put 750 kVA at 0.8 power factor,415 volt,frequency 50 Hz at alternator terminal,with all other standard accessories i.e.- (A). ENGINE: Thermostats, radiator cooled,coolant,self contained piping exhuast manifold,flexible SS piping,Silencer-Hospital grade, Air intake dry type paper element filters,Turbocharged, after cooled with restriction indicator,governing system with electronic digital governer, PT fuel pump system,fuel filters,self contained piping,branded injectors,lub oil pump,lub oil cooler,by pass filter(s),oil filter with strainer,self starter,24 volt battery charging alternator with in-built regulator,flywheel also with fly wheel housing,engine protection-trip -safety system with over speed,high water temperature,low lub oil pressure and low level,Fuel tank capacity approximately 990 litres capacitey fabricated with3 mm thik MS sheet compleate with all accessories ,batteries with leads connections etc., complete in all respect. (B) MICROPROCESSOR BASED GENSET CONTROLLER WITH FOLLOWING FEATURES- Digital electronic governing and smart starting,Digital AVR,Engine metering,engine protection,AC alternator metering,AC alternator protection,AC utility protection,AC bus/ utility metering,Gen monitoring of all critical function of engine and alternator,Data logging,true over current protection,Digital frequency,synchronization and voltage matching,Isochronous load share,modulas interface,Fault codes,and description on HMI,configurable inputs and outputs etc. |
| 524 | (C)ALTERNATOR-Output-750 kVA, Power factor-0.8, Rated Generating volts-415Volts, Voltage regulation +/- 0.5% all load between no load to full load & factor 0.8 to unity, Frequency -50 Hz, speed-1500 RPM, Class of insulation -H, Winding connection- Star connection (all six leads should be brought out of stator frame), Overload capacity-10% for one hour in any 12 hours of operation without exceeding temperature rise limits specified in IS/IEC-60034 (I) when corrected to ambient temperature at site, Bearing- long life bearing, Enclosures- Drip proof &screen protected, The alternator may be of self-excited, self regulated automaic voltag regulator and shall conform to IS/IEC-60034 (I) and shall give rated output at NTP conditions. (D) SOUND ATTENUATED SYSTEM - should be thickness of sheet - 16SWG High class sheet metal fabricated enclosure for reducing the noise level [75dB(A) at distane of 1 mtr. ] of DG set & also acts as a weather proof housing conforming statutory Govt. Noise Level. Enclosure construction should be modular with provision to assemble and dismantle easily, drip poof, screen protected IP-23, Battery, fuel tank is housed inside the enclosure. ACOUSTIC MATERIALS- Rock wool/acoustic material 100 mm thick, 96 kg/metric cube density with fiber glass sheet covered with perforated powder coated sheet, confirming to IS-8183/CPCB norms. VENTILATION- Acoustic enclosure should be designed in such a way to easy meet air requirement for combustion and heat removal. (E). EXHAUST SYSTEM: Exhaust manifold with hospital exhaust silencer and catalytic converter and connected with flexible SS expansion bellow/tube. (F) VIBRATION ISOLATION - To avoid transfer of vibration from Genset to enclosure & surrounding specially designed anti vibration pads/isolators should be used. (G) loading, Unloading, Lifting and Shifting of 750 KVA DG Set on the foundation, complete in all respect. |
| 525 | Supply Installation testing and commissioning of 5MP Bullet WDR with 30 Meter IR distance : Image sensor :1/2.8”, 5 MP Low Illumination Progressive Scan CMOS Sensor, Effective Pixels:2560(H)x1920(V), Min. illumination:Color: 0.001Lux @ (F1.2, AGC ON), 0.014 Lux @ (F1.4, AGC ON), 0 Lux with IR, Electronic Shutter:Auto, Slow Shutter, (1/5 sec ~ 1/100,000 sec Adjustable),Fixed Lens 3.6,IRIS Control:Auto,Focus Control:Auto/Manual, Compression:H.265/H.264/MJPEG, Day & Night :ICR switch, Auto, Color, B&W, External trigger,IR Distance:30 Meter,3D DNR, Defog, Slow Shutter, Gain Control, Smart IR, Exposure Mode, White Balance, Mirror, Image Setting, OSD, IR Control, Privacy Masking, 120 db WDR, Quad Stream,Mainstream: 5MP (2560X1920)@25/30fps Sub Stream: 1080P (1920X1080)@25/30fps Third Stream: VGA(640x480)@10fps Fourth Stream: VGA(640x480)@10fps,Protocol:TCP/IP, IPv4, IPv6, SSL, TLS, UDP, HTTP/HTTPS, HTTP-Base64, HTTP-Digest, DHCP, DNS, RTP, RTSPS, ICMP, RTCP, NTP, SMTP, IGMP, Multicast, ONVIF Profile S,G,T,Security Model :Authorized username and password, HTTPS with password, HTTPS digest authentication, Watermark, RTSPS, AES 256 encryption, SHA256 and RSA2048, OTP, Signed Firmware, Firmware Anti-rollback, TEE (Trusted Execution Environment), TRNG, |
| 526 | User Authentication, and encrypted firmware, Hardware Secure Boot,User Authentication, Watermark, IP address filtering,PoE+(802.3at)/DC 12V±10%,Audio :Built-In-Mic or 1 IN/1 Out ,Alarm :1Ch Alarm IN, 1Ch Alarm Out , SD Card:Yes, Up to 256GB Supported, IK10,IP67,Surge Protection :TVS 4000V Lightning Protection, Surge Protection & Voltage Transient Protection,Product Certification:CE,FCC,BIS and CCTV Cameras must comply with the Essential Requirements (ERs) notified as part of the PPO for CCTV in Gazatte of India (EXTRAORDINARY, PART II—Section 3— Sub-section (ii) dated 7th March, 2024, at Sr. No. No. 1062) issued by MeitY |
| 527 | Supply Installation testing and commissioning of 5MP Dome WDR with 30 Meter IR distance : Image sensor :1/2.8”, 5 MP Low Illumination Progressive Scan CMOS Sensor, Effective Pixels:2560(H)x1920(V), Min. illumination:Color: 0.001Lux @ (F1.2, AGC ON), 0.014 Lux @ (F1.4, AGC ON), 0 Lux with IR, Electronic Shutter:Auto, Slow Shutter, (1/5 sec ~ 1/100,000 sec Adjustable),s,IRIS Control:Auto,Focus ControFixed Lens 3.6mm:Auto/Manual, Compression:H.265/H.264/MJPEG, Day & Night :ICR switch, Auto, Color, B&W, External trigger,IR Distance:30 Meter,3D DNR, Defog, Slow Shutter, Gain Control, Smart IR, Exposure Mode, White Balance, Mirror, Image Setting, OSD, IR Control, Privacy Masking, 120 db WDR, Quad Stream,Mainstream: 5MP (2560X1920)@25/30fps Sub Stream: 1080P (1920X1080)@25/30fps Third Stream: VGA(640x480)@10fps Fourth Stream: VGA(640x480)@10fps,Protocol:TCP/IP, IPv4, IPv6, SSL, TLS, UDP, HTTP/HTTPS, HTTP-Base64, HTTP-Digest, DHCP, DNS, RTP, RTSPS, ICMP, RTCP, NTP, SMTP, IGMP, Multicast, ONVIF Profile S,G,T,Security Model :Authorized username and password, HTTPS with password, HTTPS digest authentication, Watermark, RTSPS, AES 256 encryption, SHA256 and RSA2048, OTP, Signed Firmware, Firmware Anti-rollback, TEE (Trusted Execution Environment), |
| 528 | TRNG, User Authentication, and encrypted firmware, Hardware Secure Boot,User Authentication, Watermark, IP address filtering,PoE+(802.3at)/DC 12V±10%,Audio :Built-In-Mic or 1 IN/1 Out ,Alarm :1Ch Alarm IN, 1Ch Alarm Out , SD Card:Yes, Up to 256GB Supported, IK10,IP67,Surge Protection :TVS 4000V Lightning Protection, Surge Protection & Voltage Transient Protection,Product Certification:CE,FCC,BIS and CCTV Cameras must comply with the Essential Requirements (ERs) notified as part of the PPO for CCTV in Gazatte of India (EXTRAORDINARY, PART II—Section 3— Sub-section (ii) dated 7th March, 2024, at Sr. No. No. 1062) issued by MeitY |
| 529 | Supply Installation testing and commissioning of 4MP 36X Optical and 250 Meter IR PTZ ,1/2.8”,Progressive Scan CMOS Sensor,Effective Pixels:1920(H)x1080(V),Min. illumination:Colour: [email protected]; B/W: [email protected], 0 Lux at IR ON,Electronic Shutter:Manual(1/1~1/1,00,000, Auto (normal: 1/1~1/30000 s; illumination mode:1/5~1/30,000s),Lens:4.5~162mm,IRIS Control:Auto/ Manual,Focus Control:Auto/Manual,Compression:H.265/H.264/MJPEG,D&N:Auto/Color/ B/W/Extern,Pan/Tilt range:Pan: 0° ~ 360° endless; Tilt: 185° (-5° ~ 180°),Manual Control Speed:Pan: 0.1° ~350° /s; Tilt: 0.1° ~350° /s,Preset speed:400°/s,Preset accuracy :±0.1°,Preset:256,Cruise :8 groups,Pattern:4 groups,S/N ratio:≥58db (AGC OFF),3D DNR, Defog, Slow Shutter, Gain Control, Smart IR, Exposure Mode, White Balance, Mirror, Image Setting, OSD, IR Control, Privacy Masking,Up to 120 dB, TWDR,Quad Stream:Mainstream: 1080P(1920x1080)@25/30fps,Sub Stream: 720P(1280x720)@25/30fps,Third Stream: VGA(640x480)@15fps,Fourth Stream: VGA(640x480)@15fps,Constant bit rate, variable bit rate (16kbps-8000Kbps),Audio Standard:G.711 U/A or similar,ONVIF2.4.1, Profile S, IPv4/IPv6, TCP/IP, UDP, HTTP, HTTPS, SMTP, FTP, NTP, DNS,DHCP, ARP, UPnP, RTSP, RTP, RTCP, ICMP, IGMP, SSL, QoS, IEEE802.1x, PPPoE, ICMP, SNMP, SNTP, RSTP,ONVIF Profile S, ONVIF Profile G, ONVIF Profile T, PSIA, |
| 530 | CGI,Authorized username and password, HTTPS with password, HTTPS digest authentication, Memory Protection controls , Watermark, RTSPS, AES 256 encryption,SHA256 and RSA2048, OTP, Signed Firmware, Firmware encryption, Firmware Antirollback, TEE (Trusted Execution Environment), TRNG, User Authentication, and encrypted firmware, Hardware Secure Boot, security logs; IP/MAC filtering; generation and importing of X.509 certification; syslog,User Authentication, Watermark, IP address filtering,IP67,IK10,,-50°C ~ 70°C (-40°F ~ +158°F) / 10–95% RH (condensing),,Product Certification:CE,FCC,BIS and CCTV Cameras must comply with the Essential Requirements (ERs) notified as part of the PPO for CCTV in Gazatte of India (EXTRAORDINARY, PART II—Section 3— Sub-section (ii) dated 7th March, 2024, at Sr. No. No. 1062) issued by MeitY |
| 531 | Supply Installation testing and commissioning of 2MP 36X Optical and 250 Meter IR PTZ ,1/2.8”,Progressive Scan CMOS Sensor,Effective Pixels:1920(H)x1080(V),Min. illumination:Colour: [email protected]; B/W: [email protected], 0 Lux at IR ON,Electronic Shutter:Manual(1/1~1/1,00,000, Auto (normal: 1/1~1/30000 s; illumination mode:1/5~1/30,000s),Lens:4.5~162mm,IRIS Control:Auto/ Manual,Focus Control:Auto/Manual,Compression:H.265/H.264/MJPEG,D&N:Auto/Color/ B/W/Extern,Pan/Tilt range:Pan: 0° ~ 360° endless; Tilt: 185° (-5° ~ 180°),Manual Control Speed:Pan: 0.1° ~350° /s; Tilt: 0.1° ~350° /s,Preset speed:400°/s,Preset accuracy :±0.1°,Preset:256,Cruise :8 groups,Pattern:4 groups,S/N ratio:≥58db (AGC OFF),3D DNR, Defog, Slow Shutter, Gain Control, Smart IR, Exposure Mode, White Balance, Mirror, Image Setting, OSD, IR Control, Privacy Masking,Up to 120 dB, TWDR,Quad Stream:Mainstream: 1080P(1920x1080)@25/30fps,Sub Stream: 720P(1280x720)@25/30fps,Third Stream: VGA(640x480)@15fps,Fourth Stream: VGA(640x480)@15fps,Constant bit rate, variable bit rate (16kbps-8000Kbps),Audio Standard:G.711 U/A or similar,ONVIF2.4.1, |
| 532 | Profile S, IPv4/IPv6, TCP/IP, UDP, HTTP, HTTPS, SMTP, FTP, NTP, DNS,DHCP, ARP, UPnP, RTSP, RTP, RTCP, ICMP, IGMP, SSL, QoS, IEEE802.1x, PPPoE, ICMP, SNMP, SNTP, RSTP,ONVIF Profile S, ONVIF Profile G, ONVIF Profile T, PSIA, CGI,Authorized username and password, HTTPS with password, HTTPS digest authentication, Memory Protection controls , Watermark, RTSPS, AES 256 encryption,SHA256 and RSA2048, OTP, Signed Firmware, Firmware encryption, Firmware Antirollback, TEE (Trusted Execution Environment), TRNG, User Authentication, and encrypted firmware, Hardware Secure Boot, security logs; IP/MAC filtering; generation and importing of X.509 certification; syslog,User Authentication, Watermark, IP address filtering,IP67,IK10,,-50°C ~ 70°C (-40°F ~ +158°F) / 10–95% RH (condensing),,Product Certification:CE,FCC,BIS and CCTV Cameras must comply with the Essential Requirements (ERs) notified as part of the PPO for CCTV in Gazatte of India (EXTRAORDINARY, PART II—Section 3— Sub-section (ii) dated 7th March, 2024, at Sr. No. No. 1062) issued by MeitY |
| 533 | Supply Installation testing and commissioning of 32 CH NVR with 4 Sata Supported,Quad-core Embedded processor ,Network Access Bandwidth:512Mbps ,Video Compression :H.265 /H.264 /MJPEG ,Video Output :1 CH VGA output (1920×1080@60Hz 1280×1024@60Hz) 1 CH HDMI output (3840×2160@30Hz, 1920×1080@60Hz, 1280×1024 @60Hz) ,,Video Resolution :4K/5MP/3MP/1080P/960P/720P/D1/VGA/4CIF/DCIF/2CIF/CIF/QC,Preview Capability:1×4K, 4x4K,6(1*4K+5*2MP), 8(1*4K+7*2MP), 9x2MP, 16x1080P, 25x720P, 36xD1 ,Image Display :1/4/6/8/9/16/36 image display ,Intelligent Detection :Support Smart IPC intelligent function: Face detection(Optional), Target Count, Object Count, Object Left/Lost, Electric Fence, Line Crossing, Face Grouping List, Human Detection, Retrograde Detection (wrong Direction), |
| 534 | Leave Position Detection, face recognition black and white list classification,Storage Interface :4 SATA ,HDD Capacity :Single max.10TB ,Backup Location :Local, network, IPSAN, NAS ,Backup Method:USB Device, U Disk, network backup,ANR Supported,Network Protocol :IPv4, IPv6, TCP/IP, HTTP, HTTPS, RTMP, SMTP(SSL), DHCP, PPPoE, UPnP, NTP, P2P, FTP, DNS, DDNS, Alarm Server, IP filter ,Interoperability :ONVIF Profile G, S & T ,Protocol port :ONVIF/RTSP/HTTP/HTTPS/RTMP port customized,Network Interface:2 X RJ45 10M/100M/1000M adaptive Ethernet port ,Alarm Input /Output 1/1,Certification :CE, FCC, EN-60950-1, IEC-60950-1, BIS Certified. |
| 535 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by PVC Jacket. Certified performance in a 4-connector configuration upto 150 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 536 | Supply & Installation of IP-20 & IK-08 , UL Listed Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19\\" angles with wall mounting provision on wall. Accessories like: 1 No of 19\\" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19\\" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required.All as per pre approved by Engineer in charge. 9 U Rack with Width 600 mm & Depth 400 mm + 100 mm |
| 537 | Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent PoE Giga Ethernet Switch providing 24 x 10/100/1000 MBPS PoE Giga Ethernet ports and with min 4 SFP Giga Ports (provision for Fiber Giga connectivity) with provision of minimum Stacking of 06 Switches with minimum 370 Watt PoE Power Budget with related LAN Base Software including making connections etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , |
| 538 | Supply , Installation, Testing and Comissioning of Hot pluggable Small Form Factor Pluggable (SFP Module), 1000BASE-SX, 1.25/2.125G Fiber Channel, LC Type Duplex Connector, 850nm laser transmitter, Should support distance upto 500m on 50/125um of data rate upto 2.125 Gb/s on bi-directional data links. Should also support industrial temperature, should have metal enclosure for lower EMI. The transceiver should be ROHS Compliant. (For Each MM Fiber) all switches & related Fiber modules should be of same make & category for seamless integration with each other of Enterprise class, complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work. |
| 539 | SITC of 55'' 4k Resolution or Better LED TV with remote control and wall mount unit / floor stand complete with making connections etc. as required. |
| 540 | Supplying & Fixing of following sizes of steel conduit along with heavy duty accessories, junction box etc. in surface / recesse including painting in case of surface conduit, or cutting the wall, repair and making good the same as required. |
| 541 | 20 mm |
| 542 | 25 mm |
| 543 | SITC of 10TB Surveillance HDD |
| 544 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump). Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 545 | 450 lpm at 35 m Head |
| 546 | Fabrication, Supplying, installation, testing & commissioning double door type CPRI approved electrical control panel of cubical construction, floor mounted type, fabricated out from CRCA sheet steel of 2 mm thick for frame work, enclosure and doors, 3 mm thick for gland plates with stiffeners wherever required, 200Amp. heat shirinkable Al. alloy Bus Bar with necessary colour coding, front Area not less than 1.00 Sq. mtr. 350 mm Deep having IP-54 degree of protection compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade, cable alley, interconnection, including providing and fixing following switchgears and accessories alongwith internal wiring, earth terminals, labeling etc. complete in all respect, suitable for operation on 415 V, 3 phase, 50 Hz. AC supply for Outdoor application as required. (For 1 Working + 1 Standby Pump). a) 63 Amp. 25 KA 4 Pole MCCB with thermal magnetic release and Extended Rotatory handle - 1 No. (Incomer). b) Digital Multifunction LED meter class 1.0, 96 Sqmm - 1 No. c) Set of 3 Phase LED indicating Lamp - 1 Set d) 2A control SP MCB 10KA - 4 Nos. e) 63A FP AC1 Duty power contractor - 1 No. f) 63 Amp. TPN MCB=2 Nos. g) 32 Amp. DP MCB=2 Nos. |
| 547 | h) FASD starter suitable for upto 10.0 HP pump (rating upto 40 A) complete with Motor protection relay having inbuilt over load, earth fault, locked rotor and single phasing protection feature complete with all accessories and internal wiring with minimum 2.5 Sqmm PVC insulated copper conductor wire required for operation, selector swtich for local/remote, auto/manual/OFF operation Attempt starting device, timers and relays as required, push buttons for start/stop in manual mode, 3 phase LED indication lamps with individual Toggle switch, Pump ON/ OFF LED indication, Control MCB etc. = 2 Nos. |
| 548 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required |
| 549 | 80 mm |
| 550 | 100 mm |
| 551 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 552 | 100 mm dia |
| 553 | 80 mm dia |
| 554 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
| 555 | 100 mm |
| 556 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 557 | 80 mm dia |
| 558 | 100 mm dia |
| 559 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required |
| 560 | 100 mm dia |
| 561 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket |
| 562 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required |
| 563 | 2 way-100 mm dia M.S. Pipe |
| 564 | Supplying and fixing air vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required |
| 565 | Providing outdoor type Weather proof hose cabinet made of 18 gauge thick MS sheet having lockable double doors made out of 18 gauge thick sheet steel along with glazed glass front and downside openable of suitable size but not less than 750 mm x 600 mm x 250 mm suitable to accommodate 2 Nos. 15 mtr. long Hose pipe and 1 No. short branch pipe duly painted with two coats of anticorrosive primer and two coats of approved Post office red synthetic enamel paint complete in all respect as required. |
| 566 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 567 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 568 | Supplying and fixing Single headed external/Internal hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/ Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/ Stainless Steel cap and chain as required : |
| 569 | Single headed Stainless steel |
| 570 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required |
| 571 | Stainless Steel (Grade 304) |
| 572 | Supplying & Laying of one number XLPE insulated and PVC sheathed Armoured Power cable of 1.1 kV grade conforming to IS 7098 (Part 1) 1988 or upto date amendments of following size on cable tray/ wall surface as required. |
| 573 | 4 x 6 sq mm. Copper conductor (clamped with 1mm thick saddle) |
| 574 | Supplying of one number XLPE insulated PVC sheated Al. Conductor armoured Power cable of 1.1 KV grade of following sizes Conforming to IS. 7098/1988 with upto date ammendment etc. as required. |
| 575 | 3.5 x 35 Sqmm |
| 576 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 577 | Upto 35 sq. mm |
| 578 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 579 | Upto 35 sq. mm |
| 580 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on the wall surface as required. |
| 581 | Upto 35 sq. mm |
| 582 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 583 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 584 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 585 | Access Control System (without Finger Print) Supplying, Installation, Testing and Commissioning of cleanroom compatible Access Control System comprising of Face Recognition with including all accessories like cable control cable etc. as require for fulley functional the syestem, Smart Card, QR Code, NFC & PIN Code based Reader, following sizes of 5” IPS TFT Touch Screens, 1GB RAM, 8 GB ROM, AES 128 bit encrypted, Live Face Detection with anti-spoofing against 2D photograph, mobile selfie & video, Fake Fingerprint Detection Technology, 10,000 Face storage (1:N) /, 10,000 card storage (1:N), QR code storage 10,000 (1:N), 2 lakh transaction 20,000 image logs, onboard dual camera (colour & IR) storage, Primary camera min 2MP, Support Face authentication & verification from up to 1 meters, Communication protocols WiFi, TCP/IP, Wiegand Out, USB, MQTT protocol, Blacklist Employee Management, User wise authentication modes; Built in Lock Control, Mask Detection & Alert (configurable), 40 to 30,000 lux illumination, IP54 for Ingress Protection, Certification: CE, FCC, BIS, ROHS, WPC etc. Metal enclosure with battery backup, suitable for mounting on metal surface/metal frames/ wooden frames/wall/flap barriers including all mounting bracket & accessories complete etc. as required. |
| 586 | HVAC WORKS:- 'Water Cooled Chilling Units:- 'Designing, Supplying , Installation, Testing & Commissioning of Water Cooled screw chillers of following capacity each at Design Conditions comprising of semi-hermetic mono/twin rotor screw compressors with automatic capacity control from 100% to 25% complete with insulated shell and tube type flooded cooler, water cooled condenser with all required accessories. The chiller package shall also be complete with copper piping, R‐134a refrigerant gas, Lubricants, system control wiring, Star delta starter, incoming suitable electrical switch gear complete with accessories as required, automatic & safety controls including electronic thermostatic expansion valve. The chiller assembly shall be installed on a fabricated mild steel base frame factory assembled to form a compact assembly. Compressor motor shall be suitable for operation on 415V+/‐ 10%, 50 Hz, 3 phase. The cooler and condenser shall be designed with water connections for ease of piping connectionsThe scope also includes the following: A) Mono/Twin Screw helical rotary low noise compressor semi hermatic complete with automatic step less capacity control 100%-25%, safety switches, forced feed lubrication system etc. B) Unit shall be complete with incoming suitable electrical isolator, star delta stater complete with ammeter with CTs, overload protection, under voltage protection, protection against phase reversal & independent single phase preventors etc as required. C) Refrigerant piping i/c fittings, valves and accessories to inter connect compressor, condenser, chillers and expansion valve, safety valves, etc. Suction line and chiller insulation with minimum 19 mm thick polyvinyl nitrile rubber insulation. complete as required. |
| 587 | D) Microprocessor based control panel with automatic controls and display module compatible to BMS operation and with BACnet/MODBUS/J Bus communication card etc. including sensors, factory manufactured and tested. All Control function including start up and shut down leaving chilled water temperature Control, Compressor and Electronic Expansion Valve modulation, anti re-cycle logic, automatic Compressor and load limiting. it shall also be equipped with the following protection and monitoring devices :- i) High (Condenser) & Low (Evaporator) pressure protection.ii) Low oil level & pressure protection.iii) Chilled/Condenser Water flow loss.iv) Chiller Water Freeze protection.v) Sensor error protection.vi) Motor load control and overload.vii) High motor temperature protection.viii) High oil temperature protection.ix) Chiller inlet and outlet Water temperature.x) Outlet water temperaturexi) Suction and discharge Compressor pressure. E) Water flow switches, water drain and air purge valves etc. complete wherever required. F) Matching shell and tube ASME/GB stamped water cooled condenser of M.S. shell and both side integrally finned copper tubes having max. three passes. G) Matching shell & tube as per ASME/GB/BIS flooded type chiller for screw type units of MS shell and both side integrally finned copper tubes having max. three passes. The chiller shall be duly insulated with 19 mm thick elastomeric nitrile insulation at factory. H) Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with antivibration pads/springs etc. complete as required. I) Initial / first charge of refrigerant gas and compressor oil etc. as required. J) Dial type thermometers and pressure gauges at inlet and outlet of condenser and chiller. K) Anti-vibration mountings as per mfgs recommendations |
| 588 | L) Suitable RCC/Cement concrete foundation for the chilling unit installation complete as required. M) Lot - Flow switches at outlet of condenser & chiller, water drain & air purge valves, cable termination box, wherever required. N) Design parameters are as under:1. Type of Refrigerant : R-134a2. Chilled Water 'In' : 53.6 Deg F (12 DeG C) 3. Chilled Water 'Out' : 44.6 Deg F ( 7 Deg C)4. Chiller Fouling Factor (FPS) : 0.00055. Water Side Pressure Drop in Chiller : max 10m6. Condenser Water 'In' : 90 Deg F (32.2 Deg C)7. Condenser Water 'Out' : 97.5 Deg F (36.4 Deg C)8. Condenser Fouling Factor (FPS) : 0.0029. Water Side Pressure Drop in condenser: Max 5m OEM provided software selection sheet in accordance with ARI 550/590 at above mentioned parameters shall be submitted with the bid. The scope also includes the following: Minimum 100 TR actual capacity as above mentioned Design Conditions. Chilled water circulation rate: 266 US GPM ( @2.66 USGPM/TR)Condenser Water circulation rate: 380 US GPM (@3.8 USGPM/TR)NPLV shall be <= 0.50 IKW/TR Max IKW/TR at design conditions: less than 0.70 |
| 589 | COOLING TOWER :- Designing, Supplying , installation, testing and commissioning of CTI Certified, FRP/ Steel Induced draft, Cross flow, belt/ direct driven or driven through reduction gear box, site erected cooling tower (suitable for above mentioned chillers) of capacity at A) Water Temp. IN :36.4°C B) Water Temp. OUT :32.2°C C) and according to the parameters (Flow) as described below. D) approach less than 2.8°C at Wet bulb 29.4 Deg C. E) Cooling tower shall be complete with PVC Fills, Louvers , Drift Eliminators with flame spread rating of 5 as per ASTM E84, Weather Proof IP 55 TEAO (Totally Enclosed Air Over) Motor, statically and dynamically balanced Propeller Fan, FRP/ Steel Basin in the bottom of the basin, Hot dip galvanised / powder coated Steel Ladder, Perimeter handrail, Steel hardware including nut, bolt, washer etc., suction screen, make-up quick fill arrangement, overflow and drain connections with necessary valves, access arrangement for cooling tower interior / fan, cement concrete foundation, steel/ masonry supporting structure, anti-vibration mountings etc. For longer life of the product Hot dip galvanization / powder coating on the steel frame and ladder other hardware shall be with minimum G-235 / Poweder coated. F) The maximum allowable sound power at a distance of 3 Mt for the one cell cooling Tower shall be less than 65 dB at air inlet . G) Tower fan motor shall be suitable for VFD operation The scope shall include VFD (to be installed in electrical panel) suitable for operation on 415 + 10% volts, 50 Hz. AC supply, Cooling Tower sump temperature sensor, controller to modulate the cooling tower fan speed based on sump temperature. Scope shall include suitable electrical control switchgear, for outdoor application near cooling towers. H) Software generated curves to be submitted by manufacturer. |
| 590 | I) Cooling tower should have access door for maintenance on one side of CT atleast of 2 x 0.450m size and a catwalk within CT to attend fins and fan. J) Water Flow 380 USGPM (Cooling tower capacity should not less than 125TR) |
| 591 | Designing, Supplying , erection, testing and commissioning of end suction/Vertical split casing / Vertical Inline Split Coupled (Long coupled) centrifugal Condenser water pump set capable of delivering following capacity of water, each comprising of the following and complete with TEFC squirrel cage induction motor, efficiency IE3 with class 'F\\" insulation. 1450 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply, BMS compatible. pump shall have CI body, SS/Bronze impeller, spacer coupling and coupling guard, The mechanical seal shall be outside type, The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Vendor shall provide antivibration arrangement for pumps as per Manufacturers recommendation . Minimum efficiency of pump shall be 70%. The scope also shall include following. A) 19mm thick polyvinyl nitrile rubber insulation duly cladded between aluminium sheets of 0.5mm thickness and properly clamped to pump. B) 2 Nos. - 150 mm dia dial type pressure gauges C) Mounting frame with antivibration pads ( In case pumps are inline, anti vibration system shall be as per Manufacturers recommendation) D) RCC/cement concrete foundation for the pump unit. ( In case pumps are inline, foundation shall be as per Manufacturers recommendation) |
| 592 | Pump capacity are as under: E) For 100 TR capacity unit not less than 380 USGPM of water at 30 mtr head each |
| 593 | Designing, Supplying ,erection, testing and commissioning of end suction / Vertical Inline Split Coupled (Long coupled) centrifugal chilled water pump set capable of delivering following capacity of water, each comprising of the following and complete with TEFC squirrel cage induction motor, efficiency IE3 with class 'F\\" insulation. 1450 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply, BMS compatible (for remote operation). pump shall have CI body, SS/Bronze impeller, spacer coupling and coupling guard, The mechanical seal shall be outside type, The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Vendor shall be provide antivibration arrangement for pumps . Pumps shall have minimum efficiency of pump shall be 70%. The scope also shall include following. A) 19mm thick polyvinyl nitrile rubber insulation duly cladded between aluminium sheets of 0.5mm thickness and properly clamped to pump. B) 2 Nos. - 150 mm dia dial type pressure gauges C) Mounting frame with antivibration pads ( In case pumps are inline, anti vibration system shall be as per Manufacturers recommendation) |
| 594 | D) RCC/cement concrete foundation for the pump unit. ( In case pumps are inline, foundation shall be as per Manufacturers recommendation) E) Pump capacity are as under: F) For 100 TR capacity unit not less than 266 USGPM of water at 35 mtr head each |
| 595 | Air Handling units (AHUs),TFA and DHU :- Designing, Supplying , installing, testing and commissioning of factory built, site assembled double skin Air Handling units as described below. A) Standard 43mm thick panels consisting of pre plasticized painted sheet casing of thickness 0.8mm outside layer and 0.8 mm inside layer with zinc coating and polyurethane foam (PUF) insulation having density of 40kg/cum factory injected between them by injection moulding machine, view windows, marine Lamp, limit switch, electrically interlocked fan section with hinged access door, fire retardant flexible joints for outlets of the units. Drain connection with stainless steel drain pan duly insulated and necessary vibration isolation arrangement to avoid any vibration etc. B)The extruded aluminium framework shall be with thermal break profiles as required, minimum 2 bend GSS/PVC eliminators. AHUs shall have below sections:- Mixing section with dampers - Filter section with Pre filter (EU4) and fine filters (EU7)- Cooling coil section, 2 bend eliminator, UVGI- Heating section - Supply air section with port for Pan humidifier, bleed off damper, supply air damper. C) Supply air fan plug type direct driven with VFD & forward curve/plug type Exhaust fan(2 fans / single fan with below mentioned capacity) with VFD, TEFC motors (IE3 efficiency) suitable for 415 + 10% volts, 50 Hz, 3 phase AC supply. Fans should be AMCA certified for Air & sound performance. D) Chilled water cooling coil with aluminium finned copper tubes (tube thickness not less than 0.5mm), The face velocity across cooling coil shall be limited to 450FPM maxm, The scope shall include 3 way valve, bypass butterfly valve, actuator and temperature sensors. E) Supply air stream will have Filter section having EU4 filter and EU7 filters. F) Mixing Box with three zero leakage dampers, one damper shall be for fresh air, and return air. Coil section shall have bypass damper, as per design requirement. The scope shall include motorized actuators complete with wiring , enthalpy sensors for return air and ambient air, thermostat/ Controller to set & modulate damper position for free cooling. |
| 596 | G) SS Tubular heater section in supply air of capacities as mentioned below ( equally distributed over the 3 phases. The scope shall include1. Heating thermostat (TH) for temperature control 2. Air flow switch for switching off heaters in case of no air flow, 3. Humidistats (HU) for humidity control, 4. Geyser stat in pan humidifier,5. Thyristor based controller to switch ON heaters in steps.complete with interwiring including cable, switch gear & connection thimbles, clamps, earthing, etc , terminal electrical distribution board, glass insulated flexible wires for connection of heaters, fire rated fillings at duct crossing etc. as required. H) UVGI lamps - UVC emitter in coil section of AHU. The scope shall include electrical wiring and electrical isolator for following capacities. The purpose of these UVC emitters is to improve indoor air quality (IAQ) by eliminating mould, bacteria and other contaminants in down stream section. I) Scope shall also include Supply, installation, testing and commissioning suitable for outdoor application of 3KW pan type humidifiers consist of main body out of 2mm thick stainless steel sheet SS-304 having connections of quick fill, make up, over flow and drain. The top cover is open able for access to the inside of Humidifier for servicing. The body of Humidifier is leak proof. Finally Humidifier is insulated with 50mm thick fibreglass 32 kg/m3 and then cladded with 0.5 mm thick Aluminium sheet. J) The scope shall include K) DPR operated variable speed arrangement (V.F.D) in weather proof enclosure complete with incoming electrical isolator for supply & exhaust air fan's to allow for constant air volume delivery at all filter pressure drop conditions. The scope shall include pressure drop sensors with alarm system. L) Set of Butterfly valve for cooling coil isolation |
| 597 | M)Y strainer's in water supply to cooling coil N) Automatic pressure independent balancing cum control valve (In addition to 3 way valve as mentioned in item description d) for cooling coil.Pressure independent Balancing and modulating Control valves should be single Unit of PN16 Rating. The valve should be Globe Type in construction. It should be diaphragm type & pressure balancing should be done with Rolling Diaphragm based Delta Pcontroller only, Minimum Pressure Drop across the valve must not exceed 35kPa for any size. Valve shall be complete with duly mounted with Modulating actuator IP42/54, suitable for 24V AC. Actuator should be Gear type only (not thermal/wax) & should have the self-calibrating feature.Valve & Actuator combination should be able to give logarithmic control characteristics to achieve linear control. The valve shall have manual override facility & the scope shall include proportionate thermostat and wiring for interconnection with 1.5 sq.mm copper conductor multicore armoured cable complete as required. O) AHU's shall be mounted on P.C.C. blocks with ceretted rubber pads P) Set of each Temperature & water pressure guage (100 mm Ø) bourdon type with brass ball valve of 3/8\\" Ø and SS tubing, socket. Range (0-50) for coils Q) Air vent on header of coils in AHU. R) The scope includes incomer electrical isolator and further distribution including cable, VFDs, starters, etc as required and as described above S) AHU mounted Contactor complete with suitable incoming electrical isolator for heaters & humidifier in weather proof enclosure mounted over AHU body T) The capacity of Air-handlers shall be as follows: |
| 598 | AHU -1(EBL) without HEPA filters 50,000 CFM @150 WC SP USING TWO FANS HEPA terminal filters so HEPA is not part of AHU |
| 599 | AHU- 2A (Equipment area ) without HEPA filters 50,000CFM @150 WC SP USING TWO FANS HEPA terminal filters so HEPA is not part of AHU |
| 600 | AHU- 2B ( Equipment area) without HEPA filters 50,000CFM @150 WC SP USING TWO FANS HEPA terminal filters so HEPA is not part of AHU |
| 601 | AHU-3 (Chemistry lab ) without HEPA filters 12,000 CFM @150 WC SP (SINGLE FAN FOR THIS AHU) HEPA terminal filters so HEPA is not part of AHU |
| 602 | AHU- 4 (Testing Lab ) without HEPA filters 12,000 CFM @150 WC SP (SINGLE FAN FOR THIS AHU) HEPA terminal filters so HEPA is not part of AHU |
| 603 | AHU- 5 (Dicing lab ) without HEPA filters 12,000 CFM @150 WC SP (SINGLE FAN FOR THIS AHU) HEPA terminal filters so HEPA is not part of AHU |
| 604 | AHU- 6 ( Corridor+ Change room) without HEPA filters 40,000 CFM @150 WC SP USING TWO FANS HEPA terminal filters so HEPA is not part of AHU |
| 605 | Designing, Supplying , installing, testing and commissioning of factory built, site assembled double skin Treated Fresh Air (TFA) units as described below. A) Standard 43mm thick panels consisting of pre plasticized painted sheet casing of thickness 0.8mm outside layer and 0.8 mm inside layer with zinc coating and polyurethane foam (PUF) insulation having density of 40kg/cum factory injected between them by injection moulding machine, view windows, marine Lamp, limit switch, electrically interlocked fan section with hinged access door, fire retardant flexible joints for outlets of the units. TFA shall be complete with fresh air and supply air dampers.Drain connection with stainless steel drain pan duly insulated and necessary vibration isolation arrangement to avoid any vibration etc. B) The extruded aluminium framework shall be with thermal break profiles as required, minimum 2 bend GSS/PVC eliminators. C) Supply air fan plug type direct driven with VFD & forward curve/plug type with VFD, TEFC motors (IE3 efficiency) suitable for 415 + 10% volts, 50 Hz, 3 phase AC supply. Fans should be AMCA certified for Air & sound performance. D) Chilled water cooling coil with aluminium finned copper tubes (tube thickness not less than 0.5mm), The face velocity across cooling coil shall be limited to 450FPM maxm, The scope shall include 3 way valve, bypass butterfly valve, actuator and temperature sensors. E) Supply air stream will have Filter section having EU4 filter and EU7 filters and HEPA Filter EU 13. F) SS Tubular heater section in supply air of capacities as mentioned below ( equally distributed over the 3 phases. The scope shall include 1. Heating thermostat (TH) for temperature control 2. Air flow switch for switching off heaters in case of no air flow, 3. Humidistats (HU) for humidity control, 4. Geyser stat in pan humidifier,5. Thyristor based controller to switch ON heaters in steps.complete with interwiring including cable, switch gear & connection thimbles, clamps, earthing, etc , terminal electrical distribution board, glass insulated flexible wires for connection of heaters, fire rated fillings at duct crossing etc. as required. |
| 606 | G)UVGI lamps - UVC emitter in coil section of AHU. The scope shall include electrical wiring and electrical isolator for following capacities. The purpose of these UVC emitters is to improve indoor air quality (IAQ) by eliminating mould, bacteria and other contaminants in down stream section. H)Scope shall also include Supply, installation, testing and commissioning suitable for outdoor application of 3KW pan type humidifiers consist of main body out of 2mm thick stainless steel sheet SS-304 having connections of quick fill, make up, over flow and drain. The top cover is open able for access to the inside of Humidifier for servicing. The body of Humidifier is leak proof. Finally Humidifier is insulated with 50mm thick fibreglass 32 kg/m3 and then cladded with 0.5 mm thick Aluminium sheet. I) The scope shall include J) DPR operated variable speed arrangement (V.F.D) in weather proof enclosure complete with incoming electrical isolator for supply & exhaust air fan's to allow for constant air volume delivery at all filter pressure drop conditions. The scope shall include pressure drop sensors with alarm system. K) Set of Butterfly valve for cooling coil isolation. L) Y strainer's in water supply to cooling coil M) The scope shall include low leakage dampers, motorized actuators complete with wiring , enthalpy sensors for return air and ambient air, thermostat/ Controller to set & modulate damper position for free cooling. N) Automatic pressure independent balancing cum control valve (In addition to 3 way valve as mentioned in item description N) for cooling coil.Pressure independent Balancing and modulating Control valves should be single Unit of PN16 Rating. The valve should be Globe Type in construction. It should be diaphragm type & pressure balancing should be done with Rolling Diaphragm based Delta Pcontroller only, Minimum Pressure Drop across the valve must not exceed 35kPa for any size. Valve shall be complete with duly mounted with Modulating actuator IP42/54, suitable for 24V AC. Actuator should be Gear type only (not thermal/wax) & should have the self-calibrating feature. Valve & Actuator combination should be able to give logarithmic control characteristics to achieve linear control. The valve shall have manual override facility & the scope shall include proportionate thermostat and wiring for interconnection with 1.5 sq.mm copper conductor multicore armoured cable complete as required. |
| 607 | O) Air intake louvers at intake & exhaust louvers complete with washable 10μ filters, GI bird screen, etc as required. P) TFA shall be mounted on P.C.C. blocks with neoprene pads in between & if TFA is in out door inclined FRP sheet shall cover TFA ( So that rain water does hot get stagnet over TFA. Q) Set of each Temperature & water pressure guage (100 mm Ø) bourdon type with brass ball valve of 3/8\\" Ø and SS tubing, socket. Range (0-50) for coils. R) Aut air vent on header of coils in TFA. S) The scope includes incomer electrical isolator and further distribution including cable, VFDs, staters, etc as required and as described above. TFA -AHU-9000 CFM @150 WC SP |
| 608 | Designing, Supplying ,installing, testing and commissioning of factory built, site assembled double skin De-Humdifier unit with pre-cooling and heating described as below- A) The dehumidifier shall consist of a high efficiency desiccant rotor/ bed mounted on a horizontal fixed shaft arrangement. It shall have P-Seal across the rotor for process and reactivation air streams to allow for independent airflow with no balancing required. D type seal shall not be accepted as it leaves a room for cross departmental leakage. The dehumidifier shall be fully automatic, factory assembled package unit, complete with reactivation heaters, Pre-cooling fitted with a cooling coil having within itself another precooling heat exchange media made of polymer to avoid scaling and corrosion to save energy by reducing pre-cooling tonnage, post cooling coil, filters, motors, fans, desiccant bed drive assembly, access panels, volume dampers, weatherproof or dust-tight automatic electrical panel, desiccant rotor/bed, and all component auxiliaries as recommended by the manufacturer for safe, unattended, automatic operation.The dehumidifier shall not require field piping, desiccant charging, pneumatics, or field erection of fans unless specifically requested by the engineer. B) Within the industrial quality welded SS framework, shall be provided double skin insulated panels. The external panel has to be pre plasticized GI only and same shall be of at least 0.63mm thick. The inside skin/ panel shall be either MS duly coated for corrosion resistant paint, stainless steel or GI and shall be at least 0.63mm thick. The insulation, between the panels, shall be glass fiber, or Rockwool, with a minimum density of 48kg/cu.mt. C) DESICCANT ROTOR The desiccant honeycomb rotor media shall be adsorbent, non-toxic, non-flammable, fully water washable. The substrate of the rotor shall not be made from asbestos or any synthetic material, and shall not have any toxic desiccants impregnated like lithium chloride, etc. The desiccant media shall have in-situ synthesized metal silicate desiccant on an inert inorganic fiber substrate.The active desiccant material shall be at least 80% of the media weight, so as to ensure high performance and minimal heat carry over. The net organics in the honeycomb media shall not exceed 2%. The desiccant rotor shall have integral long life bearings supported by a simple fixed shaft design to allow a simple slide out of the rotor/bed. The desiccant media shall be non-flanged which should encircle the entire perimeter so as to allow greater durability. The desiccant media shall not fracture due to repeated temperature and moisture cycling and all the materials of construction shall be non-toxic. The surface of the media shall have a special edge hardening so as to ensure a smooth surface and long life of both the media and the seal contacting it. The desiccant media shall not use any organic burn off process, as this shall weaken the media structure. |
| 609 | D) PRE-COOLING TO DEHUMIDIFIER – For any fresh air requirement, precooling is required to offset the moisture load to the dehumidification system. The Pre-cooling has to have the following components:Double Skin construction made up of 48mm ±2mm thick panels consisting of pre plasticized GI casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine. Precooling Unit should compulsory be fitted with a heat exchanger modules of 400mm thickness to effect sensible cooling by 55% in dry regions.Mixing Box – for mixing Fresh and Return Air, 2 bend GSS/PVC eliminators, Cooling coil section (CHW) with Aluminium finned copper tubes ( tube thickness not less than 0.5 mm ) cooling coil of minimum 8 row deep designed at 500FPM, Filter section with 50 mm thick metal viscous filter /washable synthetic type air prefilters. E)POST COOLING UNIT – The Post cooling machine is to offset the high temperature generated by the dehumidifier after the rotor. It should have the following components – Double Skin construction made up of 48mm ±2mm thick PUF Panels having inner sheet of plain GI 0.6mm thick and outer sheet has to be pre-plasticized of 0.6mm thick. Process Fan should be Plug Fan Type Only for higher efficiency and for low sound level. F) Filters Section – All filters should be designed at minimum 500FPM for better efficiency and should be installed in flanged type tight construction and has to be installed in series as below only. G) Stage –I: This filter is to be installed on the suction side of the fan. Pre filter (EU-4); 90% down to 10 µ) shall be flange type non-woven synthetic washable media, initial pressure drop not exceeding 4 mm WG. H) Stage –II: This filter is to be installed after the stage-I filter. This second stage filter shall be flange type Fine Filter. I) Stage-III (requirement for cleanroom): This filter is to be installed on the discharge side as final stage filter. It is HEPA (EU-9; 99% down to 0.3µ). It has to be of minimum 300mm depth for better efficiency and has to be installed in flange type construction. J) Cooling coil section (DX/CHW) with Aluminium finned copper tubes cooling coil of minimum 6 rows deep designed at 500FPM. Mixing Box – For mixing Dehumidified and Return Air. Tank underneath cooling coil made up of SS-304 material. |
| 610 | K) VOLUME DAMPERS- All volume dampers on the dehumidifier shall be of multiblade, opposed blade type with locking quadrants. Dampers shall be factory installed at the outlets of both process and reactivation air fans. The damper shaft exposed at the quadrant shall be notched to indicate the position of damper blades. L) PACKAGEABILITY- The dehumidifier unit shall be modular in design so as to be able to connect with factory standardized pre cool and post cool modular boxes and to connect accessories such as face and bypass dampers. The metal work contacting the process air stream shall be duly insulated and the insulation sandwiched as in the panel work for the dehumidifier. M) ELECTRICALS & SAFETY DEVICES- The control panel shall be factory prewired for the system operation and shall be supplied with branded make fuse/MCB’s contactors, starters, control transformer, overload protection, and all the necessary components to ensure a continuous automatic operation. The PLC/HMI/DDC controller shall be of a reputed make .Multiple Safety checkpoints with inbuilt thermostat shall be provided for automatic shutdown. De-Humdifier unit (Suitable for 9000 CFM TFA unit) |
| 611 | Designing, Supplying ,installation,testing,commissioning of following modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled outdoor units suitable for cooling and heating ,having all hermetically sealed inverter type rotary/scroll compressor(s),minimum two compressor above 14 HP modules, microprocessor based controller,top discharge type condensing unit(s), with R-410A refrigerant or equivalent, Vibration isolators,with suitable masonary foundation work and suitable sizes de-rusted,cleaned,primed and duly painted MS stand etc. complete as required.The unit shall deliver the rated capacity at AHRI conditions and work even at 50 degree celcius ambient temperature without tripping.The unit shall be suitable to work on 400V +/-10%,3 Phase,50 Hz AC power supply and BMS Compatible.The unit shall be filled with first charge of refrigerant and ready for use as required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. |
| 612 | Outdoor unit 14 HP |
| 613 | Supply,installation,testing,commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre filter,fan section with low noise fan/dynammically balanced blower,multispeed motor,coil section with DX copper coil,electronic expansion valve,outer cabinet,cord less remote control,drain pan, neceessary accessaries etc., suitable for operation on 230V +/- 10%, 50Hz,single phase AC supply,complete as required.The unit shall have force shut down provision in case of fire on receiving signal from BMS system.The cooling capacity of indoor unit will be at air inlet conditions of 27 degree C DB and 19 degree C WB temperature. (Make will be same as of outdoor unit) |
| 614 | High Wall type Indoor unit 2.0 TR |
| 615 | Supply, Installtion,Testing, Commissioning including vaccumiazation and nitrogen testing of nominal sizes of soft/hard drawn copper refrigerant piping(Thickness greater than or equal 0.8 mm) for VRV/VRF system,complete with fittings,refnets/Y-joints/ branch headers/connection piping kits with suitable ring type hanger supports,jointing/brazing including accessories,insulated with XLPE class-O tubler section/with class-O closed cell elastomeric nitrile rubber tubular sleeves sections of 12/19mm thickness for suction and liquid lines,all accessories as per specification etc. as required.The bidder need to considered / quoted the copper pipe as suction and discharge as one circuit (Both length are consider in one running meter). |
| 616 | Supply and fixing of follwoing sizes piping drain on wall complete with fittings and clamps/supports etc. The joints shall be properly sealed with rubber based adhesive to ensure proper bonding. The rate shall include PVC Coupler, reducer, socket, bend, Tee as required as per the site to connect with the Drain Hopper of IDUs. |
| 617 | 25 mm dia. rigid PVC pipe. |
| 618 | Supplying Installation Testing Commissioning of Central Control Server System comprising of Intel® Xeon® CPU E5-2640 x64 (or better) compatible with dual and quad core processors, Windows 11 (Professional, Enterprise, Ultimate, 64 bit), Windows Server 2013 R2 (Standard, Enterprise, 64 bit) 16 GB or more, Video card and monitor capable of displaying at 1024 x 768 resolution or better, Latest Microsoft Licence Version Operating System Loaded with MS OFFICE 2019 Professional, Word, EXCEL, Power Point, Outlook Express, Microsoft Team official version lifetime licences suitable for running BMS software complete etc. as required. |
| 619 | Supplying Installation Testing Commissioning of Client PC System comprising of PC Hardware with minimum11th Gen Intel® I7 processor CPU E5-2640 x 64 (or better), compatible with dual and quad core processors minimum 3.1 Ghz and 8GB or higher RAM, Hard Drive Space of 256 GB SSD or better, Video card and monitor capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector) with 2 GB or higher Graphics card suitable for BMS System complete etc. as required. |
| 620 | Supplying Installation Testing Commissioning of LaserJet printer having printing resolution 1200 x 1200 dpi,(dot/inch) or better, 21 to 30 ppm printing speed (LaserJet) complete etc. as required |
| 621 | Supplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required. |
| 622 | 32 inch or larger |
| 623 | Software for Building Management System : A) Supplying Installation Testing Commissioning of Necessary Software (UL listed) Packages containing Building Management with Capability of Collection, Storage, Processing and Controlling all the Data. Software shall support Open Standard Protocols like XML, BACnet, Modbus, Lon works etc. and without the use of Proprietary Protocols, with Enterprise Level Database Like MS SQL complete Lifetime Licenced & capable to collect, store & access all points from Fire Alarm Systems, IT Systems, Automation Systems, HVAC System, Lift, Energy management, Water Management System, etc. to create & monitor historical & event data, event management data, alarm management data & reporting data, Email Alerts for Critical alarms for all the systems. The scope includes additional software required by BMS software (to enable a standard Web browser) to be resident on the DDC/client machine (manufacture-specific browsers shall not be acceptable). User log-on identification and password shall be required & a minimum three-layered security system(User interface Level, Application Level and Data Base Level) to be deployed for safety. The supplied computer software shall employ objectoriented technology (OOT) for representation of all data and control devices within the system. |
| 624 | B) This data shall reside on a server for all database access (Systems requiring proprietary database and user interface programs shall not be acceptable). All components and controllers supplied under this contract shall be true “peer-to-peer” communicating devices (Components or controllers requiring “polling” by a Master / Global / Host to pass data shall NOT be acceptable). Physical connection of BACnet/MODBUS devices shall be via Ethernet at all levels. The License must be provided by default. The BMS software shall be complete in all respect to cater the following different numbers of points managed in the installation. C) For up to 2500 point included |
| 625 | Supplying Installation Testing Commissioning of following sizes Touchscreen Color portable operator terminal capable of connecting to one of the controllers on the communication bus and view parameters of the complete system. The terminal should be capable of viewing /changing parameters and trends,the specified parameters as per requirement etc. as required. |
| 626 | 7 inch Touch screen |
| 627 | A) Supplying Installation Testing Commissioning of IP Based DDC controller with suitable enclosure capable of fully “stand- alone” operation i.e. In the event of loss of communication with other DDC’s or Control Station, they shall be able to function on their own. The controllers shall consist ofdual/quad core 32 bit microprocessors with EPROM based operating system on BACNET. The network Topology shall not allow single point failure. Each DDC on field level shall have embedded TCP/IP (10/100Mbps) connectivity so that it can be hooked into the Local Area Network (LAN) provided by the client or on dedicated network . Each DDC can be accessed from the Graphical User Interface (GUI) or from a standard Web browser (WBI) by connecting the server alongwith inbuilt web browser. |
| 628 | B) All controllers shall accept 230V+/- 10%, 50Hz Uninterrupted power supply provided by end user. Controller shall support DHCP addressing over Local Area Network (LAN) so that the static IP requirements get reduced however a single static IP shall be provided for system so that it can be hosted on to internet in consultation with end user. The microprocessor based DDC’s shall be provided with power supply, analoge to Digital and Digital to analoge converters with memory and capacity to accommodate input/output (I/O) hardware points (with or without an expansion board). Each DDC should have own board and shall accept 0-10 V /4-20mA input signal having Minimum 20% spare capacity considered for expansion. Each DDC on field level should have minimum 128MB RAM & 64MB Flash memory. Following type of All controllers should be mandatorily BTL approved with B-BC profile complete etc. as required. C) DDC Controller-(Support up to 64 points) |
| 629 | Supplying Installation Testing Commissioning of following type of input output (IO) expansion module complete etc. as required. |
| 630 | I/O Module with 16 DI channels |
| 631 | Supplying Installation Testing Commissioning following type 3rd party Integration unit to provide the interface between Ethernet LAN and the 3rd party field control devices or any other devices which need to be integrated. These shall also provide supervisory capability of functions over the devices connected to it. The purpose of using theseunits should be limited to integrate the devices only. The Unit must have two onboard Ethernet port, minimum 2/3 on board RS485 ports. The Integration unit should have inbuilt 4GB memory for program storage. The Unit must communicate over TCP/IP with communication speed of 10/100MBPS. The Integration unit should be capable of handling multiple protocol simultaneously such as Bacnet, Modbus, SNMP restricted to single protocol. All integrators should be mandatorily BTL listed. The integration unit shall be housed in suitable size sheet steel enclosure made of 1.6mm thick CRCA sheet, lockable front door with glass, arrangement for cable entry and duly powder coated complete etc as required. |
| 632 | Integrator for 1250 Points |
| 633 | Field devices: Supplying Installation Testing Commissioning of following Field Devices including connection etc. as required |
| 634 | Modulating type motorized actuator with operating voltage of 24 Volt AC/DC and modulating voltage of 0-10 V DC supply. |
| 635 | ON/OFF type actuator with operating voltage of 24 Volt AC/DC and modulating voltage of 0-10 V DC supply for motorised fire dampers. |
| 636 | Differential Pressure Switch ( DP Switch for AHU Blower and HEPA Filter Pressure status ) |
| 637 | Outside Temp & Humidity Sensor with radiation shield. Measuring Range: Temp:- -15 to 50 0C & RH 0-100%, Accuracy: +/- 1 0C +/- 3% |
| 638 | Duct mounted temperature & humidity sensor |
| 639 | Duct mounted Air DP switch for fan run status |
| 640 | Duct CO2 Sensor, 0-2000ppm, 0-10V/4-20mA Output. |
| 641 | Immersion Temp Sensor for CHW line. Measuring range: -30 to 110 0C, Accuracy: +/- 1.3 0C |
| 642 | Water Pressure Sensor |
| 643 | Water flow switch for chilled water. |
| 644 | Water differential Pressure Switch ( DP Switch for pumps status ) |
| 645 | High/Low Level Switch for Tank Level Monitoring |
| 646 | Supply and laying of following size overall shielded Control cum Communication cables in suitable PVC conduits. |
| 647 | 4C x 1.5 Sq.mm shielded copper cable |
| 648 | 2C x 1.5 Sq.mm shielded copper cable |
| 649 | 2C x 1.0 Sq.mm shielded copper cable(VRV/VRF) |
| 650 | Designing,Supplying, fixing, testing and commissioning of condenser water pipes of following nominal bore size diameters, MS C Class, and materials along with necessary supports/clamps, vibration isolators, and fitting such as bends, tees etc. but excluding valves, strainer and gauges etc adequately supported on rigid supports etc as per specification and as required. Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. The welded pipe shall be pained with 2 coats of green coloured enamel paint. |
| 651 | 150 mm Dia |
| 652 | 100 mm Dia |
| 653 | 50 mm Dia |
| 654 | Above described pipes to be laid in trench (Burried) instead of clamps, supporting frame, etc. The scope shall include excavation, re-filling of trench after completion of pipe laying, sand bed shall be prepared by laying at 50mm thick sand layer in trench, Standard brick shall be placed over sand bed, then the pipes shall be laid over brick, The top of pipe shall be atleast 800mm below ground. |
| 655 | 125mm Dia |
| 656 | Designing,Supplying , fixing , testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Supplying, fixing, testing and commissioning of following diameter valves(Complete with Flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), strainers(Complete with flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), gauges etc for condenser water circulation as per specifications.Butterfly Valve with CI body SS disc nitrile sheet & O ring, Complete with fittings, Nuts, Bolts & Gaskets. |
| 657 | 125 mm Ø Butterfly Valve |
| 658 | 100mm Ø Butterfly Valve |
| 659 | 50mm Ø Butterfly Valve |
| 660 | Designing,Supplying, fixing, testing and commissioning of following sizes Motorised butterfly valves with CI body,SS disc, O-ring and minimum PN-16 pressure rating,conforming to BS 5155,IS 13095 with IP-55 actuator,capable of accepting up to 10V DC,and up to 2mA electric signal and providing similar trasduced feedback output to control system as required.Motorised Butterfly Valve with manual override control/wheel(Complete with fittings, Nuts, Bolts & Gaskets , wafer type construction .The actuator shall be IP 67 rated and BMS compatible. |
| 661 | 125mm |
| 662 | 100mm |
| 663 | Designing,Supplying, fixing, testing and commissioning of following diameter valves(Complete with Flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), strainers(Complete with flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), gauges etc for condenser water circulation as per specifications. |
| 664 | Fully automatic balancing valve - 125mm Ø |
| 665 | Fully automatic balancing valve - 100 mm Ø |
| 666 | Designing,Supplying, fixing, testing and commissioning of water pressure gauge (100 mm Ø) bourdon type with brass ball valve of 3/8\\" Ø and SS tubing, socket. Range (0-50) / (0-100) as required |
| 667 | Designing,Supplying, fixing, testing and commissioning of Mercury in glass industrial thermometer in SS-304 casing with 0.5 C least count, range 0-50 C. Brass oil filled thermowell of 1/2\\" size |
| 668 | Designing,Supplying, fixing, testing and commissioning of PN-16 Pot strainer as per Specification. - 125 mm Ø (pipe size) |
| 669 | Designing,Supplying, fixing, testing and commissioning of PN-16 Pot strainer as per Specification. - 100 mm Ø (pipe size) |
| 670 | Designing,Supplying, fixing, testing and commissioning of Y- strainer of ductile CI body flanged ends with stainless steel strainer for chilled/hot water circulation including insulation as specified. |
| 671 | Dia. 125mm |
| 672 | Dia 100mm |
| 673 | Designing, Supplying, laying, fixing, testing and commissioning of following nominal sizes of pre insulated chilled water plumbing inside the building / outside the building along the wall/ roof (with necessary supports/clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) pipe insulation shall be polyurethane foam with 36 kg/cu m minimum density, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/OF. The insulation shall completely fill the annular space between the service pipe and jacket and-shall be bonded to both, the service pipe & jacket. The minimum thickness of insulation shall be 30mm for pipes diameter less than 125mm & shall be 50mm for pipe diameter 125 to 300mm. The pipe cladding shall be with 24 gauge Aluminium sheet. Lock seam spiral Jackets for metallic jackets must be made on a spiral duct forming machine. The lock seam jackets should have zero leakage at the seams.Note:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 674 | 125 mm Ø Piping |
| 675 | 100 mm Ø Piping |
| 676 | 80 mm Ø Piping |
| 677 | 65 mm Ø Piping |
| 678 | 50 mm Ø Piping |
| 679 | 40 mm Ø Piping |
| 680 | 32 mm Ø Piping |
| 681 | 25 mm Ø Piping |
| 682 | Designing,Supplying, fixing, testing and commissioning of following dia valves, strainers, gauge in the chilled water plumbing duly insulated to the same specifications at factory/ site as the connected piping and adequately supported as per specifications.Designing,Supplying, fixing, testing and commissioning of duly insulated C.I. Butterfly valve (PN-16) with CI body SS disc, with integral or separate welded Flange /wafer type construction with EPDM coated disc with long pitch with protected out pipe insulation and PN 16 pressure rating for chilled circulation as specified. The valves above 150 mm dia shall be with geat box for operation. |
| 683 | 125 mm Ø |
| 684 | 100 mm Ø |
| 685 | 80 mm Ø |
| 686 | 65 mm Ø |
| 687 | 50 mm Ø |
| 688 | 40 mm Ø |
| 689 | Ball valves |
| 690 | 32 mm Ø |
| 691 | 25 mm Ø |
| 692 | Designing,Supplying, fixing, testing and commissioning of duly insulated Motorised Butterfly Valve with integral or separate welded flanges, CI body, SS disc, Nitrile rubber seal and O ring water type construction with manual override control/wheel(Complete with fittings, Nuts, Bolts & Gaskets (PN-16Rating). The actuator shall be IP 67 rated and BMS compatible. |
| 693 | 125 mm Ø |
| 694 | 100 mm Ø |
| 695 | Designing,Supplying, fixing, testing and commissioning of duly insulated CI Flanged Balancing valve (PN-16) with Flanges, EPDM coated disc with built-in measuring facility as per Specification. |
| 696 | Fully automatic balancing valve-125 mm Ø |
| 697 | Fully automatic balancing valve-100 mm Ø |
| 698 | Fully automatic balancing valve-80 mm Ø |
| 699 | Designing,Supplying, fixing, testing and commissioning of duly insulated Y- strainer of ductile CI Body flanged ends with stainless steel strainer |
| 700 | 125 mm Ø |
| 701 | 100 mm Ø |
| 702 | Designing,Supplying, fixing, testing and commissioning of duly insulated Plug valves - 25mm diameter Plug valves in dirt legs |
| 703 | Designing,Supplying, fixing, testing and commissioning of duly insulated Non return valve (PN-16 rating) with CI body with integral or separate welded Flange /wafer type construction with EPDM coated disc with long pitch with protected out pipe insulation and PN 16 pressure rating for chilled circulation as specified. |
| 704 | 125 mm Ø |
| 705 | 100 mm Ø |
| 706 | SITC of water pressure gauge (100 mm Ø) bourdon type with brass ball valve of 3/8\\" Ø and SS tubing, socket. Range (0-50) / (0-100) as required. |
| 707 | SITC of Mercury in glass industrial thermometer in SS-304 casing with 0.5C least count, range 0-50 C. Brass oil filled thermowell of 1/2\\" size |
| 708 | Designing,Supplying, Installation, Testing and commissioning of INSULATED PRESSURISED CLOSED WATER EXPANSION TANK suitable for total volume of water in chilled water circuit along with necessary accessories such as 2 Nos pumps (1working +1standby) with Pressure Transmitter and interconnecting Pipe & Isolating Valve complete with piping connections, safety relief valve, drain valve, pressure gauge, automatic air purging arrangement, etc. The tank shall be pre-charged. Expansion tank Shall be with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and 20 mm drain and charging valve connection to facilitate the on site charging of nitrogen in the tank. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The tank must be constructed in accordance with IS-STANDARD 2825-1969 suitable for 125 PSI working pressure. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures required for proper functioning of the complete hydronic system. The tank shall be duly painted in approved colour shall be complete with pressure switches and power distribution and control panel IP55 Control Panel, Pressure Transmitter, interconnecting piping & wiring. (tank capacity 5000 Lts)Chilled water closed vessel pressurized expansion tank as described above shall be duly insulated with 50 mm thick EPS insulating material and cladded with aluminium Sheet (20G) |
| 709 | Designing,Supplying,Installation, Testing and commissioning of Skid mounted water softening plant of 2000 LPH capacity with instruments panel,two sofetening feed pumps(1W+1S), MS pressure vessels,buffer tank,safety relief valve, drain valve, control valves,pressure gauges,associate pipings & valves up to make up water tank and from the make up water tank up to cooling towers with suitable rubber lining,chemical for dosing and all accessories to meet system requirements as per specifications |
| 710 | Designing, Supplying, installation , testing and commissioning of Centrifugal type Air separator with pot type strainer for flanged connection 150/125/100mm pipe line, automatic air purging arrangement etc. The design parameters for the air separator of efficiency 96-98 %. Suitable for PN10 rating, complete with super vent as required. and duly insulated with 50 mm thick EPS insulated material and cladded with aluminium sheet. |
| 711 | Supply, installation , testing and commissioning of 20mm Automatic Air Vent valve suitable to purge out the trapped air in the water pipe line complete as required. |
| 712 | Supply, installation , testing and commissioning of suitable Magnehelic guages with SS box and SS cover plate with necessary tubing for filters across AHU filter status, complete as required. |
| 713 | Supplying, fixing, testing and commissioning of medium class G.I. condensate drain pipes on wall/floor/roof of following size/diameters duly insulated with 9 mm thick closed cell nitrile rubber insulation in the form of pre-formed pipe sections and along with necessary supports/clamps, fittings such as bends, tees etc. adequately supported as per specifications and as required. |
| 714 | 50 mm Ø |
| 715 | 40 mm Ø |
| 716 | 32 mm Ø |
| 717 | 25 mm Ø |
| 718 | Designing,Supplying, Installation, Testing Balancing & Commissioning of G.S.S square/ rectangular factory fabricated ducting complete with gaskets, elbows, splitters, vanes, flanges, adjustable dampers,suitable supports/ hangers/clamps etc. as required for dehumidified air distribution of following thickness as per approved working drawings, specifications and requirement . |
| 719 | Thickness 1.25mm Sheet |
| 720 | Thickness 1.00mm Sheet |
| 721 | Thickness 0.80mm Sheet |
| 722 | Thickness 0.63mm Sheet |
| 723 | Designing,Supplying, Installation, Testing Balancing & Commissioning of 20 mm thick pre insulated ducting sheet having PUF density of 45 kg/Cum with 80 micron Aluminium facing on both side(class \\"O\\" fire cetified) complete with gaskets, elbows, splitters, vanes, adjustable dampers,suitable supports/ hangers/clamps etc. as per drawings and as required.Measurement shall be on outer face of duct surface. |
| 724 | Designing,Supplying and fixing of 25mm thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (class \\"O\\") insulation on duct after applying two coats of cold setting adhesive (CPR X compound). The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. |
| 725 | Designing,Supplying, installation, testing and commissioning of GI volume control duct damper complete with other accessories such as neoprene rubber gaskets,nut,bolts,screws linkages,flanges,locking arrangement,gear train,handle position indicator etc. as per specifications |
| 726 | Manual GI volume control damper |
| 727 | Motorised GI volume control damper with sensor and necessary control wire |
| 728 | Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in confirmation to IS and as per specifications complete etc. as required.. |
| 729 | Motorised fire damper |
| 730 | Actuator |
| 731 | Designing,Supplying, fixing, testing & commissioning of false ceiling type/box type HEPA terminal filter module with volume control damper,pressure sensing port etc. and s/f of following sizes H13 HEPA terminal filters with SS 304 perforated Grill,necessary SS screws/bolts and supports/clamps etc. as required |
| 732 | Terminal HEPA filter of size 1200 x600 mm |
| 733 | Terminal HEPA filter of size 600 x600 mm |
| 734 | Designing,Supplying, fixing, testing & commissioning of Return Air Riser Grills in SS 304 contruction with pre filters (G4) , SS dome bolts and louvers but without volume control dampers,complete as required |
| 735 | Designing,Supplying, fixing, testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers.as per specifications. |
| 736 | Designing,Supplying, , fixing, testing, commissioning of return air diffusers of powder coated aluminium, as per specifications. |
| 737 | Supplying, fixing, testing commissioning of Double layered Flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, Flexible connection shall be air tight & water proof and withstand high temperature application, non flammable and does not support combustion. Flexible connection shall be complete with flanges made out of 22G G.S.S sheet on both sides for connection to unit and duct complete with nuts, bolts etc. |
| 738 | Designing,Supplying, fixing, testing & commissioning of powder coated extruded aluminium section fresh air louvers in weather maker room with aluminium volume control dampers, bird screen etc completed as required. |
| 739 | Designing,Supplying and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminium sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications. |
| 740 | Designing,Supplying, installation, testing & commissioning of cubical type wall / floor mounted Distribution Panel suitable for 433 V, 3 Phase, 4Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having Suitable Amp capacity extensible type copper bus bars of high conductivity, SMC bus bar supports, with short circuit withstand capacity of 50kA with entire panel shall have a common copper earth bus of size 32x6mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of copper bus bars and control wiring with 2.5 sq.mm. PVC insulated FRLS copper conductor Single Core cable, cable alleys, cable gland plates in two half, i/c additional NO/NC contacts in all outgoing starters for automatic operation through BMS and providing & fixing following switch gears:- Incomer - A) 1 No. - 1000 Amps Four Pole, 50 KA, ACB with Microprocessor release with O/C, S/C & E/F protection release, with following:- B) 1 Set - Digital Ammeter with in built ASS, metering C.T.s \\"CAST RESIN\\" type, 15VA, and accuracy class-1of 1600/5A for measuring current in each phase. C) 1 Set - Digital Voltmeter with in built VSS, with 2Amp. Back up MCB. D) 1 Set - 3 Nos. Phase indication LED lamps with 2Amp back up MCB, Breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. |
| 741 | Bus Bar:-TPN copper extensible type main bus bars of minimum of 1000 A capacity (As per capacity of corresponding incoming / Bus couplers) , and auxiliary bus bars of suitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50kA . Outgoings:- Designing,Supplying and fixing following outgoing MCCB / MCB complete connection, inter-connection etc. with suitable size of solid links / wires (2A backup SP MCB) complete as required. (A) 3 Nos-320A, 50 KA TPN MCCB with Microprocessor release(3# Chiller 100TR) (B) 3 Nos- 160A 35 KA TPN MCCB ( AHU -1, AHU-2A, AHU -2B) (C) 1 No- 125A 35 KA TPN MCCB ( AHU -6) (D) 3 Nos- 63A 35 KA TPN MCCB ( AHU -3, AHU -4, AHU -5,) (E) 3 No- 40A 35 KA TPN MCCB ( TFA, DHU,VRF ) (F) 9No. - 63A 35 KA TPN MCB with Star delta starter and single phase preventor ( 3# Cond pump,3# sp,3# CT) (G)8Nos. - 25/32A 25 KA TPN MCB with DOL Stater and single phase preventor (3# PP,2# SWP ,2#ET & 2#sp) H) Each MCCBs shall be with following accessories (I) MCCB for over current & shortcircuit protection and breaking capacity of 25 kA,at 433V (Ics=ku for 1 second) (J) Extended Type front door operating handle, phase spreaders and phase barriers. (K) 1 set - Breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts as required. |
| 742 | Supplying & Laying/ fixing of following size XLPE insulated and PVC sheathed aluminium conductor armoured cable of 1.1 KV grade complete as required. (ISI Marked) ( in ground/in pipe/in duct/on surface/ on cable tray) |
| 743 | 3.5 x 185 sq.mm. ( 100TR chillers ) |
| 744 | 3.5 x 95 sq.mm. ( AHU 1, AHU 2A, AHU 2B,AHU-6) |
| 745 | 3.5 x 70 sq.mm. AHU 3, AHU 4 & AHU 5) |
| 746 | 3.5x 50 sq.mm. (TFA,DHU,VRF,) |
| 747 | 3.5x 35 sq.mm. (Condenser pump ,CT ) |
| 748 | 4 x 16 sq.mm. (PP,ET) |
| 749 | Supplying & Laying/ fixing of following size of FRLS PVC insulated flexible copper conductor cable of 1.1KV grade for power supply to VRF indoor unit i/c providing and laying of suitale size PVC conduit whereever required etc. as required. |
| 750 | 3C X 1.5 sq.mm |
| 751 | Supplying , installing ,laying/fixing of following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders,tee and bends etc. as required. |
| 752 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 753 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 754 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 755 | Supplying and laying 25 mm X 5 mm G.I strip in 40mm dia. G.I pipe from earth electrode including connection with G.I. nuts,bolts,springs washers,excavation and re-filling ect,.as required |
| 756 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 757 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 758 | 3.5 x 185 sq.mm. ( 100TR chillers ) |
| 759 | 3.5 x 95 sq.mm. ( AHU 1, AHU 2A, AHU 2B,AHU-6) |
| 760 | 3.5 x 70 sq.mm. AHU 3, AHU 4 & AHU 5) |
| 761 | 3.5x 50 sq.mm. (TFA,DHU,VRF,) |
| 762 | 3.5x 35 sq.mm. (Condenser pump ,CT ) |
| 763 | 4 x 16 sq.mm. (PP,ET) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail