| 1 | LED Panel light 2x2 ft. (System lumen efficacy≥105 <120 lm/Watt)S.I.T.C of 36 Watt Panel light 2x2 ft. of following body material & construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40°C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K /5700°K /6000°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating & Fixture shall be of relevant BIS standard & trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105<120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 2 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt )S.I.T.C of 10 Watt LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA & prismatic diffuser & construction as per IS:10322 with driver as per requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, Frequency 50/60 hz, Operating temp range -15°C to 40°C, internal surge protection of 2.5 KV with Short & Open circuit protection,THD <10%, P.F.≥0.95, IP20, CRI>80 , UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K /5700°K /6000°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating & Fixture shall be confirming to relevant BIS standards & trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 & <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)Powder coated die cast /Extruded aluminum Body including trim |
| 3 | LED Flood Light, powder coated pressure die cast aluminum (System lumen efficacy ≥120 & <135 lm/Watt)S.I.T.C. of 100 Watt Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage:Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15°C to 50°C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD <10% as per IEC 61000-3-2, P.F.≥0.95, IP-66,IK-10, CRI >80, under voltage & over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg120deg as per the application & the project requirement deg. suitable tiltable fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K /5700°K /6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating & Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 & <135 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 4 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 5 | Supplying & fixing following way, horizontal type three pole & neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, inter-connections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 6 | 4 way (4 + 12), Double door |
| 7 | 6 way (4+18), Double door |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 9 | 5/6 A switch |
| 10 | 15/16 A switch |
| 11 | 3 pin 5/6 A socket outlet |
| 12 | 6 pin 15/16 A socket outlet |
| 13 | Supplying & fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 14 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 15 | 2 Module (75 mm X 75 mm) |
| 16 | 3 Module (100mmX75mm) |
| 17 | 6 Module (200mmX75mm) |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | Single pole |
| 20 | Triple pole and neutral |
| 21 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 22 | Providing & Fixing of following rating & breaking capacity Pole MCCB with thermomagnetic release & terminal spreaders in existing cubicle panel board i/c drilling holes in cubicle panel, making connections etc. as required. |
| 23 | 400 A, 50KA, FP MCCB |
| 24 | Supplying & Fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 25 | Supplying & Fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess i/c cutting the wall & making good the same in case of recessed conduit as required. |
| 26 | 20 mm |
| 27 | 25 mm |
| 28 | Supply of following sizes FRLSH PVC insulated & PVC round sheathed Multi Core Annealed bare Copper stranded Conductor (flexible) industrial Cables for 1100 Volt grade Conforming to IS 694:2010 as & when required as directed by E-I-C: |
| 29 | 3 C x 2.5 sqmm |
| 30 | 3 C x 4.0 sqmm |
| 31 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 32 | 2 x 1.5 sq.mm + 1 x 1.5 sq.mm Earth Wire |
| 33 | 2 x 2.5 sq.mm + 1 x 2.5 sq.mm Earth Wire |
| 34 | 2 x 4 sq.mm + 1 x 4 sq.mm Earth Wire |
| 35 | Supply of following sizes XLPE Armoured Cables with ALUMINIUM Conductor 650/1100V. Grade confirming to IS:7098 (Part-1) 1988 with upto date amendments complete as required as directed by E-I-C: |
| 36 | 3.5 X 185 sqmm |
| 37 | 3.5 X 50 sqmm |
| 38 | Laying of one number PVC insulated & PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required. |
| 39 | Above 35 sq.mm & upto Upto 95 sq.mm |
| 40 | Above 95 sq.mm & upto 185 sq.mm |
| 41 | Laying & fixing of one number PVC insulated & PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 42 | Above 35 sqmm & Upto 95 sqmm (clamped with 25X3 mm MS flat clamp) |
| 43 | Above 95 sq. mm and upto 185 sq. mm (clamped with25/40x3mm MS flat clamp) |
| 44 | Laying of one number PVC insulated & PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonary open duct as required. |
| 45 | Above 35 sq. mm & Upto 95 sq. mm |
| 46 | Above 95 sq. mm & upto 185 sq. mm |
| 47 | Laying & Fixing of one number PVC insulated & PVCsheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 48 | Above 35 sq.mm and Upto 95 sq.mm (clamped with 25 x 3 mm MS flat clamp) |
| 49 | Above 95 sq.mm and upto 185 sq.mm (clamped with 25 / 40 x 3mm MS flat clamp) |
| 50 | Supplying & laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting & cutting, jointing etc.direct in ground (75 cm below ground level) i/c excavation & refilling the trench but excluding sand cushioning & protective covering etc., complete as required. |
| 51 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 52 | Providing, Laying & Fixing of following dia G.I. pipe (medium class) in ground complete with G.I. fittings i/c trenching (75 cm deep)and re-filling etc as required. |
| 53 | 100 mm dia |
| 54 | Earthing with G.I. earth pipe 4.5 mtr. long, 40 mm diai/c accessories & providing masonary enclosure with cover plate having locking arrangement & watering pipe etc. with charcoal/ coke & salt as required. |
| 55 | Supplying & laying 25mm x 5mm G.I strip at 0.50 metrebelow ground as strip earth electrode i/c connection / terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 56 | Providing & fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 57 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 58 | Providing & fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cableas required. |
| 59 | Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick i/c accessories & providing masonary enclosure with cover plate having locking arrangement & watering pipe of 2.7 metre long etc. with charcoal/ coke & salt as required. |
| 60 | Supplying & laying 25mm x 5mm copper strip at 0.50 metre below ground as strip earth electrode, i/c connection / terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping & with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 61 | Providing & fixing 25mm x 5mm copper strip in 40mm dia G.I. pipe from earth electrode i/c connection with brass nut, bolt, spring, washer excavation & re-filling etc. as required. |
| 62 | Providing & fixing 25mm x 5mm copper strip on surface or inrecess for connections etc. as required. |
| 63 | Supply of 2.0 TR BEE-5 star rating wall mounted Inverter Split type Air Conditioning Units operating on eco-refrigerant (R32 preferrably), copper condenser & copper evaporator coils suitable for operation on 220-240 V single phase 50 Hz supply having all safety features, air filters, cordless remote for operation etc. incl. all accessories such as std. length copper pipe (not less than 3 mtrs), drain pipe, power cable, control cable etc. having compressor warranty of minimum 05 years complete as required. |
| 64 | Installation, Testing & Commissioning of 2.0 TR Split AC as per site conditions & connecting the Indoor & Outdoor unit with standard copper pipe of 3 mtrs. approx, brazing, connecting the drain pipe with indoor unit etc. complete as required as directed by E-I-C. |
| 65 | Supplying & fixing of copper pipe (1/2\\", 1/4\\") for suction / liquid line and connecting the same with existing copper pipe, brazing etc. of indoor / outdoor unit along with insulation, fixing insulation with vinyl tape etc. complete as required as per site requirement and as directed by E-I-C. |
| 66 | Supply & Fixing of Drain Pipe with insulation of suitable length to connect with existing drain pipe of AC complete as required |
| 67 | Supplying & Fixing of outdoor wall brackets so as to mount the outdoor units of Split AC on wall / floor complte as required with nut, bolts etc. as directed by E-I-C. |
| 68 | Supplying & applying of preventive coating on Copper pipes (condenser / evaporator) to prevent refrigerant leakage from 2 TR Split Acs complete as required as directed by E-I-C. |
| 69 | LT PANELS.I.T.C. of cubicle type LT panel (TTA) indoor type, IP54 protection, 50 KA suitable for 415V, 3 Phase, 4 wire 50 Hz AC supply system fabricated in compart-mentalized design from CRCA sheet steel of 2mm thick for frame work & covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade having 4P Aluminium alloy bus bars of high conductivity, SMC bus bar supports with short circuit withstand capacity of 50 KA for 1 sec, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. Bus bars & control wiring with suitable size of PVC insulated copper conductor, cable alleys, cable gland plates in two half i/c providing following: |
| 70 | (A) INCOMERi) 02 Nos. MCCB, 300A, 35 kA, Four Pole with micro-processor based (LSING) release having Over Current, Short Circuit, Earth Fault Protection (Ics=Icu) for both incomers.ii) 01 No. MCCB, 300A, 35 kA, Four Pole with micro-processor based (LSING) release having Over Current, Short Circuit, Earth Fault Protection (Ics=Icu) for bus coupler. Each MCCB above shall be provided with:i) 16 Parameter Multifunction digital meter to read A, V, KVA, KW, KVAR, KVAH, Hz, P. F & THD etc. The MFM to be duly equipped with RS-485 Port on both the incomer MCCBs.ii) OFF/ON/Trip indicating LED lights with 2A SP MCBiii) 1 Set Extended Rotary operating mechanism & terminal extension spreaders for all MCCBs.iv) 1-Set of LED Phase Indicating Lights R,Y,B with 2A SP MCB for protection.(B) BUS BARS4 Nos 400 A Electrolytic Aluminium Bus- Bars of equal cross-section.(C) Accessories for Electrical Inter-Lockingi) Electrical interlocking arrangement as per drawing approved by E-I-C & technical specifications among 2 nos. Incomers from Main LT Panel & 1 nos. Bus coupler i/c inter-connections etc. as required. |
| 71 | (D) OUTGOINGSi) 08 Nos. MCCB, 200A, 35 kA, Four Pole with micro--processor based (LSING) release having Over Current, Short Circuit, Earth Fault Protection (Ics=Icu).Each Outgoing MCCB above shall be provided with:i) 16 Parameter Multifunction digital meter to read A, V, KVA, KW, KVAR, KVAH, Hz, P.F & THD etc. The MFM to be duly equipped with RS-485 Port.ii) OFF/ON/Trip indicating LED lights with 2A SP MCBiii) 1 Set Extended Rotary operating mechanism & terminal extension spreaders for all MCCBs.iv) 1-Set of LED Phase Indicating Lights R, Y, B with 2A SP MCB for protection. |
| 72 | Execution of items of work as per requirement of site from the CPWD Schedule of Rates (DSR E&M-2022) as per CPWD Specification complete as required (total amount of Rs.3,00,000/- (excl. GST) is kept for DSR Items 2022). Note:- Bidder may refer Clause 32 of e-NOTICE INVITING TENDER before quoting against this item. Please Enable Macros to View BoQ information |