| 1 | Water proofing |
| 2 | Grading roof for water proofing treatment with:Cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 3 | Providing and laying APP (Atactic Polypropylene Polymer) modified prefabricated five layer, 3 mm thick water proofing membrane, black finished reinforced with glass fibre matt consisting of a coat of bitumen primer for bitumen membrane @ 0.40 litre/sqm by the same membrane manufactured of density at 25°C, 0.87 - 0.89 kg/litre and viscocity 70 - 160 cps. Over the primer coat the layer of membrane shall be laid using butane torch and sealing all joints etc., and preparing the surface complete. The vital physical and chemical 1155 SUB HEAD : 14- REPAIRS TO BUILDING parameters of the membrane shall be as under : Joint strength in longitudinal and transverse direction at 23°C as 350/300 N/5 cm. Tear strength in longitudinal and transverse direction as 60/80N. Softening point of membrane not less than 150°C. Cold flexibility shall be upto -2°C when tested in accordance with ASTM, D - 5147.The laying of membrane shall be got done through the authorised applicator of the manufacturer of membrane :3 mm thick |
| 4 | Landscape Works |
| 5 | Providing and Laying Landscaping of outdoor area with buffalo grass and small plants with all necessary levelling and filling as required. |
| 6 | Plantation of Trees, Shrubs, and Hedge at site i/c watering and removal of unsaverieable material?s as per direction of officer in charge (excluding cast of plant & water )Cost of plantation per trees plants (for 100 nos.=427.45/100) |
| 7 | Plantation of Trees, Shrubs, and Hedge at site i/c watering and removal of unsaverieable material?s as per direction of officer in charge (excluding cast of plant & water )Cost of plantation per Shrubs plants (for 200 nos.=427.45/200) |
| 8 | Plantation of Trees, Shrubs, and Hedge at site i/c watering and removal of unsaverieable material?s as per direction of officer in charge (excluding cast of plant & water )Cost of plantation per Hedge plants (for 300 nos.=427.45/300) |
| 9 | Supplying of Flowering Shrubs (Heliconiya st. Vincent red, Ixora bush, Cana durf etc..) |
| 10 | Joinery |
| 11 | Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge |
| 12 | Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar |
| 13 | 12 mm cement plaster of mix:1:6 (1 cement : 6 fine sand). |
| 14 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 15 | Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer |
| 16 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 17 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).Second class teak wood |
| 18 | Providing and fixing panelled or panelled and glazed shutters for shutters for doors, windows and clerestory windows, including ISI marked M.S. pressed butt hinges bright finished of required size with necessery screws, excluding panelling which will be paid for separately, all complete as per direction of Engineer - in-charge.Second class teak wood35 mm thick shutters |
| 19 | Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:Second class teak wood |
| 20 | Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 21 | Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. ( Shutter area to be measured) |
| 22 | Providing and fixing CP Brass Handle 450mm in all types of doors with the necessary fittings and arrangements all complete. |
| 23 | Providing and fixing stainless steel catcher of approved quality in doors, including fixing with necessary screws etc. Complete |
| 24 | Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 25 | Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality, with necessary screws etc complete as per direction of Engineer- in- charge. |
| 26 | French spirit polishing:Two or more coats on new works including a coat of wood filler |
| 27 | Repair work |
| 28 | Dismantling barge boards including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in- Charge |
| 29 | Providing and fixing double scaffolding system (cup lock type) on the exterior side, upto seven story hight made with 40 mm dia. M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staricase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required location with essential safety features for the workmen etc. complete as per directions and approval of Engineer- in Charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment will be made once irrespective of duration of scaffolding. Note:- This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done . |
| 30 | Providing and fixing 160 mm standard width PVC rain water gutter pipe with clamp and all necessary accessories required for supporting to wall inculding cost of labour and making necessary connection with rain water pipes as specified and as directed by engineer in charge |
| 31 | Providing and fixing fiber glass asphalt roofing shingles of min thickness 4mm and having UL class A fire rating and possess a wind resistance for wind speeds upto 170 km/hr. The shingles should have been treated for algae resistance and should possess zero water absorption ensuring complete water proofness. The shade and patter of the shingles to be as per design or as per the instructions of the engineer in charge. |
| 32 | DB and Switchgear |
| 33 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 34 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 35 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)6 Way (4+18), Double door |
| 36 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 100 A, 16KA |
| 37 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 38 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 39 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 40 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 41 | Supply and fixing following in the MCCB/MCB DB complete with connections, testing and commissioning etc, as required.40 Amp TP MCB |
| 42 | Supply and fixing following in the MCCB/MCB DB complete with connections, testing and commissioning etc, as required.63 Amp TP MCB |
| 43 | Wiring |
| 44 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 45 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 46 | Landscape Lighting and External Ambient Lighting |
| 47 | Supply & Installation of LED Bollard 12W , Integral type bollard cylindrical/Conical Shape, Die cast aluminum Housing , Dome shape , Top cover fixed with , Cylindrical/ Conical Shape acrylic cover Opal White Poly Carbonate Diffuser. SMD LED of 1 to 3 Watt each assembled on single MCPCB, Led Lamp lumens output with efficacy >80 lm/W, Rated Current < 0.050 A, Lumen Output > 800 Lm, Approx. Weight< 2.0Kg , Driver PF> 0.95 Luminaire having color temp up to 6500K & 50,000 Burning Hours. Life with minimum @ L 70, The color rendering index of LED light should be more than 70. Luminaire, Conical Surface flux @ 120 Degree is > 80 L/w, comprises of driver PF >0.95 & Surge Protection 3KV , IP65 Protection , Submission with Technical Data Sheet , LM80 Report, Warranty letter from Manufacturers,Connection Wire, Testing etc. to complete the job having base plate with holes for direct mounting. Bollard LED 12 Watt cylindrical shape height > 600mm, Color Temp 3000-6000k ±10%, Product Dimension Minimum- L- 815mm, D- 140mm (± 10%) |
| 48 | Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 49 | Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3 core 1.5 sq mm |
| 50 | Supply, Installation, Testing and Commissioning of IP 66 Facade Lighting including accessories with following specifications.Wattage : 200 - 240W, Input Voltage/Current : DC 24V / 10000 mA? Electrical Class : III Class, Power Factor (Min) : 0.9? Harmonic Distortion : < 10%, Driver/power unit : External? Beam Angle : 25°, Optional Beam Angle : 15° , 45°? Field Angle : 32°, LED Source : SMD Based? Colour Temperature : RGBW, CRI : > 80? Lumens/W : > 55, Net Luminous Flux : 13200? SDCM : < 3, LED Hours Burning life : 50,000? Control Option : DmX512/Auto, DmX Channels : 4 CH? Dimension : 420 x445x230mm, Ingress Protection : IP66 Rated? Body Housing : Aluminium Die Casted, Body Colour : Black / Grey? Mounting Type : Yoke Mount, Impact Resistance : IK08? Connector : M/F Cable Mount, Working Temperature : +55° ~ -30° |
| 51 | Supply and Installation of 3 - 7W IP 65, garden spike LED lamp including accessories as per the direction of Engineer in charge. |
| 52 | SITC of skirting light fitting with white LED 3 module along with suitable size modular metal box with inner and outer plates with all accessories. |
| 53 | LT Panel, Cabling and Termination |
| 54 | Supply, Installation, Testing & Commissioning of Outdoor Type Street Light Feeder Pillar, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, free standing, floor mounting, dust and vermin proof, powder coated, compartmentalized, provision for timer, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket, Suitable Contactors etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification.Incomer - 100A, FP isolator, Bus bar - 1 Set of 100 A TPN busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. Outgoing - (1) 32A, SPN MCB - 8 nos |
| 55 | Supplying, installation, testing & commissioning of cubical type LT panel (Indoor type) suitable for 415V, 3 phase, 4 Wire 50 Hz AC supply system , fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers complete with powder coating in approved shade, having suitable capacity TPN Copper bus bars, base frame of MS channel 75 mm x 50 mm size, panel shall have common copper earth bar of size 25mm x 5 mm in cable alleys with 2 Nos. earth stud, cable alleys, removable gland plates, including providing following switch gears and as required. Incoming - a)1 No. 250Amp 4 pole Microprocessor based MCCB, 36 kA @ 415V,Ics=100% Icu along with extended rotary operating handle, Spreader Terminal, Ics=100% Icu -1 Set b)Combined Digital type display meter suitable for measuring AC voltage, Current, KWH, KW,PF ,Frequency etc.-1No c)3 Nos CT's of ratio 300 / 5 Amps for metering d)3 Nos. phase indication LED lamps with 2 Amp back up HRC fuse / MCB - 1 set. II) Bus Bars :TPN Tinned Copper bus bars of minimum of 300 Amps capacity with heat shrinkable colored sleeves and i/c DMC/ SMC bus bars supports at required intervals complete etc. Outgoings :a)125 Amp 4 pole MCCB, @ 415V and 25 kA, with thermal magneticrelease,extendedrotary operating handle, Spreader Terminal, Ics=100% Icu -4 No b) 100 Amp 4 pole MCCB, @ 415V, 25kA, with thermal magnetic release and rotary operating handle, Spreader Terminal, Ics=100% Icu. - 4 Nos (Note: All MCC Bs shall be with spreader terminals) IV) EARTH 2 No. Tinned copper Earth strip of size 25 x 6 mm for full width of board with 2 termination points. LT panel(Main panel) complete as above. |
| 56 | Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).2 core 4 sq mm |
| 57 | Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3 core 6 sq mm |
| 58 | Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3 core 10 sq mm |
| 59 | Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 240 sq mm |
| 60 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm) |
| 61 | Street Lights |
| 62 | Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters |
| 63 | Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 64 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.Above 4.5 metre and upto 6.5 metre |
| 65 | Supply and Installation of SMC junction box with suitable connectors 140X140X95MM |
| 66 | Earthing |
| 67 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 68 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 69 | Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 70 | Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) |
| 71 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re- filling etc. as required. |
| 72 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 73 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) Please Enable Macros to View BoQ information |